5-2. RAS-07SKHP-E / RAS-07S2AH-E
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating Cooling
Compressor
Heat exchanger
Propeller fan
Outdoor unit
PH108X1C-4DZDN2
Cooling
Heating
Mark( )means check points of Gas Leak.
O.D.:9.52mm
O.D.:6.35mm
Cooling
Heating
Packed valve
(
∅
9.52)
Packed valve
(
∅
6.35)
0.39m
(Connecting pipe)
∅
9.52
0.49m
(Connecting pipe)
∅
6.35
T1
P
Refrigerant
R-22 : 0.64 kg.
Accumulator
Heat exchanger
Capillary tube
∅
1.0x1000
S
(2 pcs.)
Standard 1.32 35.0 High 20/– 7/6
Heating Overload 1.93 50.0 Low 27/– 24/18
Low temperature 1.14 30.0 High 20/–
–10/–10
Standard 0.52 13.0 High 27/19 35/24
Cooling Overload 0.68 18.0 High 32/23 43/26
Low temperature 0.32 7.0 Low 21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
50Hz
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor