– 14 –

EN

 CAUTION

When the refrigerant pipe is long, provide support 
brackets at intervals of 2.5 m to 3 m to clamp the 
refrigerant pipe. Otherwise, abnormal sound may be 
generated.

 

Permissible piping length 
and height difference

They vary according to the outdoor unit.
For details, refer to the Installation Manual attached to
the outdoor unit.

 CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Reusable mechanical connectors and 

fl

ared 

joints are not allowed indoors. When mechanical 
connectors are reused indoors, sealing parts shall 
be renewed. When 

fl

ared joints are reused indoors, 

the 

fl

are part shall be refabricated.

2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using 

VACUUM PUMP.

4. Check the gas leakage. (Connected points)

 

Pipe size

Model

Pipe size (mm)

Gas side

Liquid side

HM56

Ø12.7

Ø6.4

HM80, HM90,

HM110, HM140, 

HM160

Ø15.9

Ø9.5

 

Connecting refrigerant piping

Flaring

 

y

Cut the pipe with a pipe cutter.

  Remove burrs completely.
  Remaining burrs may cause gas leakage.

 

y

Insert a 

fl

are nut into the pipe, and 

fl

are the pipe.

 As the 

fl

aring sizes of R32 differ from those of 

refrigerant R22, the 

fl

are tools newly manufactured 

for R32 are recommended.

  However, the conventional tools can be used by 

adjusting projection margin of the copper pipe.

Projection margin in 

fl

 aring: B (Unit: mm)

Outer dia. of

copper pipe

Tool used

Conventional

tool used

6.4, 9.5

0.5 to 1.1

0.5 to 1.1

12.7, 15.9

0.5 to 1.1

1.5 to 2.0

B

Flaring diameter size: A (Unit: mm)

Outer dia. of copper pipe

A

+0

-0.4

6.4

9.1

9.5

13.2

12.7

16.6

15.9

19.7

A

 CAUTION

 

y

Do not scratch the inner surface of the 

fl

ared part 

when removing burrs.

 

y

Flare processing under the condition of scratches 
on the inner surface of 

fl

are processing part will 

cause refrigerant gas leak.

 

y

Check that the 

fl

ared part is not scratched, 

deformed, stepped, or 

fl

attened, and that there 

are no chips adhered or other problems, after 

fl

are 

processing.

 

y

Do not apply refrigerating machine oil to the 

fl

are 

surface. 

*    In case of 

fl

aring with the conventional 

fl

are tool, 

pull it out approx. 0.5 mm more than that for R22 
to djust to the speci

fi

ed 

fl

are size. The copper pipe 

gauge is useful for adjusting projection margin size.

 

y

  The sealed gas was sealed at the atmospheric 

pressure so when the 

fl

are nut is removed, there 

will no “whooshing” sound: This is normal and is not 
indicative of trouble.

 

y

  Use two wrenches to connect the indoor unit pipe.

Work using double spanner

 

y

  Use the tightening torque levels as listed in the 

following table.

Outer dia. of connecting 

pipe (mm)

Tightening torque (N•m)

6.4

14 to 18

9.5

34 to 42

12.7

49 to 61

15.9

63 to 77

Tightening torque of flare pipe connections

Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.
Align the centres of the connecting pipes and tighten 
the 

fl

are nut as far as possible with your 

fi

ngers. Then 

tighten the nut with a spanner and torque wrench as 
shown in the 

fi

gure.

 CAUTION

Tightening with an excessive torque may crack the 
nut depending on installation conditions.

 

Evacuation

Perform vacuuming from the charge port of valve of 
the outdoor unit by using a vacuum pump.
For details, follow to the Installation Manual attached 
to the outdoor unit.

 

y

Do not use the refrigerant sealed in the outdoor unit 
for evacuation.

REQUIREMENT

For the tools such as charge hose, etc., use those 
manufactured exclusively for R32.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant 
“R32” referring to the attached Installation Manual of 
outdoor unit.
Use a scale to charge the refrigerant of speci

fi

ed 

amount.

REQUIREMENT

 

y

Charging an excessive or too little amount of 
refrigerant causes a trouble of the compressor.

  Charge the refrigerant of speci

fi

ed amount.

 

y

A personnel who charged the refrigerant should 
write down the pipe length and the added 
refrigerant amount in the F-GAS label of the 
outdoor unit. It is necessary to 

fi

x the compressor 

and refrigeration cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4 mm-
hexagonal wrench is required for opening the valve.
For details, refer to the Installation Manual attached to
the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas
leaks or not, from the pipe connecting section or cap of
the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for 
HFC refrigerant (R32, R134a, R410A, etc.).

7

 Refrigerant 

piping 

Содержание RAV-HM1101BTP-E

Страница 1: ...CONDITIONER SPLIT TYPE Installation Manual Indoor Unit Model name Concealed Duct Type RAV HM561BTP E RAV HM801BTP E RAV HM901BTP E RAV HM1101BTP E RAV HM1401BTP E RAV HM1601BTP E For commercial use English ...

Страница 2: ...oroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has be...

Страница 3: ...ture poisoning and other injuries which leave aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets MEANINGS OF SYMBO...

Страница 4: ... safety work clothing during installation servicing and removal Do not touch the aluminum fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Before opening the suction board cover set the circuit breaker to the OFF position Failure to set the circuit breaker to the OFF posi...

Страница 5: ...st the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or ho...

Страница 6: ... Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks If...

Страница 7: ...l and possibly resulting in rupture injury or other trouble CAUTION This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer As the R32 refrigerant is easily affected by impurities such as moisture oxidized film oil etc due to the high pressure be careful not to allow the moisture dirt existing refrigerant refrigerating machine oil etc to get mixed up in the re...

Страница 8: ... combust and start a fire y Locations where vapors from food oils are formed such as kitchens where food oils are used Blocked filters may cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result y Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be...

Страница 9: ...nditions Indoor side 27 C dry bulb temperature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours Installation space Unit mm Reserve sufficient space required for installation or service work 25 A 25 120 B 25 570 570 25 570 25 Ceiling Ceiling Ceiling Ceiling Air intake Air intake Air intake 50 or more 300 or more 100 or more 2500 or more Floor surface Service door Ceiling o...

Страница 10: ...the indoor unit Procure hanging bolts washer and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Washer M10 8 pieces Installation of hanging bolt Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below New concrete slab Install the bolt...

Страница 11: ...r unit with proper heat insulation Improper heat insulation will cause condensation to form y The drain pipe must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Doing so may cause abnormal sounds y Restrict the length of the traversing drain pipe to 20 meters or less For a long pipe provide support brackets at intervals o...

Страница 12: ...hen installed in heating period When the electrical and wiring work has been completed Pour some water by following the method shown in the following figure Then while performing a cooling operation check that the water drains from the drain pipe connecting port transparent and that no water is leaking from the drain pipe When the electrical and wiring work has not been completed Disconnect the fl...

Страница 13: ...140 150 160 170 180 190 200 210 220 600 800 1000 1200 1400 1600 1800 2000 2200 0 10 20 30 40 50 50 70 80 90 100 110 120 130 140 150 160 170 180 190 200 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 Standard air volume 800 m3 h Standard air volume 1700 ...

Страница 14: ... 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 254 975 37 5 37 5 27 27 960 235 2 100 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 254 27 27 37 5 37 5 1359 4 100 100 235 4 100 0 0 1 0 0 1 100 0 0 1 0 0 1 100 100 100 0 0 1 0 0 1 0 0 1 100 254 1375 27 27 37 5 37 5 1360 235 2 0 0 1 0 0 1 100 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 100 0 0 1 0 0 1 0 0 1 100 100 100 HM56 HM80 HM90 HM110 HM140 HM160 Under air i...

Страница 15: ...are size The copper pipe gauge is useful for adjusting projection margin size y The sealed gas was sealed at the atmospheric pressure so when the flare nut is removed there will no whooshing sound This is normal and is not indicative of trouble y Use two wrenches to connect the indoor unit pipe Work using double spanner y Use the tightening torque levels as listed in the following table Outer dia ...

Страница 16: ...e is connected in the middle may give rise to smoking and or a fire CAUTION y For power supply specifications follow the Installation Manual of outdoor unit y Do not connect 220 240V power to the terminal blocks A B for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and Indoor Outdoor connecting wires when peeling them Perfor...

Страница 17: ...Be sure to connect both ends of the shield wire to earth leads y Connect earth wires for each indoor unit in the simultaneous twin simultaneous triple and simultaneous double twin systems Communication type TU2C Link can be used with these models If the indoor unit and the connected remote controller remote sensor are all TU2C Link models TU2C Link communication will be performed automatically If ...

Страница 18: ...cted Wiring diagram A B A B Terminal block for remote controller wiring of indoor unit Remote controller wire Locally procured Terminal block Remote controller unit Applicable controls setup settings at the site Remote controller model name RBC ASCU1 Basic procedure Be sure to stop the air conditioner before making settings Change the setup while the air conditioner is not working CAUTION Set only...

Страница 19: ...above is when SW501 1 and SW501 2 is OFF External static pressure When using the wireless remote controller To set up the external static pressure use the DIP switch on the circuit board of the wireless reception part For details refer to the instruction manual of the wireless remote controller kit Alternatively use the switch on the indoor micro computer circuit board as shown in the following fi...

Страница 20: ... 2 3 4 5 6 7 Specify d1 for the Code No in Procedure 4 Select the following data for the set data in Procedure 5 SET DATA 8 C Operation setting 0000 None Factory default 0001 8OC Operation setting Installing optional parts When installing optional parts data setup may be required with remote controller Be sure to set the data according to Installation Manual for optional parts Information The foll...

Страница 21: ... Procedure example 1 After setup change of manual address Line system Indoor unit Indoor unit Single system Twin system The above address is set by the automatic addressing when the power is turned on However line addresses and indoor addresses are set randomly For this reason change the setting to match line addresses with indoor addresses Manual address setting 1 Push and hold menu button and se...

Страница 22: ...utton and then select HIGH with FAN button 10Test run 3 Cooling test run Heating test run Set the temperature to 17 C with the temp setup buttons Set the temperature to 30 C with the temp setup buttons 4 Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 18 C with the temp setup buttons After confirming a signal receiving sound beep ...

Страница 23: ...S 65 Heatsink temperature THS 6A Operating current x1 10 6D Outdoor heat exchange coil temperature TL F1 Compressor cumulative operating hours x100 h 1 The above temperature values are estimated from the temperature of the heat exchanger It may differ from the actual discharge temperature 2 For outdoor unit data refer to the Installation Manual and Service Manual of the outdoor unit Daily maintena...

Страница 24: ...irt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louvers Indoor Dust d...

Страница 25: ...sconnected or short circuited Entire stop F13 ALT Heat sink sensor error Outdoor Abnormal temperature was detected by the temp sensor of the IGBT heat sink Entire stop Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main problem parts Judging device Parts to be checked error description Air conditioner status Indication Operation Timer Ready GR GR ...

Страница 26: ...sor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan error Outdoor Outdoor unit fan motor outdoor unit P C board An error overcurrent locking etc was detected in the outdoor unit fan drive circuit Entire stop P26 ALT Outdoor unit inverter Idc activated Outdoor IGBT outdoor unit P C board inverter wiring compres...

Страница 27: ...omes invalid if technical or operational modifications are introduced without the manufacturer s consent Declaration of Conformity Manufacturer Toshiba Carrier Thailand Co Ltd 144 9 Moo 5 Bangkadi Industrial Park Tivanon road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand TCF holder TOSHIBA CARRIER UK LTD Porsham Close Belliver Industrial Estate Roborough Plymouth Devon PL6 7DB United Kin...

Страница 28: ...s 2 When the existing pipe thickness is thinner than the specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works y The operating pressure of refrigerant is high If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thickness mm Pipe out...

Страница 29: ...1128950185 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Отзывы: