198
P9 ASD Installation and Operation Manual
Over-Torque Detection Level (Positive Torque)
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during positive torque. This setting is a percentage of the
maximum rated torque of the ASD.
.
Direct Access Number — F616
Parameter Type —
Numerical
Factory Default —
200.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Over-Torque Detection Level (Negative Torque)
Program
Protection
Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during negative torque (regen). This setting is a percentage of
the maximum rated torque of the ASD.
.
Direct Access Number — F617
Parameter Type —
Numerical
Factory Default —
200.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Over-Torque Detection Time
Program
Protection
Over-Torque Parameters
This parameter sets the amount of time that the over-torque condition may
exceed the tripping threshold level set at
and
before a trip occurs.
.
Direct Access Number — F618
Parameter Type —
Numerical
Factory Default —
0.50
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 10.0
Units — Seconds
Over-Torque Detection Hysteresis
Program
Protection
Over-Torque Parameters
During a momentary over-torque condition, this parameter provides a torque
threshold level to which the over-torque condition must return within the time
setting of
or an
Over-Torque Trip
will be incurred.
Direct Access Number — F619
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Cooling Fan Control
Program
Protection
Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Direct Access Number — F620
Parameter Type —
Selection List
Factory Default —
Automatic
Changeable During Run —
Yes
Cumulative Operation Time Alarm
Program
Protection
Special Protection Parameters
This parameter sets a run-time value that, once exceeded, closes a discrete
output contact. The output signal may be used to control external equipment or
to engage a brake.
Associate the
Total-Operation-Hours Alarm
setting of
to a
discrete output contactor.
Note:
The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Direct Access Number — F621
Parameter Type —
Numerical
Factory Default —
610.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 999.9
Units — Hours (X 10)
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......