– 22 –
Characteristics of hot water module flow rate and pressure loss
The following graph shows the range of flow rates used for the hot water module, and the characteristic pressure losses. Use this as an aid in the local pump procurement process.
027type
Min.
Rated
Max.
Water flow rate (L/min)
19.5
22.9
26.3
Pressure loss (kPa)
28.5
40.5
53.5
056type
Min.
Rated
Max.
Water flow rate (L/min)
38.9
45.8
52.6
Pressure loss (kPa)
35.2
44.2
58.2