Toshiba MMF-AP0156H-E (TR) Скачать руководство пользователя страница 17

– 16 –

Check method

On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation 
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the following table.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.
• In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.

: Lighting,  : Flashing,  : Goes off

IPDU: Intelligent Power Drive Unit

ALT: Flashing is alternately when there are two flashing LED.

SIM: Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote controller

Check code name

Judging device

Wired remote controller 

display

Outdoor unit 7-segment display

Sensor block display of receiving unit

Auxiliary code

Operation

Timer

Ready

Flash

E01

Communication error between indoor unit and remote controller (Detected at remote 

controller side)

Remote controller

E02

Remote controller transmission error

Remote controller

E03

Communication error between indoor unit and remote controller (Detected at indoor 

unit side)

Indoor unit

E04

Communication circuit error between indoor / outdoor unit (Detected at indoor unit 

side)

Indoor unit

E06

E06

No. of indoor units in which sensor has been 

normally received

Decrease of No. of indoor units

I/F

E07

Communication circuit error between indoor / outdoor unit (Detected at outdoor unit 

side)

I/F

E08

E08

Duplicated indoor unit addresses

Duplicated indoor unit addresses

Indoor unit • I/F

E09

Duplicated master remote controllers

Remote controller

E10

Communication error between indoor unit MC

Indoor unit

E12

E12

01:Indoor / Outdoor units communication
02:Outdoor / Outdoor units communication

Automatic address start error

I/F

E15

E15

No indoor unit during automatic addressing

I/F

E16

E16

00:Capacity over
01 ~:No. of connected units

Capacity over / No. of connected indoor units

I/F

E18

Communication error between header and follower units Indoor unit

Indoor unit

E19

E19

00:No header
02:Two or more header units

Outdoor header units quantity error

I/F

E20

E20

01:Outdoor unit of other line connected
02:Indoor unit of other line connected

Other line connected during automatic address

I/F

E21

E21

02:No header unit
00:Multiple number of header units

Error in number of heat storage master units

I/F

E22

E22

Reduction in number of heat storage units

I/F

E23

E23

Sending error in communication between outdoor units
Error in number of heat storage units (trouble with reception)

I/F

E25

E25

Duplicated follower outdoor addresses

I/F

E26

E26

No. of outdoor units which received signal 

normally

Decrease of No. of connected outdoor units

I/F

E28

E28

Detected outdoor unit number

Follower outdoor unit error

I/F

E31

E31

Number of IPDU (*1)

IPDU communication error

I/F

F01

ALT

Indoor unit TCJ sensor error

Indoor unit

31-EN

32-EN

Содержание MMF-AP0156H-E (TR)

Страница 1: ...h For commercial use MMF AP0366H E MMF AP0486H E MMF AP0566H E Indoor Unit Model name Floor Standing Type MMF AP0156H E MMF AP0186H E MMF AP0246H E MMF AP0276H E AIR CONDITIONER MULTI TYPE Installation Manual ...

Страница 2: ...ation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individu...

Страница 3: ...s for use in industry Transportation of heavy objects Shoes with additional protective toe cap Repair of outdoor unit Gloves to provide protection for electricians Model name X mm Y mm Z mm Total weight kg MMF AP0156H E 90 290 830 46 MMF AP0186H E MMF AP0246H E 47 MMF AP0276H E MMF AP0366H E 180 295 860 62 MMF AP0486H E MMF AP0566H E G Z Y X Warning indications on the air conditioner unit Warning ...

Страница 4: ...You may injure yourself if the bands should break Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the ...

Страница 5: ...service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or vibration may r...

Страница 6: ...ay cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations wher...

Страница 7: ...vention of accident of falling because this unit is formed into a thin type If it is not fixed a falling accident may occur After carry in the indoor unit to the specified place fix it to the wall and the floor immediately for safety Installation of indoor unit Fixing to the wall surface Use the attached wall fixing bracket by inverting it at upper side of the unit Fix the indoor unit to the wall ...

Страница 8: ...AP036H to AP056H type 258 52 to 102 Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Vertical louver Turn the vertical louver while lifting up lightly and then insert it into the clearance of extrusion of the coupling rod Extrusion Coupling rod 8 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work...

Страница 9: ...apart If the clearance is less than 5 mm it will be hard to remove the drip proof cover and the electrical control box can not be taken out Drain hose Drain pan Heat insulator Hart polyvinyl chloride pipe Adhesion for hart polyvinyl chloride pipe used To connect drain hose on right route it through the knock out for refrigerant piping on AP015 to AP027 model Power supply wire take in port both sid...

Страница 10: ... 19 7 Use two wrenches to connect the indoor unit pipe Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connection...

Страница 11: ...ual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 I...

Страница 12: ...ow to remove the electrical control box cover AP015 to AP027 models Take off screws 1 and 2 at this side of the electrical control box and remove the drip proof cover Take off screws 3 and 4 at front side of the electrical control box and remove the electrical control box cover AP036 to AP056 models Take off screws 3 and 4 at front side of the electrical control box and remove the cover of the ele...

Страница 13: ...ayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be co...

Страница 14: ...l supplied with the outdoor unit Execute a test run When a fan operation is to be performed for an individual indoor unit turn off the power short CN72 on the circuit board and then turn the power back on First set the operating mode to fan and then operate When the test run has been performed using this method do NOT forget to release the shorting of CN72 after the test run is completed Operate t...

Страница 15: ... once every 3 months Ask a professional for this cleaning maintenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer...

Страница 16: ... be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used to set temp...

Страница 17: ... side Indoor unit E04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor u...

Страница 18: ...p 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system error IPDU H04 H04 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 Low pressure protective operation I F H07 H07 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor error 03 TK3 sensor error 04 TK4 sensor error 05 TK5 senso...

Страница 19: ...ide 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address ALT Indoor ...

Страница 20: ... code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch alarm of general purpose equipment control interface General purpose equipment I F P30 Alar...

Страница 21: ...sentative TCF holder Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF AP0156H E MMF AP0186H E MMF AP0246H E MMF AP0276H E MMF AP0366H E MMF AP0486H E MMF AP0566H E Commercial name Super Modular Multi ...

Страница 22: ...tioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for minim...

Страница 23: ...filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 ...

Страница 24: ...EB99802699 ...

Отзывы: