Wiring for Flow selector unit (FS unit) for SHRM-e
Connect communication wire of FS unit to terminal A, B (no polarity) of Hot Water Module.
when the Hot water module connects to SHRM-e system.
NOTE
In case of connecting at least one Hot Water Module in SHRM-e system, all of FS units in the system should be
Single port type FS unit (long piping model) or Multiport type FS unit.
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
▼
Wiring diagram
Output signal function wiring
Connect the following output signals from the hot water module.
Terminal
block No.
Function
Comments
COM
DC12 V (COM)
Common for connector S2 ~ S5
S1
Defrosting output (COM-S1)
DC12 V
Relay coil is less than 16 mA.
S2
Line heater output (COM-S2)
DC12 V
Relay coil is less than 16 mA.
S3
-
-
S4
Heating thermostat ON output (COM-S4)
DC12 V
Relay coil is less than 16 mA.
S5
Pump output (COM-S5)
DC12 V
Relay coil is less than 16 mA.
COM
S2
S1
S5
S3
S4
CN040
(144'/16'%10641.
ȪȢdzȳဇ
ᲬᲪᲪ᳐ǛҮьƠƳƍƜƱ
Ჾ ų᳆᳓ųᲬᲬᲪᲧᲬᲮᲪ᳐
#
ϋٳบǓᣐዴဇ
(14+06'470+6
$
4. 50
IC501
RY005
L401
RY006
RY007
RY008
C170
C150
C140
黒
白
CN030
白
赤
CN074
白
橙
橙
赤
茶
赤
CN075
茶
FAN
黒
CN102
CN101
黒
黒
黒
黒
黒
TA
CN104
CN041
白
CN083
CN067
黒
黒
CN103
黒
白
黒
黒
CN100
CN022
CN060
7X7
7X7
Power supply wire
Communication wire (FS unit)
Remote controller wire
Control wire
A
B
A
B
Terminal block
Remote controller unit
Terminal block for
remote controller wiring
of hot water module
Remote controller wire
(Locally procured)
NOTE
Auxiliary relays (locally procured) must be connected to output signal function wirings to allow connection to the
hot water module output signal functions. The maximum current output signal, from each of the output signal
function wirings, is 16 mA. Please ensure the rated current of the relay coil is less than 16 mA to avoid damage to
the hot water module P.C. board.
▼
Output function wire
CAUTION
Output signal functions are separated from primary basic insulation.
• To prevent noise trouble, use 2-core shield wire.
• Determine the wire length between the hot water module output signal function terminal block and the relay up
to 2 m.
• Locally procure and install protective devices such as the heater and pump.
COM
S1
S2
S3
S4
S5
External
actuator
Output function wire
Hot water module
output signal
function terminal
block (CN60)
Locally procured
Relay
59-EN
60-EN