– 13 –

SMMS Floor Standing Concealed Type

Installation Manual

SMMS Floor Standing Concealed Type

Installation Manual

„

Remote controller sensor

The temperature sensor of the indoor unit senses room 
temperature usually. Set the remote controller sensor 
to sense the temperature around the remote controller.
Select items following the basic operation procedure 

 

(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• Specify [32] for the CODE No. in Procedure 

3

.

• Select the following data for the SET DATA in 

Procedure 

4

.

When 

 flashes, the remote controller sensor is 

defective.
Select the SET DATA [0000] (not used) or replace the 
remote controller.

„

Group control

In a group control, a remote controller can control up to 
maximum 8 units.
• The wired remote controller only can control a group 

control. The wireless remote controller is unavailable 
for this control.

• For wiring procedure and wires of the individual line 

(Identical refrigerant line) system, refer to “Electrical 
Connection” in this Manual.

• Wiring between indoor units in a group is performed 

in the following procedure.

• Connect the indoor units by connecting the remote 

controller wires from the remote controller terminal 
blocks (A, B) of the indoor unit connected with a 
remote controller to the remote controller terminal 
blocks (A, B) of the other indoor unit. (Non-polarity)

• For address setup, refer to the Installation Manual 

attached to the outdoor unit.

9

Test Run

„

Before test run

• Before turning on the power supply, carry out the 

following procedure.

1) By using 500 V-megger, check that resistance 

of 1 M

Ω

 or more exists between the terminal 

block L to N and the earth (grounding).

 

If resistance of less than 1 M

Ω

 is detected, do 

not run the unit.

2) Check the valve of the outdoor unit being 

opened fully.

• To protect the compressor at activation time, leave 

power-ON for 12 hours or more before operating.

• Do not press the electromagnetic contactor to 

forcibly perform a test run. (This is very dangerous 
because the protective device does not work.)

• Before starting a test run, set addresses by following 

the Installation Manual supplied with the outdoor 
unit.

„

Execute a test run

• When a fan operation is to be performed for an 

individual indoor unit, turn off the power, short CN72 
on the circuit board, and then turn the power back 
on. (First set the operating mode to “fan,” and then 
operate.) When the test run has been performed 
using this method, do NOT forget to release the 
shorting of CN72 after the test run is completed.

Operate the unit with the wired remote controller as 
usual.

 

For the procedure of the operation, refer to the 
attached to the outdoor unit Owner’s Manual.

 

A forced test run can be executed in the following 
procedure even if the operation stops by thermostat-
OFF.

 

In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation.

CAUTION

Do not use the forced test run for cases other than the 
test run because it applies an excessive load to the 
devices.

SET DATA

0000

0001

Remote controller 
sensor

Not used 

(Factory default)

Used

Wired remote controller

1

Push 

 button for 4 seconds or more. 

[TEST] is displayed on the display part and 
the selection of mode in the test mode is 
permitted.

2

Push  

button.

3

Select the operation mode with 

 

button, [

Cool] or [

Heat].

• Do not run the air conditioner in a mode other 

than [

Cool] or [

Heat].

• The temperature controlling function does not 

work during test run.

• The detection of error is performed as usual.

4

After the test run, push 

 button to 

stop a test run.

(Display part is same as procedure 1.)

5

Push 

 button to cancel (release from) the 

test run mode.

([TEST] disappears on the display and the status 
returns to a normal.)

Wireless remote controller

1

Remove a small screw which fixes the 
nameplate of the receiver unit.

Remove the nameplate of the sensor section by 
inserting a flat-blade screwdriver into the notch at 
the bottom of the plate, and set the Dip switch to 
[TEST RUN ON].

2

Execute a test operation with 

 ON / OFF 

button on the wireless remote controller.

, and 

 LED flash during test operation.

• Under status of [TEST RUN ON], the 

temperature adjustment from the wireless 
remote controller is invalid.

Do not use this method in the operation other than 
test operation because the equipment is 
damaged.

3

Use either Cool or Heat operation mode for a 
test operation.

• The outdoor unit does not operate approx. 3 

minutes after power-ON and operation stop.

4

After the test operation finished, stop the air 
conditioner from the wireless remote 
controller, and return Dip switch of the 
receiver section as before.

(A 60-minutes timer clearing function is attached 
to the receiver section in order to prevent a 
continuous test operation.)

2, 4

3

1,5

Small 
screw

Nameplate

Notch

M4 × 25 screw 

(2 pieces)

Spacer

Receiver unit

25-EN

26-EN

+00EH99880701_01EN.book  Page 13  Thursday, April 7, 2011  4:47 PM

Содержание MML-AP0074BH-E

Страница 1: ...t Model name Floor Standing Concealed Type MML AP0074BH E MML AP0094BH E MML AP0124BH E MML AP0154BH E MML AP0184BH E MML AP0244BH E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99880701_01EN book Page 1 Thursday April 7 2011 4 47 PM ...

Страница 2: ... work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in su...

Страница 3: ...ective toe cap Repair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts Y...

Страница 4: ...round the packing carton You may injure yourself if the bands should break Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down result...

Страница 5: ...on and contact a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage n...

Страница 6: ...ance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations where an in house power generator is used ...

Страница 7: ...air filter to the arrow mark and remove the air filter Air filter 220 or more Service space at Power supply Service space at pipe side 220 or more A 70 4 Installation CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury Do not put a heavy article on the indoor unit or let a person get on it Even units are packaged Carry in the indoor unit as it is...

Страница 8: ... control box Foamed polystylene cushion Both left and right A B 110 220 Front side Unit mm Model MML A B AP007 to AP012 580 610 AP015 to AP024 880 910 A B 140 315 600 Floor Hole is provided to rear side Unit mm Electrical control box Electrical control box mounting screws 2 pcs Installation of remote controller Sold separately For installation of the wired remote controller follow the Installation...

Страница 9: ...d slope 1 100 or more Arched shape Trap Downward slope 1 100 or more Collective piping As long as possible Approx 10 cm Heat insulator Incorrect VP30 Drain pan accessory Cut the insulation insert the protrusion on the drain pan into the hole and then install it by pushing it in the directions indicated by the arrows Drain pan screw accessory Pipe material size and insulator The following materials...

Страница 10: ...e R410A tool used Conventional tool used 6 4 9 5 0 to 0 5 1 0 to 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 Work using double spanner Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pip...

Страница 11: ...ocally For the power supply specifications follow to the following table If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supp...

Страница 12: ...s provided for the remote controller Do not connect the high voltage circuit Remove the mounting screws from electrical control box cover Dettach the cover from the electrical control box Connect the wires to the terminal block and tighten the screws Fix the wires with the cord clamp attached to the electrical control box Do not apply tension to the connecting section of the terminal block Mount t...

Страница 13: ... after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the...

Страница 14: ...test run has been performed using this method do NOT forget to release the shorting of CN72 after the test run is completed Operate the unit with the wired remote controller as usual For the procedure of the operation refer to the attached to the outdoor unit Owner s Manual A forced test run can be executed in the following procedure even if the operation stops by thermostat OFF In order to preven...

Страница 15: ...indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure 4 1 3 Front panel Lower Air filter knob Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Exa...

Страница 16: ...p to 4 errors The log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing o...

Страница 17: ...Remote controller E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit ...

Страница 18: ...DU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sen...

Страница 19: ...e 02 Comp 2 side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor un...

Страница 20: ...F Comp 1 Comp 2 Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK ...

Страница 21: ...lder Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MML AP0074BH E MML AP0094BH E MML AP0124BH E MML AP0154BH E MML AP0184BH E MML AP0244BH E Commercial name Super Modular Multi System Air Conditioner S...

Страница 22: ...s used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE ...

Страница 23: ...ime CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 00...

Страница 24: ...EH99880799 00EH99880701_01EN book Page 33 Thursday April 7 2011 4 47 PM ...

Отзывы: