61
n
Monitoring function of remote controller switch
When using the remote controller (Model Name: RBC-AMT32E), the following monitoring
function can be utilized.
Calling of display
<Contents>
The temperature of each sensor of the remote controller, indoor unit and outdoor unit and the operating
status can be checked by calling the service monitor mode from the remote controller.
<Procedure>
1
Push
TEST
+
CL
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
The service monitor goes on and firstly the temperature of the CODE No.
is displayed.
ò
1 2 3 4
Returns to normal display
<Operation procedure>
2
4
1
3
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
2
Push
TEMP.
button to change CODE No. to the
CODE No. to be monitored.
For display code, refer to the following table.
ò
3
Push
UNIT LOUVER
button to change to CODE No. to
be monitored.
The sensor temperature of indoor unit or
outdoor unit in its refrigerant line and the
operating status are monitored.
ò
4
Push
TEST
button to return the status to the
normal display.
(Note 1)
In the group connection, only data of the header indoor unit
is displayed.
(Note 2)
01: Only compressor 1 is ON.
10: Only compressor 2 is ON.
11: Both compressor 1 and 2 are ON.
(Note 3)
For the CODE No., an example of header unit is described.
(Note 4)
Upper girder of CODE No. indicates the outdoor
unit No.
1: Header unit (A)
2: Follower unit (B)
3: Follower unit (C)
4: Follower unit (D)
Indoor unit data
System data
Individual outdoor unit data (Note 3, 4)
CODE
No.
00
01
02
03
04
05
08
F2
F3
0A
0B
0C
0D
Data name
Room temp.
(Under control)
(Note 1)
Room temp. (Remote controller)
Indoor suction temp. (TA)
Indoor coil temp. (TCJ)
Indoor coil temp. (TC2)
Indoor coil temp. (TC1)
Indoor PMV opening degree
Indoor fan accumulated operation time
Filter sign time
No. of connected indoor units
Total HP of connected indoor units
No. of connected outdoor units
Total HP of connected outdoor units
Unit
°C
°C
°C
°C
°C
°C
pls
h
h
unit
HP
unit
HP
Display
form
× 1
× 1
× 1
× 1
× 1
× 1
× 1/10
× 100
× 1
× 10
× 10
CODE
No.
10
11
12
13
14
15
16
17
18
19
1A
1B
1D
1E
1F
Data name
Compressor 1 discharge temp. (Td1)
Compressor 2 discharge temp. (Td2)
High pressure sensor detection pressure (Pd)
Low pressure sensor detection pressure (Ps)
Suction temp. (TS)
Outdoor coil temp. (TE)
Liquid side temp. (TL)
Outside temp. (TO)
Low pressure saturation temp. (TU)
Compressor 1 current (I1)
Compressor 2 current (I2)
PMV1 + 2 opening degree
Compressor 1, 2 ON/OFF
Outdoor fan mode
Outdoor unit HP
Unit
°C
°C
MPa
MPa
°C
°C
°C
°C
°C
A
A
pls
—
—
HP
Display
form
× 1
× 1
× 100
× 100
× 1
× 1
× 1
× 1
× 1
× 10
× 10
× 1/10
(Note 2)
0 to 31
× 1