How to cancel louver lock
Set the wind direction to “
0000
” of the louver lock
setup procedure above.
• When the setting is canceled,
goes out.
Other operations are the same as those in
“How to set up louver lock (No swing)”.
How to set up power
saving mode
1. Push
button for at least four seconds
when the air conditioner is not working.
flashes.
Indicates CODE No. “C2.”
2. Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit numbers
change as follows:
The fan of the selected unit runs and the
louvers start swinging.
3. Adjust the power save setting by pushing TIME
buttons.
Each push of the button changes the power
level by 1% within the range from 100% to 50%.
* The factory setting is 75%.
4. Determine the setting by pushing
button.
5. Push
button to complete the setting.
Remote controller switch
monitoring function
This function is available to call the service
monitor mode from the remote controller during a
test run to acquire temperatures of sensors of the
remote controller, indoor unit, and outdoor unit.
1. Push
and
buttons simultaneously for at
least 4 seconds to call the service monitor
mode.
The service monitor indicator lights up and the
header indoor unit number is displayed first.
CODE No.
is also displayed.
2. Pushing TEMP.
buttons, select the
number of sensor, etc. (CODE No.) to be
monitored. (See the following table.)
3. Pushing
(left side of the button), select
an indoor unit to be monitored. The sensor
temperatures of indoor units and their outdoor
unit in the control group are displayed.
4. Push
button to return to the normal display.
0000
Setting data
Unit No.
1-1
Unit No.
1-2
Unit No.
1-3
Unit No.
1-4
Setting of power level in
power saving mode
Indoor unit data
CODE No.
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
F3
Indoor unit fan cumulative operating
hours (x1 h)
F8
Indoor unit discharge air temperature
Outdoor unit data
CODE No.
Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge air temperature
(TD)
63
Compressor intake air temperature
(TS)
64
—
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
F1
Compressor cumulative operating
hours (x100h)
1
3
4
2
26-EN