FILE NO. SVM-02007
– 24 –
8-1-4. Prevent-freezing control
The indoor heat exchanger sensor detects refrigerant
vapor temperature in COOL/DRY operation. If the
temperature is below the specified value, compressor
motor speed is reduced so that operation is performed
in temperature below the specified value to prevent-
freezing of indoor heat exchanger.
8-1-5. Louver control
(1) Vertical air flow louvers
Positions of vertical air flow louvers are automati-
cally controlled according to the operation status
(AUTO (A), COOL ( ), DRY ( ), HEAT( ) and
FAN ONLY ( ). Besides, positions of vertical air
flow louvers can be arbitrarily set by pressing the
[FIX] button.
(2) Swing
If the [SWING] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [FIX] button is pressed, swinging stops.
LOW
+
=
MED
+
=
LOW+MED
2
MED+HIGH
2
Table 8-1-2
Normal
Powerful
Fan mode
Motor
Air flow
Motor
Air flow
Remote
speed
volume
speed
volume
control
(rpm)
(m
3
/h)
(rpm)
(m
3
/h)
Cooling
H
HIGH
1,140
535
1,140
535
and
M
+
1,100
510
1,140
535
Fan only
MED
+
1,070
495
1,100
510
M
MED
1,000
510
1,060
490
LOW
+
900
395
960
430
L
+
860
370
880
380
L
LOW
810
340
860
370
L–
750
305
810
340
Heating
H
HIGH
1,250
600
1,250
600
M
+
1,200
600
1,250
600
MED
+
1,150
540
1,170
555
M
MED
1,060
490
1,100
510
L
+
1,000
455
1,060
490
LOW
+
970
435
1,050
485
L
LOW
880
380
1,000
455
L–
860
370
880
380
UL
750
305
810
340
SUL
640
240
660
250
DRY
L
+
860
370
L
810
340
L–
750
305
UL
720
285
SUL
660
250
8-1-6. Indoor fan control (DC fan motor)
(1) The indoor fan is operated by the stepless speed
change DC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
+
and HIGH) as described in Table 8-1-2. If AUTO
mode is selected, the fan motor speed is automati-
cally controlled by the difference between the
preset temperature and the room temperature.