Toshiba MML-UP0071BH-E Скачать руководство пользователя страница 27

– 26 –

Co
nfir
mati

on
 of 
ind
o

o

r u

n

it 

setu

p

Prior

 to 
deliv

er

y to
 the cu

stome
r, che

ck

 the a

ddr
ess and 

se

tup o

f the 

in

door

 un
it,

 which h

a

s bee

n installed in t

h

is

 tim
e

 an
d fi
ll 

the che

ck sh
eet (

F

ollo
wing 

table)

Da
ta of f

our
 units can b

e

 en
ter
ed in th

is che

ck sh
eet. Copy t

his sh

eet accor

d

ing
 to the

 No
. of th

e indoo

r u
n

its. If th

e install

ed system is a

 group con

tro

l s

yste

m

, use

 

this sheet 

by ente

ring
 each line system into e

a

ch inst

allation 

man

ual atta

ch

ed to

 the o

ther indo

or 
units.

REQUI

R

EMENT

This check

 she
et i

s r

equired fo

r maintenance 

after

 install

ation. 

Fil

l this s

heet and 

then pass this In

stallation Man

ual 
to 

the 

cust

om
ers.

In

door 

unit setup

 che

ck sh

eet

Indoor uni

t

Indoor 

unit

Indoor uni

t

Indoor uni

t

Room 

name

Room name

R

oom na

me

Room 

name

M

ode

l

M

odel

M

odel

M

odel

Check i

n

door unit addr

ess. 

(F

or 
chec

k m
ethod, re

fer
 to 
Service 

Man

ual

 of ou

tdoo

uni
t.)

*In 
ca

se of a si

n

gle

 sys

tem

, it i
s unne

cessar

y to enter the

 indoor

 ad
dress

. (COD

E NO.: 

Line [1

2

], 

Indoor

 [13], Group [14], C

en

tra

l control [03])

Li

ne

Indoor

Group

Line

Indo

or

G

roup

Li

ne

Indoor

Group

Line

Indoor

Group

Cent

ral
 control

 address

Central 

c

ont
rol 
a

ddress

Ce
nt

ral
 cont

rol
 addres

s

C

entral 

control 

address

Vari

ous setup

Various 

s

et

u

p

V

ari
ous set

u

p

V

a

riou
s

 setup

Have you changed

 li

g

hting time

 of 

fil

ter si

gn? If 

no
t, 

fill 

ch

eck mar

k [×] 
in [NO 

CHANGE], and fi

ll chec

m

ark

 [×] in 

[ITEM

] if

 chang

ed, res

pecti

ve

ly

.

(For 

check method, refer t

o APPLIC

ABLE CO

NTROLS 

in t
his man

ual
.)

Fil

ter sign l

ighti
ng

 ti

m

(C

ODE NO.

 [01]
)

NO
 CH

A

N

G

E

N

O

NE

[0000]

150H

[0001]

2500H

[0002]

5000H

[0003]

10000H

[0004]

Filter

 s

ign 
lighting time 

(C

O

D

E NO

. [01])

NO
 CHAN

G

E

NO
NE

[0

0

00]

150H

[00
01]

2500H

[00
02]

5000H

[00
03]

10000

H

[00
04]

Fi

lter
 sign 

light

ing t

ime 

(C

O

D

E

 N

O

. [0

1])

NO CHANG

E

NONE

[0000]

15
0H

[0001]

25
00H

[0002]

50
00H

[0003]

10
000H

[0004]

Fil

ter

 sign 

lighti
n

g ti
m

(CO

D

E N
O. 
[01])

N

O

 CH

ANGE

N

O

NE

[0000

]

150H

[0001

]

2500H

[0002

]

5000H

[0003

]

10000H

[0004

]

Have you changed

 detected tem

p. 

sh

ift value? If

 n

ot, fil
l c

heck 

ma
rk 
[×] in 

[NO CHANGE

], and

 fi

ll chec

k m
ar

k [×] in [ITE

M

] if 
chan
ged, re

specti

ve

ly

.

(For 

check method, refer t

o APPLIC

ABLE CO

NTROLS 

in t
his man

ual
.)

Det
ect

ed tem

p.

 shif
t value setu

(C

ODE NO.

 [06]
)

NO
 CH

A

N

G

E

N

O

 SH
IFT

[0000]

+1°C

[0001]

+2°C

[0002]

+3°C

[0003]

+4°C

[0004]

+5°C

[0005]

+6°C

[0006]

Det
ect

ed tem

p. s

hift 

va

lue s

etup 

(C

O

D

E NO

. [06])

NO
 CHAN

G

E

NO SHIFT

[00
00]

+1°
C

[00
01]

+2°
C

[00
02]

+3°
C

[00
03]

+4°
C

[00
04]

+5°
C

[00
05]

+6°
C

[00
06]

Det
ect

ed 
te

m

p. shift

 val
u

se

tup 

(C

O

D

E

 N

O

. [0

6])

NO CHANG

E

NO SHIFT

[0000]

+1
°C

[0001]

+2
°C

[0002]

+3
°C

[0003]

+4
°C

[0004]

+5
°C

[0005]

+6
°C

[0006]

D

etected tem

p. 

sh

ift value setup 

(CO

D

E N
O. 
[06])

N

O

 CH

ANGE

N

O

 SHIFT

[0000

]

+1°C

[0001

]

+2°C

[0002

]

+3°C

[0003

]

+4°C

[0004

]

+5°C

[0005

]

+6°C

[0006

]

Rem

ote contro

ller senso

(C

ODE NO.

 [32]
)

NO CHAN

G

E

NOT IN

 USE

[0

000]

IN

 USE

[0

001]

Rem

ote c
ontr

oll

er

 se
nsor 

(C

O

D

E NO

. [32])

NO CHANGE

NOT IN USE

[0000]

IN USE

[0001]

Remote controll

e

r sensor

 

(C

O

D

E

 N

O

. [3

2])

NO
 CH

ANGE

NO
T I
N

 USE

[00
00]

IN U

S

E

[00
01]

Rem

ote

 con

tro

ller 
sens

or 

(CO

D

E N
O. 
[32])

NO CHANG

E

NOT IN USE

[0000]

IN USE

[0001]

Incorporat

ion of part

sold 

separ

ately

In

corporati

on of

 parts 

sold 

se
parat

ely

Incorporat

ion of part

sol
d

 

separa

tely

In

corporat

ion of

 part

s

 sold 

separ

ate
ly

Have you i

nc

orpor
ate
d the followi

ng par

ts sold separ

ately?

 If i
nc

orpor
ate
d, fill
 check

 m

ark

 [×] in 

eac

[ITEM

].

(W
hen i

nc

orpor
ating, 

the setup change is 

ne
cessar

y i

n som

e c

ases.
 Fo

setu

p ch

ange 

method, r

efer 
to Insta

llation Ma

nual 

atta

che
d to each

 par
t sold 

separ

atel
y.)

O

thers

 ( 

     

    

    )

O

thers

 ( 

     

    

    )

Ot

her
s (

    

     

    

 )

Ot

her
s (

    

     

    

 )

Other

s (

   

    

   

    

)

Other

s (

   

    

   

    

)

O

thers

 ( 

   

    

   

   )

O

thers

 ( 

   

    

   

   )

51-EN

52-EN

Содержание MML-UP0071BH-E

Страница 1: ...IONER MULTI TYPE Installation Manual R410A Indoor Unit Floor Standing Concealed Type MML UP0071BH E MML UP0091BH E MML UP0121BH E MML UP0151BH E MML UP0181BH E MML UP0241BH E Model name For commercial use English ...

Страница 2: ...Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of insta...

Страница 3: ...e knowledge related to these operations The qualified service person who is allowed to do the electrical work involved in installation repair relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Car...

Страница 4: ...fferent from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the O...

Страница 5: ...Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakage...

Страница 6: ...t first conducting these checks If there is any kind of trouble such as check code display has appeared smell of burning abnormal sounds the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take steps to ensure that the power ...

Страница 7: ...oil enter the refrigerating cycle during installation work To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the R410A refrigerant For connecting pipes use new and clean piping designed fo...

Страница 8: ...art a fire Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations where an in house power generator is used for the power supply The power line frequency and voltage may fluctuate and the air conditioner ...

Страница 9: ...remove the air filter Air filter 150 or more Service space at Power supply Service space at pipe side A 100 85 150 or more 4 Installation CAUTION CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury Do not put any heavy article on the indoor unit or let a person get on it Even units are packaged Carry in the indoor unit as it is packaged if possib...

Страница 10: ...580 610 UP015 to UP024 880 910 A B 140 315 600 Floor Hole is provided to rear side Unit mm Electrical control box Electrical control box mounting screws 2 pcs Installation of remote controller sold separately For installation of the wired remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller wire together with the refrigerant pipe or dr...

Страница 11: ...Install the drain pan Accessory on the pipe side of the indoor unit Drain pan Accessory Cut the insulation insert the protrusion on the drain pan into the hole and then install it by pushing it in the directions indicated by the arrows Drain pan screw Accessory Pipe material size and insulator The following materials for piping work and insulating process are procured locally Connecting drain pipe...

Страница 12: ...sing Do not apply refrigerating machine oil to the flare surface Model MML Outside diameter size mm Gas side Liquid side UP007 UP012 9 5 6 4 UP015 UP018 12 7 6 4 UP024 15 9 9 5 Outside diameter size mm R410A tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outside diameter size mm A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 B A Tightening connection CAUTION CAUTION Do not apply ex...

Страница 13: ...nt pipes completes Power supply wire and communication wires specifications Power supply wire and communication wires are locally procured For the power supply specifications follow to the table below If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manua...

Страница 14: ...re models other than U series their system diagrams for the wiring specifications are the same as the system diagram above SMMS u U series In the case of combining with outdoor units other than Super Modular Multi System u series SMMS u The length of the communication line L1 L2 L3 means the total length of the inter unit wire length between indoor and outdoor units added with the central control ...

Страница 15: ...0 m Unit type Outdoor unit U series U series U series U series Indoor unit U series U series U series U series Remote controller Remote sensor U series U series U series U series Communication type TU2C Link TCC Link Max number of connectable units 16 8 L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller Remote controller wiring For numb...

Страница 16: ...ller wiring of indoor unit Remote controller wire Locally procured 8 Applicable controls REQUIREMENT When the air conditioner is used for the first time it will take some moments after the power has been turned on before the remote controller becomes available for operations This is normal and is not indicative of trouble Concerning the automatic addresses The automatic addresses are set up by per...

Страница 17: ...5 6 7 Specify 01 for the Code No in Procedure 4 Select the set data of filter sign term from the following table for the set data in Procedure 5 The filter sign may be unavailable depending on the remote controllers Set data Code No Set data Detection temperature shift value 0000 No shift Factory default 0001 1 C 0002 2 C 0003 3 C 0004 4 C 0005 5 C 0006 6 C Set data Filter sign term 0000 None 0001...

Страница 18: ...usual 4 After the test run push OFF timer button to stop a test run TEST disappears on the display and the air conditioner enters the normal stop mode 4 3 1 2 3 Wireless remote controller 1 Turn on the power of the air conditioner When power is turned on for the first time after installation it takes approx 5 minutes until the remote controller becomes available In the case of subsequent power on ...

Страница 19: ...ure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any clogging or damages Fan motor Access from inspection opening and check if any abnormal noise can be heard Fan Acce...

Страница 20: ... been entered If Service check is displayed the mode enters in the troubleshooting history mode 01 Order of troubleshooting history appears in the temperature indicator The OFF timer indicator alternately shows the check code and the indoor Unit No in which the problem occurred 2 Each time the setting button is pushed the recorded troubleshooting history is displayed in sequence The troubleshootin...

Страница 21: ...unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote controller E10 Communication trouble be...

Страница 22: ... 03 Comp 3 side Compressor break down Compressor inverter H02 H02 01 Comp 1 side 1 Comp 1 side 02 Comp 2 side 2 Comp 2 side 03 Comp 3 side Compressor trouble lock Compressor inverter H03 H03 01 Comp 1 side 1 Comp 1 side 02 Comp 2 side 2 Comp 2 side 03 Comp 3 side Current detect circuit system trouble Compressor inverter H04 H04 Comp 1 case thermostat operation I F H05 H05 TD1 sensor miswiring I F ...

Страница 23: ...2 Comp 2 side 2E Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage trouble comp I F P07 P07 01 Comp 1 side 1C Comp 1 side 02 Comp 2 side 2C Comp 2 side 03 Comp 3 side 04 Heat sink ALT Heat sink overheat trouble Heat sink dew condensation trouble Compressor inverter I F P10 P10 Detecte...

Страница 24: ... 2 Fan 12 Comp 2 Fan2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan2 0C Comp 3 Fan 18 Fan1 Fan2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan1 Fan2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan1 Fan2 0F All 1B All Inverter trouble Inverter trouble Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxil...

Страница 25: ...ara Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MML UP0071BH E MML UP0091BH E MML UP0121BH E MML UP0151BH E MML UP0181BH E MML UP0241BH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Ai...

Страница 26: ...ooms or install mechanical ventilation combined with a gas leak detection device The concentration is as given below Refrigerant Concentration Limit shall be in accordance with local regulations NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The ...

Страница 27: ... 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively...

Страница 28: ...EB99841301 ...

Отзывы: