Test run

• Before operating the air conditioner after having completed the work, check that the electrical control box cover of the 

indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may 
receive an electric shock if the power is turned on without first conducting these checks.

• If there is any kind of trouble (such as an error display has appeared, smell of burning, abnormal sounds, the air 

conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner 
yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure 
that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified 
service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to 
escalate or result in electric shocks or other trouble.

• After the work has finished, use an insulation tester set (500 V Megger) to check the resistance is 1 M

Ω

 or more 

between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster 
such as a leak or electric shock is caused at user’s side.

• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water 

drainage. Then conduct a test run to check that the air conditioner is operating properly.

Explanations given to user

• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know 

where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air 
conditioner.

• If the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and 

contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until 
the repairs are completed.

Relocation

• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous 

for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, 
noise and / or vibration may result.

• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. 

Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or 
other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly 
resulting in rupture, injury or other trouble.

CAUTION

New Refrigerant Air Conditioner Installation

This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.

• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is 

approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also 
been changed. Therefore, do not let water, dust, former refrigerant, or refrigerating oil enter the refrigerating cycle 
during installation work.

• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of 

the main unit and installation tools are changed from those for the conventional refrigerant.

• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not 

enter.

To Disconnect the Appliance from Main Power Supply.

• This appliance must be connected to the main power supply by means of a switch with a contact separation of at 

least 3 mm.

The installation fuse (all types can be used) must be used for the power supply line of this conditioner.

(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”

7-EN

8-EN

Содержание MMF-AP0156H-E (TR)

Страница 1: ...h For commercial use MMF AP0366H E MMF AP0486H E MMF AP0566H E Indoor Unit Model name Floor Standing Type MMF AP0156H E MMF AP0186H E MMF AP0246H E MMF AP0276H E AIR CONDITIONER MULTI TYPE Installation Manual ...

Страница 2: ...ation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individu...

Страница 3: ...s for use in industry Transportation of heavy objects Shoes with additional protective toe cap Repair of outdoor unit Gloves to provide protection for electricians Model name X mm Y mm Z mm Total weight kg MMF AP0156H E 90 290 830 46 MMF AP0186H E MMF AP0246H E 47 MMF AP0276H E MMF AP0366H E 180 295 860 62 MMF AP0486H E MMF AP0566H E G Z Y X Warning indications on the air conditioner unit Warning ...

Страница 4: ...You may injure yourself if the bands should break Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the ...

Страница 5: ...service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or vibration may r...

Страница 6: ...ay cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations wher...

Страница 7: ...vention of accident of falling because this unit is formed into a thin type If it is not fixed a falling accident may occur After carry in the indoor unit to the specified place fix it to the wall and the floor immediately for safety Installation of indoor unit Fixing to the wall surface Use the attached wall fixing bracket by inverting it at upper side of the unit Fix the indoor unit to the wall ...

Страница 8: ...AP036H to AP056H type 258 52 to 102 Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Vertical louver Turn the vertical louver while lifting up lightly and then insert it into the clearance of extrusion of the coupling rod Extrusion Coupling rod 8 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work...

Страница 9: ...apart If the clearance is less than 5 mm it will be hard to remove the drip proof cover and the electrical control box can not be taken out Drain hose Drain pan Heat insulator Hart polyvinyl chloride pipe Adhesion for hart polyvinyl chloride pipe used To connect drain hose on right route it through the knock out for refrigerant piping on AP015 to AP027 model Power supply wire take in port both sid...

Страница 10: ... 19 7 Use two wrenches to connect the indoor unit pipe Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connection...

Страница 11: ...ual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 I...

Страница 12: ...ow to remove the electrical control box cover AP015 to AP027 models Take off screws 1 and 2 at this side of the electrical control box and remove the drip proof cover Take off screws 3 and 4 at front side of the electrical control box and remove the electrical control box cover AP036 to AP056 models Take off screws 3 and 4 at front side of the electrical control box and remove the cover of the ele...

Страница 13: ...ayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be co...

Страница 14: ...l supplied with the outdoor unit Execute a test run When a fan operation is to be performed for an individual indoor unit turn off the power short CN72 on the circuit board and then turn the power back on First set the operating mode to fan and then operate When the test run has been performed using this method do NOT forget to release the shorting of CN72 after the test run is completed Operate t...

Страница 15: ... once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer...

Страница 16: ... be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to set temp...

Страница 17: ... side Indoor unit E04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor u...

Страница 18: ...p 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04 H04 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 Low pressure protective operation I F H07 H07 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor error 03 TK3 sensor error 04 TK4 sensor error 05 TK5 senso...

Страница 19: ...ide 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address ALT Indoor ...

Страница 20: ... code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch alarm of general purpose equipment control interface General purpose equipment I F P30 Alar...

Страница 21: ...sentative TCF holder Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF AP0156H E MMF AP0186H E MMF AP0246H E MMF AP0276H E MMF AP0366H E MMF AP0486H E MMF AP0566H E Commercial name Super Modular Multi ...

Страница 22: ...tioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for minim...

Страница 23: ...filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 ...

Страница 24: ...EB99802699 ...

Отзывы: