Periodic Maintenance

For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner 
in use be cleaned and maintained regularly to ensure ef

fi

cient operation of the air conditioner.

When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof 
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit 
at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner’s expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and 
even compressor failure.

Inspection before maintenance

Following inspection must be carried out by a quali

fi

ed installer or quali

fi

ed service person.

Parts

Inspection method

Heat exchanger

Access from inspection opening and remove the access panel. Examine the heat exchanger if 
there is any clogging or damages.

Fan motor

Access from inspection opening and check if any abnormal noise can be heard.

Fan

Access from inspection opening and remove the access panel. Examine the fan if there are any 
waggles, damages or adhesive dust.

Filter

Go to installed location and check if there are any stains or breaks on the 

fi

lter.

Drain pan

Access from inspection opening and remove the access panel. Check if there is any clogging or 
drain water is polluted.

 

q

Maintenance List

Part

Unit

Check (visual / auditory)

Maintenance

Heat exchanger

Indoor / outdoor

Dust / dirt clogging, scratches

Wash the heat exchanger when it is 
clogged.

Fan motor

Indoor / outdoor

Sound

Take appropriate measures when 
abnormal sound is generated.

Filter

Indoor

Dust / dirt, breakage

y

 Wash the 

fi

lter with water when it is 

contaminated.

y

  Replace it when it is damaged.

Fan

Indoor

y

 Vibration, balance

y

  Dust / dirt, appearance

y

  Replace the fan when vibration or 

balance is terrible.

y

 Brush or wash the fan when it is 

contaminated.

Air intake / discharge 
grilles

Indoor / outdoor

Dust / dirt, scratches

Fix or replace them when they are 
deformed or damaged.

Drain pan

Indoor

Dust / dirt clogging, drain 
contamination

Clean the drain pan and check the 
downward slope for smooth drainage.

Ornamental panel, 
louvers

Indoor

Dust / dirt, scratches

Wash them when they are contaminated 
or apply repair coating.

Exterior

Outdoor

y

  Rust, peeling of insulator

y

  Peeling / lift of coat

Apply repair coating.

11

Troubleshooting

If a problem occurs with the air conditioner, 
the OFF timer indicator alternately shows 
the check code and the indoor Unit No. 
in which the problem occurred.

Check code

The indoor Unit No. in which 

the problem occurred.

 

„

Troubleshooting history and con

fi

rmation

You can check the troubleshooting history with the following procedure if a problem occurs with the air conditioner.
(The troubleshooting history records up to 4 incidents.)
You can check it during operation or when operation is stopped.

 

y

If you check the troubleshooting history during OFF timer operation, the OFF timer will be canceled.

Procedure

Description of operation

1

Push the OFF timer button for over 10 seconds and 
the indicators appear as an image indicating the 
troubleshooting history mode has been entered. 
If [   Service check] is displayed, the mode enters in 
the troubleshooting history mode.

 

y

[01: Order of troubleshooting history] appears in the 
temperature indicator.

 

y

The OFF timer indicator alternately shows the 
[check code] and the [indoor Unit No. ] in which the 
problem occurred.

2

Each time the setting button is pushed, the recorded 
troubleshooting history is displayed in sequence.
The troubleshooting history appears in order from [01] 
(newest) to [04] (oldest).

 CAUTION

In the troubleshooting history mode, DO NOT push the 
Menu button for over 10 seconds, doing so deletes the 
entire troubleshooting history of the indoor unit.

3

After you have 

fi

nished checking, push the ON/OFF 

button to return to the regular mode.

 

y

If the air conditioner is operating, it remains operated 
even after the ON/OFF button has been pushed.

  To stop its operation, push the ON/OFF button again.

Содержание MMU-UP0031YHP-E

Страница 1: ...AIR CONDITIONER MULTI TYPE Installation Manual Indoor Unit Model name 1 way Cassette type MMU UP0031YHP E MMU UP0051YHP E MMU UP0071YHP E MMU UP0091YHP E MMU UP0121YHP E For commercial use English ...

Страница 2: ... oder weniger gemäss EN ISO 7779 Information If U series models TU2C Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Content...

Страница 3: ...individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carri...

Страница 4: ...the installation maintenance repair or removal work set the circuit breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Warning indications on the air conditioner unit W...

Страница 5: ...product is broken contact the dealer When the air conditioner must be transported by hand carry it by two or more people Do not move or repair any unit by yourself There is high voltage inside the unit You may get electric shock when removing the cover and main unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Sele...

Страница 6: ...hich is designed to be used outdoors Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is n...

Страница 7: ...he non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Explanations given to user Upon completion of the inst...

Страница 8: ... The installation fuse all types can be used must be used for the power supply line of this conditioner 1 Refer to the Definition of Qualified Installer or Qualified Service Person 2 Accessory parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers For other languages that do not appear in this Installation Manual please refer to the enclosed CD R ...

Страница 9: ...bour pay due attention to the level of noise y Place with poor ventilation Before air ducting work check whether value of air volume static pressure and duct resistance are correct y Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials...

Страница 10: ... a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Using the installation pattern accessory The installation patt...

Страница 11: ...y Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage y Remove the adjust corner caps at the four corners of the ceiling panel and then install the ceiling panel onto the indoor unit y Make sure that the claws of the four adjust corner caps are securely fit Im...

Страница 12: ... the clear drain socket If applying the adhesive socket will be damaged and cause water leakage 5 mm or less 10 to 12 mm hose band tightening margin VP25 vinyl chloride pipe Locally procured 10 mm Socket for VP25 vinyl chloride pipe Locally procured Flexible hose Accessory Heat insulator Drain pipe connecting port Transparent Indoor unit Connecting drain pipe y Connect a hard socket locally procur...

Страница 13: ... indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Pipe size mm Gas side Liquid side Ø9 5 Ø6 4 Connecting refrigerant piping Flaring 1 Cut the pipe with a pipe cutter Remove burrs completely Remaining burrs may cause gas leakage 2 Insert a flare n...

Страница 14: ...iling side Wrap the pipe with the attached heat insulator without any gap between the indoor unit Flare nut Heat insulator of the pipe Banding band Locally procured Union Heat insulation pipe Accessory 7 Electrical connection WARNING y Use the specified wires for wiring connection to the terminals Securely fix them to prevent external forces applied to the terminals from affecting the terminals In...

Страница 15: ...nd model names Communication type TU2C Link U series and future models TCC Link Other than U series Outdoor unit MMY MUPÛÛÛ This letter indicates U series model Other than U series MMY MHPÛÛÛ MMY MAPÛÛÛ MCY MHPÛÛÛ Indoor unit MMÛ UPÛÛÛ This letter indicates U series model Other than U series MMÛ APÛÛÛ Wired remote controller RBC ASCUÛÛÛ This letter indicates U series model Other than U series Wire...

Страница 16: ...connection causes a trouble y Be sure to pass the wires through the bushing of wiring connection port of the indoor unit y Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing etc y The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit y Make a loop on the wire for margin of the length so that the electrical cont...

Страница 17: ...utdoor Outdoor unit Follower outdoor Earth terminal Earth terminal S The ground of a shielded wire S The ground of a shielded wire Control wiring between outdoor units Shield wire Control wiring between indoor and outdoor units Shield wire Control wiring between indoor units Shield wire Indoor unit Earth Earth Earth Earth Indoor unit Indoor unit Indoor unit Remote controller Indoor power supply 22...

Страница 18: ... Change the setup while the air conditioner is not working CAUTION Set only the Code No shown in the following table Do NOT set any other Code No If a Code No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result 1 Push and hold menu button and setting button simultaneously for 10 seconds or more y After a while the display flashes as ...

Страница 19: ...E No in Procedure 3 y Select the following data for the SET DATA in Procedure 4 SET DATA 0000 0001 Remote controller sensor Not used factory default Used When flashes the remote controller sensor is defective Select the SET DATA 0000 not used or replace the remote controller 9 Test run Before test run y Before turning on the circuit breaker carry out the following procedure 1 By using insulation t...

Страница 20: ...ng heating performance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by the remote controller 2 Open the air intake grille y Slide the button of the air intake grille inward and open the air intake grille slowly while holding it Hook lock grille Hook lock grille Grille air intake Screw Direction to open Direction to open Push hook Cleaning of air filters If the air fi...

Страница 21: ...alance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louver...

Страница 22: ...outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote control...

Страница 23: ... ALT Ps sensor trouble I F F24 F24 ALT Pd sensor trouble I F F29 SIM Indoor unit other trouble Indoor unit F30 F30 SIM Occupancy sensor trouble Indoor unit F31 F31 SIM Indoor unit EEPROM trouble I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down Inverter H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock Inverter H03 H03 01 Comp 1 side 02 Comp ...

Страница 24: ... trouble I F P01 ALT Indoor fan motor trouble Indoor unit P03 P03 ALT Discharge temp TD1 trouble I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation Inverter P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage troub...

Страница 25: ...3 08 Fan 1 05 Comp 1 Comp 3 09 Comp 1 Fan 1 06 Comp 2 Comp 3 0A Comp 2 Fan 1 07 Comp 1 Comp 2 Comp 3 0B Comp 1 Comp 2 Fan 1 08 Fan 10 Fan 2 09 Comp 1 Fan 11 Comp 1 Fan 2 0A Comp 2 Fan 12 Comp 2 Fan 2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan 2 0C Comp 3 Fan 18 Fan 1 Fan 2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan 1 Fan 2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan 1 Fan 2 0F All 1B All Inverter trouble Inverter t...

Страница 26: ... E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law NOTE This declaration becomes invalid if technical or operational modifications are introduced wi...

Страница 27: ...door unit installed room m Concentration limit kg m The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device e g charged amount 10 kg Outdoor unit e g charged amount 15 kg Indoor unit Room A Room B Room C Room D ...

Страница 28: ...o 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 High ceiling setup CODE No 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE N...

Страница 29: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1127650301 ...

Отзывы: