– 46 –
To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known
Check the position during operation stop.
(Stop operation of the set.)
1
Push
+
buttons simultaneously for
4 seconds or more.
After a while, the display part flashes and the
display appears as shown below.
In this time, the position can be checked because
fan of the indoor unit operate.
• For the group control, the indoor UNIT No. is
displayed as [
] and fans of all the indoor
units in the group control operate.
Check the displayed CODE No. is [
01
].
• When the CODE No. is other than [
01
], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the remote
controller is not accepted for approx. 1 minute.)
2
In the group control, every time
button is pushed, the indoor UNIT No. in the
group control is displayed in order.
In this time, the position of the indoor unit can be
confirmed because only fan of the selected indoor
unit operate.
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
3
After confirmation, push
button to return
the mode to the usual mode.
When
button is pushed, the display disappears
and the status becomes the usual stop status.
(When
button is pushed the operation from the
remote controller is not accepted for approx. 1
minute.)
2
1,3
1
(* Display changes according to
the model No. of indoor unit.)
8 °C operation (SDI 4series
and DI 4series only)
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
1
Push
+
+
buttons simultaneously
for 4 seconds or more when the air
conditioner is not working.
After a while, the display part flashes as shown
below. Check the Displayed CODE No. is [
10
].
• When the CODE No. is other than [
10
], push
button to erase the display and repeat
procedure from the first step.
(After pushing
button, operation of the
remote controller is not accepted for approx. 1
minute.)
2
Every time
button is pushed, the
indoor unit No. in the group control is
displayed in order. Select the indoor unit of
which setup is changed. In this time, the
position of the indoor unit of which setup is
changed can be confirmed because fan of
the selected indoor unit operate.
3
Specify CODE No. [d1] TEMP.
/
buttons.
4
Select SET DATA [0001] TIME
/
buttons.
5
Push
button.
In this time, the setup finishes when the
display changes from flashing to lighting.
6
Push
button.(Setup is determined.)
When
button is pushed, the display
disappears and the status becomes the usual stop
status. (When
button is pushed the operation
from the remote controller is not accepted for
approx. 1 minute.)
SET DATA
8 °C Operation setting
0000
None
(Factory default)
0001
8 °C Operation setting
(* Display changes according to
the model No. of indoor unit.)
91-EN
92-EN