P9 ASD Installation and Operation Manual
231
My Function Frequency Data 4
Program
My Function
My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the
My Function Frequency Data 4
.
The analog signal is selected using the
Input Setting
.
Direct Access Number — F926
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Frequency Data 5
Program
My Function
My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the
My Function Frequency Data 5
.
The analog signal is selected using the
Input Setting
.
Direct Access Number — F927
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.00
Units — %
My Function Time Data 1
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 1
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F928
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 2
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 2
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F929
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 3
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 3
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F930
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......