Check method
On the remote controller (Wired remote controller, Central control remote controller) and the interface P.C.
board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the
outdoor interface P.C. board) to display the operation is provided. Therefore the operation status can be
known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found
as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be
checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of check from indoor unit with wireless remote controller: See “Sensor block display of receiving
unit” in the list.
AI-NET: Artificial Intelligence.
IPDU: Intelligent Power Drive Unit
: Lighting, : Flashing, : Goes off
ALT.: Flashing is alternately when there are two flashing LED.
SIM: Simultaneous flashing when there are two flashing LED.
Check code
Wireless remote controller
Check code name
Judging
device
Wired
remote
controller
display
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
OPERATION TIMER PRE.DEF. Flash
E01
—
—
Communication error between indoor
and remote controller
(Detected at remote controller side)
Remote
controller
E02
—
—
Remote controller transmission error
Remote
controller
E03
—
—
Communication error between indoor
and remote controller (Detected at
indoor side)
Indoor
E04
—
—
Communication circuit error between
indoor/outdoor (Detected at indoor side)
Indoor
E06
E06
No. of indoor units in which
sensor has been normally
received
Decrease of No. of indoor units
I/F
—
E07
—
Communication circuit error between
indoor/outdoor (Detected at outdoor
side)
I/F
E08
E08 Duplicated indoor addresses
Duplicated indoor addresses
Indoor / I/F
E09
—
—
Duplicated main remote controllers
Remote
controller
E10
—
—
Communication error between indoor
MCU
Indoor
E12
E12
01: Indoor/Outdoor
communication
02: Communication between
outdoor units
Automatic address start error
I/F
E15
E15
—
Indoor is nothing during automatic
addressing
I/F
E16
E16 00: Capacity over
01 ~:No. of connected units
Capacity over / No. of connected indoor
units
I/F
E18
—
—
Communication error between indoor
units
Indoor
E19
E19 00: Header is nothing
02: Two or more header units
Outdoor header units quantity error
I/F
E20
E20
01: Outdoor of other line
connected
02: Indoor of other line
connected
Other line connected during automatic
address
I/F
+1111050501_01EN_SMMS_HighWall_IM_B5.book Page 27 Wednesday, November 12, 2008 2:45 PM
SMMS High-Wall Type
Installation Manual
Toshiba
E23
E23
—
Sending error in communication
between outdoor units
I/F
E25
E25
—
Duplicated follower outdoor addresses
I/F
E26
E26 No. of outdoor units which
received signal normally
Decrease of No. of connected outdoor
units
I/F
E28
E28 Detected outdoor unit number
Follower outdoor unit error
I/F
E31
E31
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
IPDU communication error
I/F
F01
—
—
ALT Indoor TCJ sensor error
Indoor
F02
—
—
ALT Indoor TC2 sensor error
Indoor
F03
—
—
ALT Indoor TC1 sensor error
Indoor
F04
F04
—
ALT TD1 sensor error
I/F
F05
F05
—
ALT TD2 sensor error
I/F
F06
F06
—
ALT TE1 sensor error
I/F
F07
F07
—
ALT TL sensor error
I/F
F08
F08
—
ALT TO sensor error
I/F
F10
—
—
ALT Indoor TA sensor error
Indoor
F12
F12
—
ALT TS1 sensor error
I/F
F13
F13 01: Comp. 1 side
02: Comp. 2 side
ALT TH sensor error
IPDU
F15
F15
—
ALT Outdoor temp. sensor miscabling (TE,
TL)
I/F
F16
F16
—
ALT Outdoor pressure sensor miscabling
(Pd, Ps)
I/F
F23
F23
—
ALT Ps sensor error
I/F
F24
F24
—
ALT Pd sensor error
I/F
F29
—
—
SIM Indoor other error
Indoor
F31
F31
—
SIM Indoor EEPROM error
I/F
H01
H01 01: Comp. 1 side
02: Comp. 2 side
Compressor break down
IPDU
H02
H02 01: Comp. 1 side
02: Comp. 2 side
Magnet switch error
Overcurrent relay operation
Compressor trouble (lock)
MG-SW
Overcurrent
relay
IPDU
H03
H03 01: Comp. 1 side
02: Comp. 2 side
Current detect circuit system error
IPDU
H04
H04
—
Comp 1 case thermo operation
I/F
H06
H06
—
Low pressure protective operation
I/F
H07
H07
—
Oil level down detective protection
I/F
H08
H08
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
Oil level detective temp sensor error
I/F
H14
H14
—
Comp 2 case thermo operation
I/F
H16
H16
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
Oil level detective circuit error
Magnet switch error
Overcurrent relay operation
I/F
MG-SW
Overcurrent
relay
L03
—
—
SIM Indoor centre unit duplicated
Indoor
L04
L04
—
SIM Outdoor line address duplicated
I/F
L05
—
—
SIM Duplicated indoor units with priority
(Displayed in indoor unit with priority)
I/F
L06
L06 No. of indoor units with priority
SIM
Duplicated indoor units with priority
(Displayed in unit other than indoor unit
with priority)
I/F
L07
—
—
SIM Group line in individual indoor unit
Indoor
L08
L08
—
SIM Indoor group/Address unset
Indoor, I/F
+1111050501_01EN_SMMS_HighWall_IM_B5.book Page 28 Wednesday, November 12, 2008 2:45 PM