– 64 –
Ta
(˚C)
F4
F5
F5
47
42
No.
6
Item
Air speed
selection
(Continued):
In case of 4-way
Discharge
Cassette type
Outline of specifications
3) In heating operation, the mode changes to [UL] if thermostat
is turned off.
4) If Ta
≥
25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after Tc
entered in E zone of cool air discharge preventive control
(Item 7).
5) In automatic cooling/heating operation, the revolution
frequency of (HH) is set larger than that in the standard
cooling/heating operation.
However the revolution
frequency is restricted in the
automatic heating operation as
shown in the following figure.
6) Self-clean operation
When performing self-clean operation after stopping the
cooling operation, the mode becomes [UL] (210 rpm).
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
SM56
SM80
SM110
SM140
SM160
Revolution speed (rpm)
610
630
700
700
700
550
590
670
670
670
500
530
660
660
660
450
470
640
650
650
400
450
620
640
640
390
440
610
630
630
370
410
550
560
580
350
380
490
490
530
340
370
480
480
520
330
350
450
460
490
320
330
400
430
450
310
320
400
420
440
250
250
300
300
300
Item code
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard
Type 1
Type 3
Type 6
0
1
3
6
OFF/OFF
ON/OFF
OFF/ON
ON/ON
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
HH
HH
HH
HH
HH
HH
H+
H+, H H+, H
H+, H H+, H
L+, L
L+, L
H+
HH
H
HH
H
L+
L+
H+
H+
L
L
H
L+
H
L+
L
L+
L
L+
L
L
UL
UL
UL
UL
Remarks
Selection of high
ceiling type
Item code:
[5d] or selection of
high ceiling on P.C.
board SW501
However only when
the high ceiling
selection is set to
[Standard]
[Self-clean
] is
displayed.