background image

11

Installation Manual

Outdoor Unit

3. Turn on the circuit breaker to supply electricity.

In the initial LED display status, D805 is lighted as below.

 : ON,  

 : OFF,    : Rapid Flashing (5 times/sec.),  

 : Slow Flashing (1 time/sec.)

D800

D801

D802

D803

D804

D805

  Start running all the indoor units connected to the outdoor unit in the 

cooling mode.

  (The indoor unit in the room that doesn’t operate the cooling mode cannot 

be checked.)

4. After 5 minutes, hold down SW01 for at least 5 seconds, and check that 

D800 is lighted and D804 light is 

fl

 ashing ( 1 time/sec.).

D800

D801

D802

D803

D804

D805

5. Press the SW01 4 times until the LED is displayed as below.

D800

D801

D802

D803

D804

D805

6. Press SW02 for 1 times. Then D805 light is flashing (5 times/sec.).

D800

D801

D802

D803

D804

D805

7. Hold down SW02 for at least 5 seconds. Then the wiring/piping check 

starts automatically. (The LED display is lighted for a moment.)

D800

D801

D802

D803

D804

D805

•  If no problems are detected, the checking operation returns to the 

normal operation automatically. The LED is displayed as below.

D800

D801

D802

D803

D804

D805

8. The below is displayed when the error is detected.

(* Repetition of 3 sec ON / 0.5 sec OFF)

D800

D801

D802

D803

D804

D805

*

*

*

*

*

  Press the SW01 3 times until the LED is displayed as below, to check the 

room judged as error.

D800

D801

D802

D803

D804

D805

  Incorrect wiring/piping can be checked by pressing SW02. The LED is 

displayed as below. Turn off the circuit breaker, then check wiring/piping 
again.

Check result

D800 D801 D802 D803 D804 D805

Description

Normal operation (no error)

Trouble in unit A

Trouble in unit B

Trouble in unit C

Trouble in unit A and B

Trouble in unit A and C

Trouble in unit B and C

Trouble in unit A, B and C

•  The D800 LED represents unit A.
•  The D801 LED represents unit B.
•  The D802 LED represents unit C.

9. When you want to start over the operation of the SW01 and SW02, press 

the SW01 and the SW02 at the same time for 5 sec. (The procedure will 
set back to step 3.) However, do not execute the operation during the 
check. If by any chance the check is stopped by the operation, start over 
the check after turning off the power once.

10. Notes

•  It sometimes takes about 30 minutes maximum for the check.
•  During the check, the compressor and the fan of the outdoor/indoor unit 

repeat ON/OFF.

•  You cannot check wiring/piping when the external temperature is 5°C 

or less. Also, there is a possibility to misjudge if the indoor temperature 
becomes too low by cooling operation. In that case, execute the cooling 
operation for per room and check if the connection is normal.

 

Gas Leak Inspection

Refer to the “  Gas Leak Inspection” on page 9.

 

Test run

1.  If you perform the test run in summer, start running in the cooling mode 

fi

 rst 

to decrease the temperature of the room, then run in the heating mode.
(Heating mode: Set the temperature to 30°C.)
•  If you perform the test run in winter, start running in the heating mode 

fi

 rst 

to increase the temperature of the room, then run in the cooling mode.
(Cooling mode: Set the temperature to 17°C.)

2.  For the test run, be sure to satisfy the following conditions below:

 

- Perform the test run for each indoor unit respectively.

 

- Perform the test run for about 10 minutes in both the cooling mode and 

the heating mode.

•  You can perform the test run in the cooling/heating mode by utilizing the 

thermo sensor of the indoor unit.
Cooling mode: Warm the thermo sensor using an appliance such as a 
hair dryer.
Heating mode: Put a cold towel on the thermo sensor.

 

Instructions for the Customers

•  Explain to the customers the proper operation procedure and let them 

operate the air conditioner along with the supplied instruction manual.

•  When multiple indoor units are connected to the outdoor unit, the cooling 

mode and the heating mode are not available at the same time.
When multiple indoor units are running at the same time, the operation mode 
of the unit which starts running 

fi

 rst is applied to the other units.

•  When you start running the indoor unit or change the operation mode, the 

unit starts running after 3 minutes. This is due to the protection function of 
the unit, not a malfunction.

•  When the external temperature becomes low, the pre-heating of the 

compressor starts to protect it. Keep the circuit breaker on for use.
The electricity consumption during pre-heating is about 30 W.
If the circuit breaker is turned off, the indoor unit may not start running for 
about 10 minutes or more.

•  Electronic expansion valves are used for the outdoor unit.

When you turn on the power, the outdoor unit starts clattering every 1 or 
2 months. This clattering is not a malfunction, but occurs when the unit is 
returning to the default setting for optimised control.

•  While an indoor unit is running in the heating mode, the outdoor unit supplies 

refrigerant to the other indoor units which are not running.
Therefore, noise may come from the other indoor units or the exterior of 
them may become warm.

1116691099_(01) EN.indd   11

1116691099_(01) EN.indd   11

9/22/15   5:59 PM

9/22/15   5:59 PM

Содержание RAS-2M14S3AV-E

Страница 1: ... Manual Outdoor Unit Model name RAS 3M18S3AV E RAS 2M18S3AV E RAS 2M14S3AV E NOTE Descriptions about operations for the 3 indoor units in this manual are not applicable to RAS 2M18S3AV E and RAS 2M14S3AV E English Installation Manual Outdoor Unit ...

Страница 2: ...ng 10 9 Test run 10 10 Pump down Operation 12 11 Troubleshooting 12 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to the install...

Страница 3: ...ity of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that leaves after effects and requires hospitalization or extended out pa...

Страница 4: ...oles must be incorporated in the fixed wiring Turn off main power supply before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cables correctly If the connecting cables are connected wrongly electric parts may be damaged Check the earth wire that it is not broken or disconnected before installation Do not install...

Страница 5: ...s or the specified parts Failure to do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly ear...

Страница 6: ... disturb neighbours This appliance must be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed Failure to do so may cause electrical shock Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit Ensure that drained water is discharged Improper drainage can result in water leakage...

Страница 7: ... combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated Example of indoor unit class RAS...

Страница 8: ... to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoor unit in a location where there are some obstructions or a wall secure sufficient ...

Страница 9: ...hexagon wrench 1 Connect a charge hose Make sure that the Handle Hi of the gauge manifold valve is closed fully Connect the port of the gauge manifold valve and the service port Valve core Setting Pin using the charge hose NOTE If a control valve or charge valve is attached to the charge hose leak of R410A refrigerant can be avoided 2 Open the Handle Low of the gauge manifold valve fully then oper...

Страница 10: ...r refrigerant leaks may be required depending on European or local legislation Insulation of the Refrigerant Pipes Insulate the refrigerant pipes for liquid and gas separately Heat proof bubble polyethylene Gas Leak Inspection Perform a gas leak inspection for the flare nut connections valve stem connection and service port cap without fail Use a leak detector exclusively manufactured for R410A Fl...

Страница 11: ...it Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of the indoor and the outdoor unit 5 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 6 Attach the terminal cover and the valve cover Stripping Length of connecting cable for outdoor unit 55 5 5 30 1 2 3 5 5 30 55 L N Earth wire Earth wire Powe...

Страница 12: ... or less Also there is a possibility to misjudge if the indoor temperature becomes too low by cooling operation In that case execute the cooling operation for per room and check if the connection is normal Gas Leak Inspection Refer to the Gas Leak Inspection on page 9 Test run 1 If you perform the test run in summer start running in the cooling mode first to decrease the temperature of the room th...

Страница 13: ...lve at the liquid end 9 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 10 Close the valve stem of the service valve at the gas end 11 The refrigerants collection operation is finished in maximum 10 minutes After the collection is finished promptly stop the operation of all the indoor unit There are cases that the compressor restarts 12 When you want to start over the operati...

Страница 14: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116691099 ...

Отзывы: