8-3. Table Inspection of outdoor unit main parts
No.
Parts name
Checking procedure
1
Compressor
(Model : DX380A2T-20M)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
0.40
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
2
Outdoor fan motor
(Model : ICF-280-A100-1)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
14.8±1.5
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
3
4-way valve coil
(Cooling/heating switching)
(Model : DXQ-1490)
Measure the resistance value of each winding by using the tester.
Resistance value
9.1±0.36%
Ω
Under 20°C
Connector : White
- 73 -