No.
19
20
21
Item
DC motor
Self-clean operation
(Dry operation)
Save operation
Outline of specifications
1) The motor operates according to the command from the
indoor controller.
Notes)
• When the fan rotates while the air conditioner stops due to
entering of outside air, etc, the air conditioner may operate
while the fan motor stops.
• When a fan lock is found, the air conditioner stops, and an
error is displayed.
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following
three self-clean operations are performed.
2) During operation of self-clean,
lights on the wired
remote controller screen. However the operation lamp
(Green LED) goes off.
3) To stop the self-clean operation, push twice the
[ON/OFF] button on the remote controller continuously.
(Stop the operation as compressor ON time in the table
above: 10 minutes or below.)
4) When the follower unit executes self-clean operation in the
group connection, the segment of
is displayed on the
wired remote controller screen via master unit.
∗
If self-clean operation is used, set 0000 of CODE No.
D3 changing to 0015.
∗
To erase the
display during operation of self-clean,
change CODE No. [D4] from [0000: Display
(At shipment)] to [0001: Non-display].
1) Turn on
SAVE
button on the remote controller.
2) During operation of save operation,
SAVE
lights on the
wired remote controller.
3) During save operation, the current release control is
performed with the restriction ratio set in EEPROM on
the outdoor unit.
4) The restriction ratio can be set by keeping
SAVE
button
pushed for 4 seconds or more on the remote controller.
5) When validating the save operation, the next operation
starts with save operation valid because contents are
held even when operation stops, operation mode
changes or power supply is reset.
6) The restriction ratio can be set by changing the setup
data of CODE No. (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
Remarks
Check code [P12]
It is recognized as
[STOP] from the
remote monitor side.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
For the setup opera-
tion, refer to “How to
set up contents of
save operation” of
Installation Manual.
Compressor
ON period
0 to 10 min.
10 to 60 min.
60 min. to
Self-clean
operation period
None
1 hour
2 hours
FAN
Fan only
(UL)
Drain pump
STOP
Louver
Horizontal discharge position
Self-clean is not
factory default.
FILE NO. SVM-18038
- 35 -
Содержание RAV-RM 1401 CTP-TR
Страница 15: ...1 CONSTRUCTION VIEWS EXTERNAL VIEWS 1 1 Indoor Unit RAV RM401CTP RAV RM561CTP FILE NO SVM 18038 15 ...
Страница 16: ...RAV RM801CTP FILE NO SVM 18038 16 ...
Страница 17: ...RAV RM1101CTP RAV RM1401CTP RAV RM1601CTP FILE NO SVM 18038 17 ...
Страница 105: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...