Lead Length Specifications
Adhere to the NEC and any local codes during the installation of ASD/motor systems. Excessive lead
lengths may adversely affect the performance of the motor. Special cables are not required.
Lead lengths from the ASD to the motor in excess of those listed in
may require filters to be added
to the output of the ASD.
All Toshiba CT motors use an insulation system that is NEMA MG1 Part 30 compliant.
All Toshiba XT motors use an insulation system that is NEMA MG1 Part 31 compliant.
lists the suggested maximum lead lengths for the listed motor voltages.
Note:
Contact the TIC Customer Support Center for application assistance when using lead
lengths in excess of those listed or for filter selection assistance for a given application.
Exceeding the peak voltage rating or the allowable thermal rise time of the motor
insulation will reduce the life expectancy of the motor.
When operating in the
Vector Control
mode, the carrier frequency should be set to
2.2 kHz or above.
Table 1. Lead Length Recommendations.
Model
PWM Carrier
Frequency
NEMA MG1 Part 30
Compliant Motors
NEMA MG1 Part 31
Compliant Motors
230-Volt
All
450 feet
1000 feet
460-Volt
5 kHz
200 feet
600 feet
5
kHz
100 feet
300 feet
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......