– 18 –
EN
2
Each time [ ] [ ] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs. The
indoor unit can be con
fi
rmed for which to change
settings.
3
Push OFF timer button to con
fi
rm the selected
indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
]
fl
ash. Change Code No. [
] with
[ ] [ ] setting button.
5
Push the menu button to make Set data
[
]
fl
ash. Change Set data [
] with
[ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
• To change other settings of the selected indoor
unit, repeat from Procedure
4
.
7
When all the settings have been completed,
push ON/OFF button to determine the settings.
“
”
fl
ashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is
fl
ashing.)
• To change settings of another indoor unit, repeat
from Procedure
1
.
■
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
y
Specify [5d] to the CODE No. in procedure
4
.
y
For the SET DATA of procedure
5
, select a SET
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote controller>
HM561, 801BTP series
SET DATA
External static pressure
0000
30 Pa
Factory setting
0001
50 Pa
0002
40 Pa
0003
100 Pa
0004
65 Pa
0005
120 Pa
0006
150 Pa
HM901, 1101BTP series
SET DATA
External static pressure
0000
40 Pa
Factory setting
0001
30 Pa
0002
50 Pa
0003
100 Pa
0004
65 Pa
0005
120 Pa
0006
150 Pa
HM1401, 1601BTP series
SET DATA
External static pressure
0000
50 Pa
Factory setting
0001
30 Pa
0002
40 Pa
0003
100 Pa
0004
65 Pa
0005
120 Pa
0006
150 Pa
The list above is when SW501-1 and SW501-2 is OFF.
■
External static pressure
When using the wireless remote controller
To set up the external static pressure, use the DIP
switch on the circuit board of the wireless reception
part.
For details, refer to the instruction manual of the
wireless remote controller kit. Alternatively, use the
switch on the indoor micro computer circuit board as
shown in the following
fi
gure and table.
* Once switched, the settings "0001", "0003", and
"0006" can be changed, but to reset to "0000",
you need to set the switch to the normal (default)
position and use a separately-sold wired remote
controller to overwrite the data with "0000".
SW501-1
OFF
ON
OFF
ON
SW501-2
OFF
OFF
ON
ON
SET DATA
0000
0001
0003
0006
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a
separately-sold
wired remote controller, and then perform the procedure
for installing a separately-sold
fi
lter on this page to set the
[5d] data to "0000"
■
Filter sign setting
According to the installation condition, the
fi
lter sign
term (Noti
fi
cation of
fi
lter cleaning) can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
y
For the CODE No. in Procedure
4
, specify [01].
y
For the [SET DATA] in Procedure
5
, select the SET
DATA of
fi
lter sign term from the following table.
SET DATA
Filter sign term
0000
None
0001
150 H
0002
2500 H
(Factory default)
0003
5000 H
0004
10000 H
■
To secure better effect of
heating
When it is dif
fi
cult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
y
For the CODE No. in Procedure
4
, specify [06].
y
For the SET DATA in Procedure
5
, select the SET
DATA of shift value of detection temperature to be
set up from the following table.
SET DATA
Detection temperature shift value
0000
No shift
0001
+1°C
0002
+2°C
(Factory default)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C