46
9
TEST RUN
n
Before test run
• Before turning on the power supply, carry out
the following procedure.
1) Using 500V-megger, check that resistance
of 1M
Ω
or more exists between the termi-
nal block of the power supply and the earth
(grounding).
If resistance of less than 1M
Ω
is detected,
do not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
• To protect the compressor at activation time,
leave power-ON for 12 hours or more be for
operating.
• Never press the electromagnetic contactor to
forcibly perform a test run.
(This is very dangerous because the protec-
tive device does not work.)
• Before starting a test run, be sure to set
addresses following the installation manual
supplied with the outdoor unit.
n
How to execute a test run
Using the remote controller, operate the unit as
usual.
For the procedure of the operation, refer to the
attached Owner’s Manual.
A forced test run can be executed in the follow-
ing procedure even if the operation stops by
thermo.-OFF.
In order to prevent a serial operation, the forced
test run is released after 60 minutes have
passed and returns to the usual operation.
CAUTION
• Do not use the forced test run for cases other
than the test run because it applies an excessive
load to the devices.
In case of wired remote controller
In case of wireless remote controller
Procedure
1
Turn on the power of the air conditioner.
When power is turned on for the first time after installation, it takes approx. 5 minutes until the remote con-
troller becomes available.
In the case of subsequent power-on, it takes approx. 1 minute until the remote controller becomes available.
Execute a test run after the predetermined time has passed.
Procedure
2
Push “ON/OFF” button on the remote controller, select [
COOL] or [
HEAT] with “MODE” button, and
then select [
HIGH] with “FAN” button.
Procedure
3
Procedure
1
Keep
TEST
button pushed for 4 seconds or more.
[TEST] is displayed on the display part and the
selection of mode in the test mode is permitted.
Procedure
2
Push
ON / OFF
button.
Procedure
3
Using
MODE
button, select the operation mode,
[
COOL] or [
HEAT].
• Do not run the air conditioner in a mode other
than [
COOL] or [
HEAT].
• The temperature controlling function does not
work during test run.
• The detection of error is performed as usual.
Procedure
4
After the test run, push
ON / OFF
button to stop a test
run. (Display part is same as Procedure
1
.)
Procedure
5
Push
TEST
check button to cancel (release from) the
test run mode. ([TEST] disappears on the display
and the status returns to a normal.)
Procedure
6
Repeat procedures
4
→
5
→
4
→
5
.
Indicators “Operation” (green), “Timer” (green), and “Ready” (orange) in the wireless receiver section flash in
approx. 10 seconds, and the air conditioner starts operation.
If any of these indicators does not flash, repeat Procedures
3
to
5
.
Procedure
7
Upon completion of the test run, push “ON/OFF” button to stop operation.
<Overview of test run operations using the wireless remote controller>
u
Cooling test run:
ON/OFF
→
18°C
→
19°C
→
18°C
→
19°C
→
18°C
→
19°C
→
18°C
→
(test run)
→
ON/OFF
u
Heating test run:
ON/OFF
→
30°C
→
29°C
→
30°C
→
29°C
→
30°C
→
29°C
→
30°C
→
(test run)
→
ON/OFF
Procedure
4
Cooling test run
After confirming a signal receiving sound “beep” immediately
set the temperature to 19°C with the temp. setup buttons.
Heating test run
After confirming a signal receiving sound “beep” immediately
set the temperature to 29°C with the temp. setup buttons.
Procedure
5
Cooling test run
After confirming a signal receiving sound “beep” immediately
set the temperature to 18°C with the temp. setup buttons.
Heating test run
After confirming a signal receiving sound “beep” immediately
set the temperature to 30°C with the temp. setup buttons.
Cooling test run
Set the temperature to 18°C with the temp. setup buttons.
Heating test run
Set the temperature to 30°C with the temp. setup buttons.
2, 4
3
1, 5
Always select
[ HIGH]
air volume.
2
3, 4,
5, 6
2, 7