Check code
[E08] / [96]
(Current code / AI-NET)
Check code name
Duplicated indoor addresses
Cause of operation
1. Indoor addresses are duplicated.
2. Switch setup error of wall type P.C. board
Sub-code:
Duplicated indoor address
Using a main remote controller (RBC-AMT32E), check the setup item codes (DN code) 12, 13, and 14.
When there is no address duplication, check to the following flowchart.
YES
YES
YES
NO
NO
NO
Is cable connection to
communication line normal?
Is not communication line connected
to the different outdoor unit?
Is indoor unit quantity connected
to outdoor unit correct?
Set up indoor address again.
Correct communication line.
Correct cable connection.
NO
Correct switch setup.
YES
Is setup of the model SELECT SW
(SW02) on wall type P.C. board of normal?
Bit 1: ON
Bit 2: OFF
Check code
[E09] / [99]
(Current code / AI-NET)
Check code name
Duplicated master
remote controller
Cause of operation
Setup of master remote controller is duplicated.
YES
NO
Are two remote controllers set up
as two master remote controllers?
Correct setup of remote controllers as a master:
a other. (Remote controller address connector)
Check remote controller P.C. board.
Failure
→
Replace
FILE NO. SVM-
16046