– 25 –
10
Test run
Before test run
• Before turning on the circuit breaker, carry out the
following procedure.
1) By using insulation tester (500V Megger), check
that resistance of 1 M
Ω
or more exists between the
terminal block L to N and the earth (grounding).
If resistance of less than 1 M
Ω
is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more for operating.
• Before starting a test run, be sure to set addresses
following the Installation Manual supplied with the
outdoor unit.
Execute a test run
• When a fan operation is to be performed for an
individual indoor unit, turn off the power, short circuit
CN72 on the circuit board, and then turn the power
back on. (Set the operation mode to "fan" to operate
the unit.) When the test run has been performed using
this method, be sure to release the short circuit of
CN72 after the test run is completed.
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the Owner’s
Manual attached to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test run
is released after 60 minutes have passed and returns to
the usual operation.
CAUTION
CAUTION
• Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
Wired remote controller
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not working.)
1
Push and hold OFF timer button and [
]
setting button simultaneously for 10 seconds
or more. [TEST] is displayed on the display
part and the test run is permitted.
2
Push ON/OFF button.
3
Push menu button to select the operation
mode. Select [
Cool] or [
Heat] with [
]
[
] setting button.
• Do not run the air conditioner in a mode other
than [Cool] or [Heat].
• The temperature setting function does not work
during test run.
• The check code is displayed as usual.
4
After the test run, push OFF timer button to
stop a test run.
([TEST] disappears on the display and the air
conditioner enters the normal stop mode.)
4
3
1
2
3
Wired remote controller
1
Turn on the power of the air conditioner.
When power is turned on for the first time
after installation, it takes approx. 5 minutes
until the remote controller becomes available.
In the case of subsequent poweron, it takes
approx. 1 minute until the remote controller
becomes available. Execute a test run after
the predetermined time has passed.
2
Push “ON/OFF” button on the remote
controller, select [
Cool] or [
Heat] with
“MODE” button, and then select
[
HIGH] with “FAN” button.
3
4
5
6
Repeat procedures
4
→
5
→
4
→
5
.
Indicators “Operation” (green), “Timer”
(green), and “Ready” (orange) in the wireless
receiver section flash in approx. 10 seconds,
and the air conditioner starts operation. If any
of these indicators does not flash, repeat
procedures 2 to 5.
7
Upon completion of the test run, push “ON/
OFF” button to stop operation.
<Overview of test run operations using the wireless
remote controller>
▼
Cooling test run:
ON/OFF
→
17°C
→
18°C
→
17°C
→
18°C
→
17°C
→
18°C
→
17°C
→
(test run)
→
ON/OFF
▼
Heating test run:
ON/OFF
→
30°C
→
29°C
→
30°C
→
29°C
→
30°C
→
29°C
→
30°C
→
(test run)
→
ON/OFF
Cooling test run
Heating test run
Set the temperature to 17°C
with the temp. setup buttons.
Set the temperature to 30°C
with the temp. setup buttons.
Cooling test run
Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 18°C with the
temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 29°C with the
temp. setup buttons.
Cooling test run
Heating test run
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 17°C with the
temp. setup buttons.
After confirming a signal
receiving sound “beep”
immediately set the
temperature to 30°C with the
temp. setup buttons.
49-EN
50-EN