Outdoor Unit :
RAS-5M34S3AV-E,-A,-TR
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent. (Thermistor thermometer)
2. Connecting piping condition : 5 meters × 5 units (5m/each indoor unit)
Indoor unit
Indoor
Outdoor
A
B
C
D
E
P (MP)
T1 (°C)
T2 (°C)
1 unit
07
—
—
—
—
2.1 to 2.3
36 to 38
3 to 5
High
27
10
—
—
—
—
2.7 to 2.9
44 to 46
2 to 4
High
38
13
—
—
—
—
3.2 to 3.4
52 to 54
2 to 4
High
46
16
—
—
—
—
3.6 to 3.9
53 to 55
2 to 4
High
50
18
—
—
—
—
3.6 to 3.9
53 to 55
2 to 4
High
53
22
—
—
—
—
3.6 to 3.9
53 to 55
2 to 4
High
57
24
—
—
—
—
3.6 to 3.9
53 to 55
2 to 4
High
65
2 units
07
07
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
46
10
07
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
46
13
07
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
47
16
07
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
53
18
07
—
—
—
2.9 to 3.1
46 to 48
0 to 2
High
54
22
07
—
—
—
2.9 to 3.1
46 to 48
0 to 2
High
56
24
07
—
—
—
3.0 to 3.2
47 to 49
–1 to 1
High
57
10
10
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
46
13
10
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
48
16
10
—
—
—
2.9 to 3.1
46 to 48
0 to 2
High
54
18
10
—
—
—
2.9 to 3.1
46 to 48
0 to 2
High
56
22
10
—
—
—
3.0 to 3.2
47 to 49
–1 to 1
High
57
24
10
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
13
13
—
—
—
2.8 to 3.0
45 to 47
0 to 2
High
50
16
13
—
—
—
3.0 to 3.2
47 to 49
–1 to 1
High
57
18
13
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
22
13
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
24
13
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
16
16
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
18
16
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
22
16
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
24
16
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
18
18
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
22
18
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
24
18
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
22
22
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
22
24
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
24
24
—
—
—
3.1 to 3.3
48 to 50
–1 to 1
High
58
3 units
07
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
10
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
13
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
16
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
18
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
22
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
24
07
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
10
10
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
13
10
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
16
10
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
18
10
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
10
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
24
10
07
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
20 / –
7 / 6
13
13
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
13
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
13
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
13
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
13
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
16
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
16
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
16
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
16
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
18
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
18
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
18
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
10
10
10
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
13
10
10
—
—
2.3 to 2.5
38 to 40
–1 to 1
High
59
16
10
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
10
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
10
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
10
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
13
13
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
13
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
13
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
13
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
13
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
16
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
16
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
16
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
16
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
18
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
13
13
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
13
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
13
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
13
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
13
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
16
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
16
16
16
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
16
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
16
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
16
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
18
18
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
18
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
18
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
18
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
18
13
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
22
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
22
22
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
22
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
22
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
24
07
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
24
24
10
—
—
2.5 to 2.7
37 to 39
–2 to 0
High
60
Temperature
condition
No. of
operating
units
Standard
pressure
Heat exchanger
pipe temperature
Indoor
fan
Compressor
revolution
(rps)
FILE NO. SVM-15036
- 45 -
Содержание RAS-5M34S3AV-A