background image

34-EN

33-EN

– 17 –

8

Applicable controls

REQUIREMENT

When the air conditioner is used for the 

fi

rst time, 

it will take some moments after the power has 
been turned on before the remote controller 
becomes available for operations: This is normal 
and is not indicative of trouble.

 

y

Concerning the automatic addresses 
(The automatic addresses are set up by 
performing operations on the outdoor interface 
circuit board.)

  While the automatic addresses are being set 

up, no remote controller operations can be 
performed. Setup takes up to 10 minutes (usually 
about 5 minutes).

 

y

When the power is turned on after automatically 
address setup, It takes up to 10 minutes (usually 
about 3 minute) for the outdoor unit to start 
operating after the power has been turned on.

Before the air conditioner was shipped from the 
factory, all units are set to [STANDARD] (factory 
default).
If necessary, change the indoor unit settings.
The settings are changed by operating the wired 
remote controller.
*  The settings cannot be changed using only a 

wireless remote controller and simple remote 
controller by itself so install a wired remote 
controller separately as well.

 

„

Applicable controls setup 
(settings at the site)

Remote controller model name:
RBC-ASC11E

Basic procedure

Be sure to stop the air conditioner before making 
settings.

(Change the setup while the air conditioner is not 
working.)

 CAUTION

Set only the Code No. shown in the following table: 
Do NOT set any other Code No.
If a Code No. not listed is set, it may not be possible 
to operate the air conditioner or other trouble with 
the product may result.

1

Push and hold menu button and [

setting button simultaneously for 
10 seconds or more.

 

y

After a while, the display 

fl

ashes as shown in the 

fi

gure. “ALL” is displayed as indoor unit numbers 

during initial communication immediately after 
the power has been turned on.

Indoor unit No.

2

Each time [

] [

] setting button is 

pushed, indoor unit numbers in the group 
control change cyclically. Select the indoor 
unit to change settings for.

 

y

The fan of the selected indoor unit runs.

  The indoor unit can be con

fi

rmed for which to 

change settings.

3

Push OFF timer button to con

fi

rm the 

selected indoor unit.

Set data

Code No.

4

Push the menu button to make Code No. 

 ] 

fl

ash. Change Code No. [ 

 ] with 

[

] [

] setting button.

5

Push the menu button to make Set data 
[

 

 

fl

ash. Change Set data [

 

 

with [

] [

] setting button.

6

Push OFF timer button.
By doing so, the setup is completed.

 

y

To change other settings of the selected indoor 
unit, repeat from Procedure 

4

.

7

When all the settings have been completed, 
push ON/OFF button to determine the 
settings.

“ 

 

” 

fl

ashes and then the display content 

disappears and the air conditioner enters the 
normal stop mode. (The remote controller is 
unavailable while “ 

 

” is 

fl

ashing.)

 

y

To change settings of another indoor unit, repeat 
from Procedure 

1

.

Содержание MMU-UP0031YHP-E

Страница 1: ...AIR CONDITIONER MULTI TYPE Installation Manual Indoor Unit Model name 1 way Cassette type MMU UP0031YHP E MMU UP0051YHP E MMU UP0071YHP E MMU UP0091YHP E MMU UP0121YHP E For commercial use English ...

Страница 2: ... oder weniger gemäss EN ISO 7779 Information If U series models TU2C Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Content...

Страница 3: ...individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carri...

Страница 4: ...the installation maintenance repair or removal work set the circuit breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Warning indications on the air conditioner unit W...

Страница 5: ...product is broken contact the dealer When the air conditioner must be transported by hand carry it by two or more people Do not move or repair any unit by yourself There is high voltage inside the unit You may get electric shock when removing the cover and main unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Sele...

Страница 6: ...hich is designed to be used outdoors Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage or other trouble Carry out the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is n...

Страница 7: ...he non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Explanations given to user Upon completion of the inst...

Страница 8: ... The installation fuse all types can be used must be used for the power supply line of this conditioner 1 Refer to the Definition of Qualified Installer or Qualified Service Person 2 Accessory parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Hand over to customers For other languages that do not appear in this Installation Manual please refer to the enclosed CD R ...

Страница 9: ...bour pay due attention to the level of noise y Place with poor ventilation Before air ducting work check whether value of air volume static pressure and duct resistance are correct y Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materials...

Страница 10: ... a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Using the installation pattern accessory The installation patt...

Страница 11: ...y Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage y Remove the adjust corner caps at the four corners of the ceiling panel and then install the ceiling panel onto the indoor unit y Make sure that the claws of the four adjust corner caps are securely fit Im...

Страница 12: ... the clear drain socket If applying the adhesive socket will be damaged and cause water leakage 5 mm or less 10 to 12 mm hose band tightening margin VP25 vinyl chloride pipe Locally procured 10 mm Socket for VP25 vinyl chloride pipe Locally procured Flexible hose Accessory Heat insulator Drain pipe connecting port Transparent Indoor unit Connecting drain pipe y Connect a hard socket locally procur...

Страница 13: ... indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Pipe size mm Gas side Liquid side Ø9 5 Ø6 4 Connecting refrigerant piping Flaring 1 Cut the pipe with a pipe cutter Remove burrs completely Remaining burrs may cause gas leakage 2 Insert a flare n...

Страница 14: ...iling side Wrap the pipe with the attached heat insulator without any gap between the indoor unit Flare nut Heat insulator of the pipe Banding band Locally procured Union Heat insulation pipe Accessory 7 Electrical connection WARNING y Use the specified wires for wiring connection to the terminals Securely fix them to prevent external forces applied to the terminals from affecting the terminals In...

Страница 15: ...nd model names Communication type TU2C Link U series and future models TCC Link Other than U series Outdoor unit MMY MUPÛÛÛ This letter indicates U series model Other than U series MMY MHPÛÛÛ MMY MAPÛÛÛ MCY MHPÛÛÛ Indoor unit MMÛ UPÛÛÛ This letter indicates U series model Other than U series MMÛ APÛÛÛ Wired remote controller RBC ASCUÛÛÛ This letter indicates U series model Other than U series Wire...

Страница 16: ...connection causes a trouble y Be sure to pass the wires through the bushing of wiring connection port of the indoor unit y Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing etc y The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit y Make a loop on the wire for margin of the length so that the electrical cont...

Страница 17: ...utdoor Outdoor unit Follower outdoor Earth terminal Earth terminal S The ground of a shielded wire S The ground of a shielded wire Control wiring between outdoor units Shield wire Control wiring between indoor and outdoor units Shield wire Control wiring between indoor units Shield wire Indoor unit Earth Earth Earth Earth Indoor unit Indoor unit Indoor unit Remote controller Indoor power supply 22...

Страница 18: ... Change the setup while the air conditioner is not working CAUTION Set only the Code No shown in the following table Do NOT set any other Code No If a Code No not listed is set it may not be possible to operate the air conditioner or other trouble with the product may result 1 Push and hold menu button and setting button simultaneously for 10 seconds or more y After a while the display flashes as ...

Страница 19: ...E No in Procedure 3 y Select the following data for the SET DATA in Procedure 4 SET DATA 0000 0001 Remote controller sensor Not used factory default Used When flashes the remote controller sensor is defective Select the SET DATA 0000 not used or replace the remote controller 9 Test run Before test run y Before turning on the circuit breaker carry out the following procedure 1 By using insulation t...

Страница 20: ...ng heating performance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by the remote controller 2 Open the air intake grille y Slide the button of the air intake grille inward and open the air intake grille slowly while holding it Hook lock grille Hook lock grille Grille air intake Screw Direction to open Direction to open Push hook Cleaning of air filters If the air fi...

Страница 21: ...alance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louver...

Страница 22: ...outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote control...

Страница 23: ... ALT Ps sensor trouble I F F24 F24 ALT Pd sensor trouble I F F29 SIM Indoor unit other trouble Indoor unit F30 F30 SIM Occupancy sensor trouble Indoor unit F31 F31 SIM Indoor unit EEPROM trouble I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down Inverter H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock Inverter H03 H03 01 Comp 1 side 02 Comp ...

Страница 24: ... trouble I F P01 ALT Indoor fan motor trouble Indoor unit P03 P03 ALT Discharge temp TD1 trouble I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation Inverter P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage troub...

Страница 25: ...3 08 Fan 1 05 Comp 1 Comp 3 09 Comp 1 Fan 1 06 Comp 2 Comp 3 0A Comp 2 Fan 1 07 Comp 1 Comp 2 Comp 3 0B Comp 1 Comp 2 Fan 1 08 Fan 10 Fan 2 09 Comp 1 Fan 11 Comp 1 Fan 2 0A Comp 2 Fan 12 Comp 2 Fan 2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan 2 0C Comp 3 Fan 18 Fan 1 Fan 2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan 1 Fan 2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan 1 Fan 2 0F All 1B All Inverter trouble Inverter t...

Страница 26: ... E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law NOTE This declaration becomes invalid if technical or operational modifications are introduced wi...

Страница 27: ...door unit installed room m Concentration limit kg m The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device e g charged amount 10 kg Outdoor unit e g charged amount 15 kg Indoor unit Room A Room B Room C Room D ...

Страница 28: ...o 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 High ceiling setup CODE No 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE N...

Страница 29: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1127650301 ...

Отзывы: