– 52 –
FILE NO. SVM-12039
<When the installation plate is directly mounted on
the wall>
1.
Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2.
To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3.
Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Projection
15 mm or less
Clip anchor
(local parts)
5 mm dia. hole
Anchor
bolt
Fig. 10-3-4
7
7
7
7
7
Mounting
screw
∅
4 x 25
s
s
s
s
s
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
•
In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
•
Insert clip anchors for appropriate
7
mounting
screws.
NOTE
•
Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
Installation plate
<Keep horizontal direction>
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
10-3-3. Wiring connection
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable slot
on the rear panel so that it protrudes about 20 cm
from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tighten firmly but not over 1.2 N.m (0.12 kgf.m)
7. Secure the connecting cable with the cord clamp.
CAUTION
•
Be sure to refer to the wiring system diagram
labeled inside the front panel.
•
Check local electrical cords and also any specific
wiring instructions or limitations.
•
Wire type : More than H07RN-F or 60245 IEC66
•
Use stranded wire only.
NOTE
(1.0 mm
2
or more)
Fig. 10-3-5
without removing the front panel.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Stripping length of the connecting cable
Screw
Terminal cover
Cord clamp
Terminal block
Earth line
Screw
100 mm
10 mm
10 mm
90 mm
Connecting cable
about 2
0 cm
3