background image

– 28 –

F12

ALT

TS sensor trouble

Outdoor

TS sensor may be displaced, disconnected or short-

circuited.

Entire 

stop

F13

ALT

Heat sink sensor 

trouble

Outdoor

Abnormal temperature was detected by the temp. 

sensor of the IGBT heat sink.

Entire 

stop

F15

ALT

Temp. sensor 

connection trouble

Outdoor

Temp. sensor (TE / TS) may be connected incorrectly. Entire 

stop

F29

SIM

Indoor unit, other P.C. 

board trouble

Indoor

Indoor P.C. board --- EEPROM trouble

Auto-

reset

F31

SIM

Outdoor unit P.C. 

board

Outdoor

Outdoor P.C. board ---- In the case of EEPROM 

trouble.

Entire 

stop

H01

Outdoor unit 

compressor 

breakdown

Outdoor

Current detect circuit, power voltage --- Minimum 

frequency was reached in the current releasing 

control or short-circuit current (Idc) after direct 

excitation was detected

Entire 

stop

H02

Outdoor unit 

compressor lock

Outdoor

Compressor circuit --- Compressor lock was detected. Entire 

stop

H03

Outdoor unit current 

detect circuit trouble

Outdoor

Current detect circuit, outdoor unit P.C. board --- 

Abnormal current was detected in AC-CT or a phase 

loss was detected.

Entire 

stop

H04

Case thermostat 

operation

Outdoor

Malfunction of the case thermostat

Entire 

stop

H06

Outdoor unit low-

pressure system 

trouble

Outdoor

Current, high-pressure switch circuit, outdoor P.C. 

board --- Pressure sensor trouble was detected or 

low-pressure protective operation was activated.

Entire 

stop

J29

SIM

Refrigerant leak 

detection sensor 

trouble

Indoor

A trouble or open-short-circuit was detected by output 

of refrigerant leak detection sensor.

Operation 

continued

J30

SIM

Refrigerant leak 

detection

Indoor

Refrigerant leak was detected by refrigerant leak 

detection sensor.

Entire 

stop

J31

SIM

Refrigerant leak 

detection sensor 

exceeding its life of 

the product

Indoor

In the case of refrigerant leak detection sensor 

exceeding its life of the product.

Operation 

continued

L03

SIM

Duplicated header 

indoor units 

Indoor

Indoor address setting trouble --- There are two or 

more header units in the group.

Entire 

stop

L07

SIM

Group line in 

individual indoor unit  Indoor

Indoor address setting trouble --- There is at least one 

group-connected indoor unit among individual indoor 

units.

Entire 

stop

L08

SIM

Indoor group address 

not set 

Indoor

Indoor address setting trouble --- Indoor address 

group has not been set.

Entire 

stop

L09

SIM

Indoor unit capacity 

not set

Indoor

Indoor unit capacity has not been set.

Entire 

stop

L10

SIM

Outdoor unit P.C. 

board

Outdoor

In the case of outdoor P.C. board jumper wire (for 

service) setting trouble

Entire 

stop

L20

SIM

LAN communication 

trouble

Network 

adapter 

central 

control

Address setting, central control remote controller, 

network adapter --- Duplication of address in central 

control communication

Auto-

reset

L29

SIM

Other outdoor unit 

trouble

Outdoor

Other outdoor unit trouble

Entire 

stop

1) Communication trouble between IPDU MCU and 

CDB MCU

Entire 

stop

2) Abnormal temperature was detected by the heat 

sink temp. sensor in IGBT.

L30

SIM

Abnormal external 

input into indoor unit 

(interlock)

Indoor

External devices, outdoor unit P.C. board --- 

Abnormal stop due to incorrect external input into 

CN80

Entire 

stop

L31

SIM

Phase sequence 

trouble, etc.

Outdoor

Power supply phase sequence, outdoor unit P.C. 

board --- Abnormal phase sequence of the 3-phase 

power supply

Operation 

continued 

(thermos-

tat OFF) 

Remote 

controller 

display

Wireless remote controller

Sensor block display of 

receiving unit

Main defective parts

Judging 

device

Parts to be checked / trouble description

Air 

conditioner 

status

Indication

Operation Timer    

Ready

 GR GR OR

Flashing

 : Lighting 

 : Flashing 

 : OFF 

 : The air conditioner automatically enters the auto-address setting mode.

ALT: When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization.
Receiving unit display OR: Orange   GR: Green

P01

ALT

Indoor unit fan trouble Indoor

Indoor fan motor, indoor P.C. board --- Indoor AC fan 

trouble (fan motor thermal relay activated) was 

detected.

Entire 

stop

P03

ALT

Outdoor unit 

discharge temp. 

trouble

Outdoor

A trouble was detected in the discharge temp. 

releasing control.

Entire 

stop

P04

ALT

Outdoor unit high-

pressure system 

trouble

Outdoor

High-pressure switch --- The IOL was activated or an 

trouble was detected in the high-pressure releasing 

control using the TE.

Entire 

stop

P05

ALT

Open phase detected Outdoor

The power wire may be connected incorrectly. Check 

open phase and voltages of the power supply.

Entire 

stop

P07

ALT

Heat sink overheat

Outdoor

Abnormal temperature was detected by the temp. 

sensor of the IGBT heat sink.

Entire 

stop

P10

ALT

Indoor unit water 

overflow detected

Indoor

Drain pipe, clogging of drainage, float switch circuit, 

indoor P.C. board --- Drainage is out of order or the 

float switch was activated.

Entire 

stop

P12

ALT

The fan trouble of the 

indoor unit

Indoor

Abnormal operation of the indoor fan motor, indoor 

P.C. board, or indoor DC fan (over current or lock, 

etc.) is detected. 

Entire 

stop

P15

ALT

Gas leakage 

detected

Outdoor

There may be gas leakage from the pipe or 

connecting part. Check for gas leakage.

Entire 

stop

P19

ALT

4-way valve trouble

Outdoor
(Indoor)

4-way valve, indoor temp. sensors (TC / TCJ) --- A 

trouble was detected due to temperature drop of the 

indoor unit heat exchanger sensor when heating.

Auto-

reset

P20

ALT

High-pressure 

protective operation 

Outdoor

High-pressure protection

Entire 

stop

P22

ALT

Outdoor unit fan 

trouble

Outdoor

Outdoor unit fan motor, outdoor unit P.C. board --- A 

trouble (overcurrent, locking, etc.) was detected in the 

outdoor unit fan drive circuit.

Entire 

stop

P26

ALT

Outdoor unit inverter 

Idc activated

Outdoor

IGBT, outdoor unit P.C. board, inverter wiring, 

compressor --- Short-circuit protection for compressor 

drive circuit devices (G-Tr / IGBT) was activated.

Entire 

stop

P29

ALT

Outdoor unit position 

trouble

Outdoor

Outdoor unit P.C. board, high-pressure switch --- 

Compressor motor position trouble was detected.

Entire 

stop

P31

ALT

Other indoor unit 

trouble

Indoor

Another indoor unit in the group is raising an alarm.

Entire 

stop

E03/L07/L03/L08 alarm check locations and trouble 

description

Auto-

reset

Remote 

controller 

display

Wireless remote controller

Sensor block display of 

receiving unit

Main defective parts

Judging 

device

Parts to be checked / trouble description

Air 

conditioner 

status

Indication

Operation Timer    

Ready

 GR GR OR

Flashing

55-EN

56-EN

Содержание RAV-HM1101FT-E

Страница 1: ... CONDITIONER SPLIT TYPE Installation Manual R32 Indoor Unit Floor Standing type RAV HM561FT E RAV HM801FT E RAV HM901FT E RAV HM1101FT E RAV HM1401FT E RAV HM1601FT E Model name For commercial use English ...

Страница 2: ...rant HFC R32 which does not destroy the ozone layer This indoor unit is for the R32 refrigerant Be sure to combine with an outdoor unit for the R32 refrigerant Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 4 2 Accessory parts 8 3 Selection of installation place 8 4 Installation 10 5 Drain piping ...

Страница 3: ... Qualified service person 1 The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual or indi...

Страница 4: ... or loss of life if the product is handled improperly Text set off in this manner indicates that failure to adhere to the directions in the caution could result in slight injury 2 or damage 3 to property if the product is handled improperly WARNING Risk of fire Read the OWNER S MANUAL carefully before operation Service personnel are required to carefully read the OWNER S MANUAL and INSTALLATION MA...

Страница 5: ...d for some reason first put on protective gloves and safety work clothing and then proceed WARNING When work is performed at heights use a ladder which complies with the ISO 14122 standard and follow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake the work This unit is equipped with a refrigerant leak detection sensor for safety to ...

Страница 6: ... and the refrigeration cycles is over pressurized which may cause an injury Tighten the flare nut with a torque wrench in the specified manner Excessive tighten of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a ...

Страница 7: ... the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other trouble After the work has finished use an insulation tester set 500 V Megger to check the resistance is 1 MΩ or more between the charge section and the non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused ...

Страница 8: ...tallation work A special tool for the R32 refrigerant is required for installation Use a new and clean piping materials for the connecting pipe so that moisture and dirt are not mixed together during the installation work When using existing pipes follow the Installation Manual enclosed with the outdoor unit Be careful of fan operation when the circuit breaker is turned on If the refrigerant leak ...

Страница 9: ...d places where the exhaust air from combustion appliances will be sucked into the unit Doing so may cause the heat exchanger its aluminum fins and copper pipes and other parts to become corroded Locations with atmospheres with mist of cutting oil or other types of machine oil Doing so may cause the heat exchanger to become corroded mists caused by the blockage of the heat exchanger to be generated...

Страница 10: ...sulator to the side face and the rear side of the indoor unit 200 or more 500 or more 1000 or more Front side In case of right direction piping Front side To open the intake grille Direction of vertical louver The intake grille is fixed by the screws for safety reasons Use a screwdriver to unfasten the screws of the intake grille two places to open the intake grille The screws are designed to stay...

Страница 11: ...ther material not to damage the unit Carry the package by four or more persons and do not bundle it with plastic band at positions other than specified Be sure to take measures to prevent falling at the wall surface and the floor and fix it surely considering prevention of accident of falling because this unit is formed into a thin type If it is not fixed a falling accident may occur After carryin...

Страница 12: ... Height of head of fixing bolt Model A B HM56 to HM80 type 88 30 to 80 HM90 to HM160 type 258 40 to 90 A B Wooden wall Screws for side plate Concrete wall Screws bolts Total 4 at right and left Screws for side plate Anchor bolts Total 4 at right and left 634 mm Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Installation of wired remote control...

Страница 13: ... the Cover kit TCB CKC1F E sold separately Follow the steps below to install the Cover kit 1 Removing the remote controller panel 1 Untie the cords of the air inlet grille and remove the air inlet grille 2 Unfasten the two screws fastening the upper cabinet Lift up the upper cabinet and remove it 3 Unfasten the two screws fastened on the back of the upper cabinet and remove the foam cover 4 Push o...

Страница 14: ...e in the drain hose and water leakage in the room NOTE The drain pipe and drain hose must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Be sure to connect the drain hose and drain pipe at the outside of unit and fix them If clearance occurs between piping wiring and drain hose in opening the knockout hole apply putty to ...

Страница 15: ...l be hard to remove the drip proof cover and the electrical control box cannot be taken out Drain hose Drain pan Heat insulator Hard polyvinyl chloride pipe Adhesion for hard polyvinyl chloride pipe used To connect drain hose on right or left route it through the knock out for refrigerant piping on HM56 to HM80 model Wiring port both sides Refrigerant pipe connecting port both sides Piping port at...

Страница 16: ...hat there are no chips adhered or other problems after flare processing Do not apply refrigerating machine oil to the flare surface Model name RAV HM56 type HM80 HM90 to HM160 type Pipe size Gas side 12 7 mm 15 9 mm Liquid side 6 4 mm 9 5 mm Outer dia of copper pipe R32 tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9...

Страница 17: ...e may give rise to smoking and or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during peeling them Perform the electric wiring so that it do...

Страница 18: ...iring connections between the indoor and outdoor units and between the indoor units and remote controller The wires indicated by the broken lines are provided at the locally 2 Refer to the both indoor and outdoor unit wiring diagrams 3 For details refer to the Installation Manual for outdoor unit to be connected Wiring diagram Example Use 2 core shield wire MVVS 0 5 to 2 0 mm or more for the remot...

Страница 19: ... figure Do not apply tension on the connecting part of the terminal block Be sure to mount cover of the electrical control box and the drip proof cover 1 3 4 2 Drip proof cover HM56 to HM80 only Electrical control box cover Electrical control box A B Positioning of hole for wiring Knock out hole HM56 HM80 HM90 to HM160 Wiring hole Knock out hole Wiring hole Knock out hole Earth screw Indoor and ou...

Страница 20: ...buttons for more than 4 seconds Power on Setting flashes Setting goes out Remote controller is available Approx 5 minutes Power on Setting flashes Setting goes out Remote controller is available Approx 1 minutes 6 Setting timer operation mode 7 DN setting 8 Reset power consumption data 9 Notice history Field setting menu 2 2 Return Set 3 Push the button to select 7 DN setting on the Field setting ...

Страница 21: ...he basic operation procedure 1 2 3 4 5 For the Code DN in Procedure 3 specify 00FC For the Data in Procedure 3 select the Data 0000 TCC Link Data Filter sign term 0000 None 0001 150 H Factory default 0002 2500 H 0003 5000 H 0004 10000 H Data Detection temperature shift value 0000 No shift Factory default 0001 1 C 0002 2 C 0003 3 C 0004 4 C 0005 5 C 0006 6 C Data 8 C Operation setting 0000 None Fac...

Страница 22: ...n system Triple system Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Indoor unit Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Indoor unit Indoor unit Group control for system of multiple units One group can control up ...

Страница 23: ...ess 3 2 2 Address 3 3 2 Address 3 1 2 Address 2 2 2 Address 1 2 2 Procedure example Manual address setup procedure While the operation stops change the setup Stop the operation of the unit Address is displayed here 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more th...

Страница 24: ...stance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activation time leave power ON for 12 hours or more before operating Execute a test run Operate the unit with the remote controller as usual For the procedure of the operation refer to the attached Owner s Manual A forced test run can be executed in the fol...

Страница 25: ... to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more than 4 seconds 3 Push the button to select 4 Monitor function on the Field setting menu screen then push the Set F2 button Push the button to select the code to check data 4 Push the CANCEL button to return to the Field setting menu screen...

Страница 26: ...itioner when filter sign appears on the detailed display Push one of the operation buttons to erase the message or wait for more than 5 seconds until the message disappears Cool 24 Room A 12 00 Mode Fan Speed Filter sign Filter check Room A 12 00 Mode Fan Speed 1 Push the ON OFF button to stop the operation then turn off the circuit breaker 2 Use a screwdriver to unfasten the screws of the intake ...

Страница 27: ...if there are any waggles damages or adhesive dust Filter Go to installed location and check if there are any stains or breaks on the filter Drain pan Access from inspection opening and remove the access panel Check if there is any clogging or drain water is polluted Refrigerant leak detection sensor Open the intake grille and E BOX and check if there are any troubles on sensor s appearance or its ...

Страница 28: ...was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting trouble Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E10 CPU CPU communication trouble Indoor Indoor P C board Communication trouble between main MCU and moto...

Страница 29: ...e to incorrect external input into CN80 Entire stop L31 SIM Phase sequence trouble etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermos tat OFF Remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked trouble descriptio...

Страница 30: ...90 14 86 1 80 6 00 15 11 1 84 4 64 6 10 15 36 1 90 4 79 6 20 15 62 2 00 5 04 6 30 15 87 2 10 5 29 6 40 16 12 2 20 5 54 6 50 16 37 2 30 5 80 6 60 16 62 2 40 6 05 6 70 16 87 2 50 6 30 6 80 17 13 2 60 6 55 6 90 17 38 2 70 6 80 7 00 17 63 2 80 7 05 7 10 17 88 2 90 7 31 7 20 18 13 3 00 7 56 7 30 18 38 3 10 7 81 7 40 18 64 3 20 8 06 7 50 18 89 3 30 8 31 7 60 19 14 3 40 8 57 7 70 19 39 3 50 8 82 7 80 19 ...

Страница 31: ...EB99847901 DH91308301 ...

Отзывы: