FILE NO. SVM-06017
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-4.
Fig. 7-2-4
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO and Hi Power operations can not be set.
7-2-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 2 operations (Cooling, Fan only) is
selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit is
pushed, the preset temperature is fixed at 24°C and
the indoor unit is controlled as shown in Fig. 7-2-6.
Fig. 7-2-6
+4
0
(Room temp
.)
–
(Preset temp
.)
°C
Cooling operation
The louver moves to the position
same as Hi Power operation.
Cooling operation
Fan only operation
RAS-
30NKP-AR-1
(Room temp.)
– (Preset temp.)
Preset
temp.
ON
+3
+2
+1
0
OFF
Outdoor fan
OPERATION
display
Compressor
ON:6min. OFF:4min.
ON:5min. OFF:5min.
OFF
ON:6min. OFF:4min.
ON:5min. OFF:5min.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
L.
*
S.L.
S.L.
L.
L.
S.L.
L.
ON
ON
ON
ON
OFF
OFF
OFF
*
Super Low
RAS-
30NKP2B-1