28
–
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
Description
* Symbols
UH
: Ultra High
H
: High
M+
:
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
(Fig. 1)
(Fig. 2)
(Table 1) Indoor fan air flow rate
+2.5
Ta
[˚C]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WB)
*3
*4
*5
L(W6)
Air volume AUTO
L
L+
M
M+
H
W6
(L + M) / 2
W9
(M + H) / 2
WC
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
from M+ and L)
FILE NO. SVM-12050
Fan speed
level
COOL HEAT DRY
Fan speed
Air flow rate
Fan speed
Air flow rate
(rpm)
(m3/h)
(rpm)
(m3/h)
WF
UH
1210
571
1300
620
WE
H
1210
571
1300
620
WD UH M+
1170 546 1250 590
WC
H
1120
515
1200
570
WB M+
1040 465 1080 490
WA 1000 440
465
W9 M L+
960 415
990 434
W8
L
870
359
870
359
W7
L+
L-
L+
850
347
860
353
W6
L
L
760
291
770
297
W5 L- UL L- 760 291
770 297
W4
UL
UL
700
253
720
266
W3
SUL
SUL
650
222
670
234
W2
SUL
500
129
520
141
W1
500
129
500
129
RAS-B13N3KV2-E
RAS-B10N3KV2-E
UH
H
M
M+
M
1050