8
Electrical Work
Refrigerant Piping
1. The supply voltage must be the same as the rated voltage of the air
conditioner.
2. Prepare the power source for exclusive use with the air conditioner.
Stripping length of the connecting cable
Knockout of Pipe Cover For 30k only
Model
RAS-24BKS-HK
RAS-30BKS-HK
Power source
50Hz, 220 V Single phase
Maximum running current
13A
21A
Plug socket & fuse rating
16A
27A
Power cord
4 mm
2
(H07RN-F or 60245 IEC66)
or 3.5 mm
2
(AWG-12)
NOTE
: Connecting cable
• Wire type : More than 1.5 mm² (H07RN-F or 60245 IEC66) or 1.3 mm²
(AWG-16)
• Wrong wiring connection may cause some electrical parts burn out.
• Be sure to comply with local rule on running the wire from indoor unit
to outdoor unit (size of wire and wiring method, etc.).
• Every wire must be connected
fi
rmly.
• If incorrect or incomplete wiring is carried out, it will cause an ignition
or smoke.
• Prepare the power supply for exclusive use with the air conditioner.
• This product can be connected to the mains.
Connection
to
fi
xed wiring: A switch which disconnects all poles and
has a contact separation of at least 3 mm must be incorporated in the
fi
xed wiring.
CAUTION
6
10
0
10
10
13
0
6
3
2
N
L
60
60
1
Connecting cable
Terminal screw
Screw
Terminal block
Earth line
Earth line
Connecting cable
Power supply cord
Power supply cord
Cord clamp
Cord clamp
Round type
terminal
Round type
terminal
Cable tie
Power supply cord
Connecting cable
Protective bush
Knockout procedure
Rear direction
Pipe cover
PLATE-TRANSPORTATION
• Should be take off and no
need to
fi
x.
• The indoor/outdoor connecting pipes can be connected in rear direction.
Take off the knockout part of the pipe cover through which pipes.
• Detach the pipe cover and tap on the knockout section a few times with
the shank of a screwdriver. A knockout hole can easily be punched.
* Be sure to wear heavy work gloves while working.
Process of installation protective bush For 24k, 30k
• Install the supplied protective bush and guard material around the
passage hole to protect wires and pipes.
Be sure to attach the pipe covers after pipes have been connected.
Cut the slits under the pipe covers to facilitate the installation.
After connecting the pipes, be sure to mount the pipe cover.
The pipe cover is easily mounted by cutting off the slit at the lower part of
the pipe cover.
Supplied protective bush
Supplied passage hole guard material
* Attach the guard material securely so
that it does not come loose.
01_1115551256-EN.indd 8
01_1115551256-EN.indd 8
8/26/2558 BE 2:50 PM
8/26/2558 BE 2:50 PM
Содержание RAS-24BAS-HK
Страница 21: ...MEMO 02_1115551256 CT indd 10 02_1115551256 CT indd 10 10 1 2558 BE 3 01 PM 10 1 2558 BE 3 01 PM ...
Страница 22: ...MEMO 02_1115551256 CT indd 11 02_1115551256 CT indd 11 10 1 2558 BE 3 01 PM 10 1 2558 BE 3 01 PM ...
Страница 23: ...02_1115551256 CT indd 12 02_1115551256 CT indd 12 10 1 2558 BE 3 01 PM 10 1 2558 BE 3 01 PM ...
Страница 24: ...1115551256 02_1115551256 CT indd 13 02_1115551256 CT indd 13 10 1 2558 BE 3 01 PM 10 1 2558 BE 3 01 PM ...