135
No.
9
Part name
Drain pan
(Continued)
Procedure
1. Detachment (In cases of AP027/AP048)
1) Perform work Detachment 1 of
3
.
Perform work Detachment 1 of
7
.
2) Take off the drain cap and then extract
accumulated drain water in the drain pan.
Note)
When taking off the drain cap, be sure to receive drain
water in a bucket, etc.
3) Take off screw (Ø4 × 8, 1 pc.) which fixes the
partition board and then remove it as if lifting up it.
• As shown in the right Photo, the drain pan is
fixed by the drain pan fixing sheet metal at the
both sides of the fan motor. Take off each
screw and then remove the drain pan fixing
board. (Ø4 × 8, 1 pc. each)
4) Take off screws at 4 corners (Ø4 × 8, 4 pcs.)
which fix the drain pan and then pull out the
drain pan quietly.
2. Attachment (In cases of AP027/AP048)
1) Attach the drain pan as original while passing
the fan motor wiring and the drain pump sensor
wiring through the specified hole.
Note)
Be sure to pass the drain pump sensor wiring through
the specified fixing slit of the inner foaming.
2) Attach all the partition board, electric parts box,
ceiling panel, air filter and center panel as
original.
For wiring in the electric parts box, be sure to
wire it as original.
• Be sure necessarily to attach the drain pan
fixing sheet metal for AP048 type.
Remarks
Total 4 screws
Total 4 screws
Drain pump/
Drain pump/
sensor wiring
sensor wiring
Inner foaming
Inner foaming
In cases of AP027/AP048
In case of AP048
Partition board
Partition board
Screw
Screw
Drain cap
Drain pan fixing board
Drain pan fixing board
Screws
Total 4 screws
Drain pump/
Drain pump/
sensor wiring fixing slit
sensor wiring fixing slit
Drain pump/
sensor wiring
Inner foaming
Partition board
Screw
Drain pan fixing board
Drain pump/
sensor wiring fixing slit