Group control for system of multiple units

One remote controller can control maximum 8 indoor units as a group.

Group control in single system

• For wiring procedure and wiring method of the individual line (Identical refrigerant line) system, follow to 

“Electrical connection”.

• Wiring between lines is performed in the following procedure.

 

Connect the terminal block (A/B) of the indoor unit connected with a remote controller to the terminal blocks (A/
B) of the indoor units of other indoor units by wiring the inter-unit wire of the remote controller.

• When the power supply has been turned on, the automatic address setup starts and which indicates that address 

is being set up flashes on the display part in about 3 minutes. During setup of automatic address, the remote 
controller operation is not accepted.

Required time up to the finish of automatic addressing is approx. 5 minutes.

NOTE

In some cases, it is necessary to change the address manually after setup of the automatic address according to the 
system configuration of the group control.
• The follow mentioned system configuration is a case when complex systems in which systems of the simultaneous 

twin and simultaneous triple unit is controlled as a group by a remote controller.

(Example) Group control for complex system

The above address is set by the automatic addressing when the power is turned on. However, line 
addresses and indoor addresses are set randomly. For this reason, change the setting to match line 
addresses with indoor addresses.

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Remote controller

Finish of address setup by power-ON

(Max. 8 units)

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

Outdoor unit

Line system

Indoor No.

After setup of 

automatic 

address

(Example of random 

setup)

After setup 

change of 

manual address

(Example of address setup change)

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Line address

Group address

Indoor address

Address: 1-1-1

Address: 2-1-2

Address: 2-2-2

Address: 1-1-2

Address: 2-1-2

Address: 3-3-1

Procedure 

example 1

<Single system> <Twin system>

<Triple system>

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Remote controller

Address: 3-1-2

Address: 3-2-2

Address: 3-3-2

Address: 3-1-2

Address: 2-2-2

Address: 1-2-2

[Procedure example]

Manual address setup procedure

While the operation stops, change the setup.
(Stop the operation of the unit.)

1

Push 

 + 

 + 

 buttons simultaneously 

for 4 seconds or more. After a while, the 
display part flashes as shown below. Check 
the displayed CODE No. is [10].

• When the CODE No. is other than [

10

], push 

 

button to erase the display and repeat 
procedure from the first step. 

 

(After pushing

 

 

button, operation of the 

remote controller is not accepted for 
approx. 1 minute.) 

 

(For a group control, No. of the firstly displayed 
indoor unit becomes the header unit.)

2

Every time 

 button is pushed, the 

indoor UNIT No. in the group control is 
displayed in order. Select the indoor unit of 
which setup is changed.

In this time, the position of the indoor unit of which 
setup is changed can be confirmed because fan of 
the selected indoor unit operate.

3

1) Specify CODE No. [

12

] with TEMP. 

 / 

 

buttons. 

 

(CODE No. [

12

]: Line address)

2) Change the line address from [

3

] to [

2

] with 

TIME  

/  

buttons.

3) Push  

button.

 

In this time, the setup finishes when the display 
changes from flashing to lighting.

4

1) Specify CODE No. [

13

] with TEMP. 

 / 

 

buttons. 

 

(CODE No. [

13

]: Indoor address)

2) Change the indoor address from [

3

] to [

2

] TIME 

 / 

 buttons.

3) Push  

button.

 

In this time, the setup finishes when the display 
changes from flashing to lighting.

2,6

1

7

3

-1, 

4

5

6

 -1, 
 -1,

7

3

 -3, 

4

 -3, 

3

 -2, 

4

 -2, 

5

 -2

5

 -3, 

(* Display changes according to 

the model No. of indoor unit.)

Indoor unit No. before setup change is displayed.

Indoor unit No. before setup change is displayed.

39-EN

40-EN

Содержание RAV-RM1101CTP-E

Страница 1: ...Indoor Unit Model name Ceiling Type For commercial use English AIR CONDITIONER SPLIT TYPE Installation Manual RAV RM401CTP E RAV RM561CTP E RAV RM801CTP E RAV RM1101CTP E RAV RM1401CTP E R32 or R410A ...

Страница 2: ...l describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit For precaution for safety follow the Installation Manual attached to the outdoor unit ADOPTION OF R32 or R410A REFRIGERANT This Air Conditioner has adopted a refrigerant HFC R32 or R410A which does not destroy the ozone layer Be sure to check the r...

Страница 3: ...ho has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to do the refrigerant handling and piping work...

Страница 4: ...ng to install the air conditioner read through the Installation Manual carefully and follow its instructions to install the air conditioner Only a qualified installer 1 or qualified service person 1 is allowed to do installation work Inappropriate installation may result in water leakage electric shock or fire Do not use any refrigerant different from the one specified for complement or replacemen...

Страница 5: ...rotection from falling objects Do not use the refrigerant other than R32 or R410A For the refrigerant type check the outdoor unit to be combined The refrigerant used by this air conditioner follow to the outdoor unit The air conditioner must be transported in stable condition If any part of the product is broken contact the dealer When the air conditioner must be transported by hand carry it by tw...

Страница 6: ...ent If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or hoist at installation of them Refrigerant piping Install the refrigerant pipe securely during the installation work before operating the air conditioner If ...

Страница 7: ... the places where the wire is extended may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and installation manual Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and ...

Страница 8: ...p down work shut down the compressor before disconnecting the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION This Air Conditioner has ado...

Страница 9: ... to be generated the plastic parts to be damaged the heat insulators to peel off and other such problems to result Locations where vapors from food oils are formed such as kitchens where food oils are used Blocked filters may cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result Locations near obstructions such...

Страница 10: ...l Possible installed ceiling height Up to 4 0 m RM110 RM140 m 3 4 o t p U Model SET DATA Standard Factory default Up to 3 5 m Up to 3 5 m 0000 3 0 0 0 m 3 4 o t p U m 0 4 o t p U 1 g n i l i e c h g i H 250 or more 250 or more 500 or more A p p r o x 8 m 4 Installation CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury Do not put a heavy article...

Страница 11: ...unit receives a signal surely and then install it Wireless type Keep 1 m or more from the devices such as television stereo Disturbance of image or noise may generate Wireless type Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 8 pieces Installation pattern Ceiling surface Wall face 90 110 120 150 Additional hole required when Drain Up Kit is used Ø100 Lateral side of chassis Pipe hole on top f...

Страница 12: ...n out from the rear side Grooves Groove Side panel Right Groove Side panel Left side Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the separately sold Elbow Piping Kit Installation of indoor unit Preparation before holding down main unit Confirm the presence of the ceiling material beforehand because the fixing method of hanging ...

Страница 13: ...de the area where the pipe connects to the indoor unit with proper heat insulation Improper heat insulation will cause condensation to form The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds Restrict the length of the traversing drain pipe to 20 meters or less For a long ...

Страница 14: ... right Push in the plug of which end is not sharp up to the end Drain pipe NO GOOD Refrigerant pipe Drain pipe Drain pan Attached drain hose Confirm that soft hose is pushed in up to the end of the drain pan Fit the attached hose band to the end of the hose lay down the knob and then tighten hose band 10 to 15 mm 10 to 15 mm Fit the attached hose band to the end of the hose with both of the two kn...

Страница 15: ...e length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cycle malfunction Work using double spanner RM40 RM56 RM80 RM110 RM140 Ø15 9 Ø9 5 IMPORTANT 4 POINTS FOR PIPING WORK 1 Reusable mechanical connectors and flared joints are not allowed indoors When mechanical connectors are reused indoors sealing parts shall be re...

Страница 16: ...ling them Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulting in an accident Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes System interconnection wires specifications For power supply specifications follow the Installation Manual of outdoor unit The power of the in...

Страница 17: ...or side Remote controller inter unit wiring Indoor side Triple Double twin Indoor power inter unit wiring Indoor power inter unit wiring Outdoor side Remote controller Remote controller wiring Indoor side System interconnection wires Wire connection REQUIREMENT Connect the wires matching the terminal numbers Incorrect connection causes a trouble Pass the wires through the bushing of wire connectio...

Страница 18: ...be changed using the wireless remote controller sub remote controller or remote controller less system for central remote controller only Therefore install the wired remote controller to change the settings Basic procedure for changing settings Change the settings while the air conditioner is not working Stop the air conditioner before making settings CAUTION Set only the CODE No shown in the foll...

Страница 19: ...o 4 0 m Up to 4 3 m 0003 SET DATA SW501 1 SW501 2 0000 Factory default OFF OFF 0003 OFF ON SW501 2 MCU IC501 SW501 1 Filter sign setting According to the installation condition the filter sign term Notification of filter cleaning can be changed Follow to the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 3 specify 01 For the SET DATA in Procedure 4 select the SET DATA of filter...

Страница 20: ...coil temperature TE 61 Outside air temperature TO 62 Compressor discharge temperature TD 63 Compressor suction temperature TS 64 65 Heatsink temperature THS 6A Operating current x1 10 F1 Compressor cumulative operating hours x100 h Group control Simultaneous twin triple or double twin system A combination with an outdoor unit allows simultaneous ON OFF operation of the indoor units The following s...

Страница 21: ...ress Example of random setup After setup change of manual address Example of address setup change Outdoor unit Indoor unit Indoor unit Indoor unit Line address Group address Indoor address Address 1 1 1 Address 2 1 2 Address 2 2 2 Address 1 1 2 Address 2 1 2 Address 3 3 1 Procedure example 1 Single system Twin system Triple system Outdoor unit Indoor unit Indoor unit Indoor unit Remote controller ...

Страница 22: ... push button to erase the display and repeat procedure from the first step After pushing button operation of the remote controller is not accepted for approx 1 minute 2 In the group control every time button is pushed the indoor UNIT No in the group control is displayed in order In this time the position of the indoor unit can be confirmed because only fan of the selected indoor unit operate For a...

Страница 23: ... run push button to stop a test run Display part is same as procedure 1 5 Push button to cancel release from the test run mode TEST disappears on the display and the status returns to a normal 2 4 3 1 5 Wireless remote controller NOTE Be sure to operate the unit following the instruction manual Do not run the air conditioner in forced cooling mode for a long time since it overloads the air conditi...

Страница 24: ...cratches and remove them or apply rustproof treatment if necessary As a general rule when an indoor unit is operated for 8 hours or more daily clean the indoor unit and outdoor unit at least once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor unit...

Страница 25: ...Serial communication error between indoor unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote contro...

Страница 26: ...rge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power wire may be connected incorrectly Check open phase and voltages of the power supply Entire stop P07 ALT Heat sink overheat Outd...

Страница 27: ... air conditioner has a history of the compressor failing and being replaced When discolored oil a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other ...

Страница 28: ...1115652999 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Отзывы: