– 12 –

7

Refrigerant piping

CAUTION

When the refrigerant pipe is long, provide support 
brackets at intervals of 2.5 m to 3 m to clamp the 
refrigerant pipe. Otherwise, abnormal sound may be 
generated.
Use the flare nut attached with the indoor unit or R410A 
flare nut.

„

Permissible piping length and 
height difference

They vary depending on the outdoor unit. For details, 
refer to the Installation Manual attached to the outdoor 
unit.

„

Pipe size

„

Connecting refrigerant piping

Flaring

1. Cut the pipe with a pipe cutter. 

Remove burrs completely. (Remaining burrs may 
cause gas leakage.)

2. Insert a flare nut into the pipe, and flare the pipe.

Use the flare nut provided with the unit or the one 
used for the R410A refrigerant. The flaring 
dimensions for R410A are different from the ones 
used for the conventional R22 refrigerant. A new 
flare tool manufactured for use with the R410A 
refrigerant is recommended, but the conventional 
tool can still be used if the projection margin of the 
copper pipe is adjusted to be as shown in the 
following table.

Projection margin in flaring: B (Unit: mm)

Flaring diameter size: A (Unit: mm)

* In case of flaring for R410A with the conventional 

flare tool, pull it out approx. 0.5 mm more than that 

for R22 to adjust to the specified flare size. The 

copper pipe gauge is useful for adjusting projection 

margin size.

Model MMD-

Pipe size (mm)

Gas side

Liquid side

Outer dia. of 

copper pipe

R410A tool used

Conventional 

tool used

6.4, 9.5

0 to 0.5

1.0 to 1.5

12.7, 15.9

Outer dia. of copper pipe

A +0

–0.4

1

.

9

4

.

6

2

.

3

1

5

.

9

6

.

6

1

7

.

2

1

7

.

9

1

9

.

5

1

‡

The sealed gas was sealed at the atmospheric 
pressure so when the flare nut is removed, there will 
no “whooshing” sound: This is normal and is not 
indicative of trouble.

‡

Use two wrenches to connect the indoor unit pipe.

‡

Use the tightening torque levels as listed in the 
following table.

‡

Tightening torque of flare pipe connections.
Pressure of R410A is higher than that of R22. 
(Approx. 1.6 times) Therefore, using a torque 
wrench, tighten the flare pipe connecting sections 
which connect the indoor and outdoor units of the 
specified tightening torque.
Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.

CAUTION

Tightening with an excessive torque may crack the nut 
depending on installation conditions.

„

Evacuation

Perform vacuuming from the charge port of valve of the 
outdoor unit by using a vacuum pump.
For details, follow to the Installation Manual attached to 
the outdoor unit.

‡

Do not use the refrigerant sealed in the outdoor unit 
for evacuation.

REQUIREMENT

For the tools such as charge hose, use those 
manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” 
referring to the attached Installation Manual of outdoor 
unit.
Use a scale to charge the refrigerant of specified 
amount.

REQUIREMENT

‡

Charging an excessive or too little amount of 
refrigerant causes a trouble of the compressor.
Charge the refrigerant of specified amount.

‡

A personnel who charged the refrigerant should write 
down the pipe length and the added refrigerant 
amount in the F-GAS label of the outdoor unit. It is 
necessary to fix the compressor and refrigeration 
cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4 mm-
hexagonal wrench is required for opening the valve.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas 
leaks or not, from the pipe connecting section or cap of 
the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC 
refrigerant (R410A, R134a).

Outer dia. of connecting 

pipe (mm)

Tightening torque (N

‡

m)

8

1

 

o

t

 

4

1

4

.

6

2

4

 

o

t

 

4

3

5

.

9

1

6

 

o

t

 

9

4

7

.

2

1

7

7

 

o

t

 

3

6

9

.

5

1

Work using double spanner

23-EN

24-EN

 AP018 

Ø12.7 

Ø6.4

AP024 to AP056

Ø15.9

Ø9.5

1117065599 (01)_EN.indd   13

1117065599 (01)_EN.indd   13

01/07/15   3:42 PM

01/07/15   3:42 PM

Содержание MMD-AP0186HP-E

Страница 1: ...For commercial use Indoor Unit Model name Concealed Duct High Static Pressure Type MMD AP0186HP E MMD AP0246HP E MMD AP0276HP E MMD AP0366HP E MMD AP0486HP E MMD AP0566HP E 1117065599 01 _EN indd 1 1117065599 01 _EN indd 1 01 07 15 3 42 PM 01 07 15 3 42 PM ...

Страница 2: ...cations pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and ...

Страница 3: ...or electricians Warning indications on the air conditioner unit n o i t p i r c s e D n o i t a c i d n i g n i n r a W WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do n...

Страница 4: ...her objects into the indoor unit while the air conditioner is running Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Suction duct length must be longer than 850 mm When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used In...

Страница 5: ...wn work shut down the compressor before disconnecting the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION New refrigerant air conditioner ...

Страница 6: ... works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetn...

Страница 7: ...he indoor unit as it is packaged if possible If carrying in the indoor unit unpacked by necessity use buffering cloth or other material to not damage the unit To move the indoor unit hold the hooking brackets 4 positions only Do not apply force to the other parts such as refrigerant pipe drain pan foamed parts or resin parts Carry the package by four or more persons and do not bundle it with plast...

Страница 8: ...p and down of the hanging bracket of the indoor unit to hang down the indoor unit Check that four sides are horizontal with a level gauge Horizontal degree Within 5 mm REQUIREMENT Hang the unit in a horizontal position When unit is hanged to slant it may cause overflow of drainage Install the unit within the dimension according to the figure below Use level gauge to confirm whether the unit is han...

Страница 9: ...rain hose using the hose band without using adhesive Pipe material Hard vinyl chloride pipe VP25 Nominal outer diameter Ø32 mm Insulator Foamed polyethylene foam thickness 10 mm or more 1 5 m to 2 m Support bracket Downward slope 1 100 or more Arched shape Trap Downward slope 1 100 or more Collective piping As long as possible Approx 10 cm Heat insulator Incorrect VP30 Flexible drain hose Hose ban...

Страница 10: ...g from the drain pipe connecting port and check that no water is leaking from the drain pipe After checking that the water drains and there are no water leaks turn off the power connect the float switch connector to its original location CN34 on the printed circuit board and return the electrical control box to its original position Supply water hose Pull out connector CN34 Red from P C board Whit...

Страница 11: ... pressure loss option 0 25 50 75 100 125 150 175 200 225 250 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 Static Pressure Pa 200Pa 150Pa 100Pa 50Pa Spigot Flange pressure loss option Filter set pressure loss option Fan characteristics Air Flow m3 h Standard Air Flow 800m3 h AP0186 type AP0246 0276 type AP0366 type Standard Air Flow 1 200m3 h Air Flow m3 h Air Flow m3 h Standard Air Flow ...

Страница 12: ...Canvas joint Air conditioner Air supply port Silencer chamber Air filter Air inlet Check port Silencer chamber 180 Outside 1340 Outside 87 13 22 22 87 180 Outside 940 Outside 20 100 100 100 100 100 100 100 100 100 13 Arrangement Referring to the following dimensions manufacture duct at the local site Air inlet Air inlet 975 7 100 100 100 100 100 100 100 100 100 418 180 276 256 50 100 100 100 100 1...

Страница 13: ...ipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle CAUTION Tightening with an excessive torque may crack the nut depending...

Страница 14: ...e product Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires when peeling them Use the power cord and system interconnection wire of specified thickness type and protective devices required Do not connect 220 V 240 V power to the terminal blocks for control wiring Otherwise the system will fail REQUIREMENT For power supply wiring strictly con...

Страница 15: ...controller inter unit wiring Wire size 0 5 mm to 2 0 mm Total wire length of remote controller wiring and remote controller inter unit wiring L L1 L2 Ln In case of wired type only Up to 500 m In case of wireless type included Up to 400 m m 0 0 2 o t p U n L 2 L 1 L g n i r i w t i n u r e t n i r e l l o r t n o c e t o m e r f o h t g n e l e r i w l a t o T L1 L n L 2 L Indoor unit Remote contro...

Страница 16: ... used for the first time it will take some moments after the power has been turned on before the remote controller becomes available for operations This is normal and is not indicative of trouble Concerning the automatic addresses The automatic addresses are set up by performing operations on the outdoor interface circuit board While the automatic addresses are being set up no remote controller op...

Страница 17: ...connected To set up a tap change follow to the basic operation procedure 1 2 3 4 5 6 Specify 5d to the CODE No in procedure 3 For the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table The list above is when SW501 1 and SW501 2 is OFF If the setting is wrong P12 may appear indicating a fan motor error SET DATA External static pressure 00...

Страница 18: ...1 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C SET DATA 0000 0001 Remotecontroller sensor Not used Factory default Used 10Test run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L to N and the earth grounding If resistance of less than 1 MΩ is de...

Страница 19: ...r cover the air discharge In addition stop the operation before replacing the opening the service panel After the test run reset the circuit breaker of the indoor unit TEMPORARY button 11Maintenance 1 Take out the air filter sold separately 2 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter by tepid water with neutral detergent or water After cleaning with water dry the ...

Страница 20: ...t r i d t s u D r o o d n I r sold separately e t l i F Wash the filter with water when it is contaminated Replace it when it is damaged r o o d n I n a F Vibration balance Dust dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed...

Страница 21: ... r o o d n I s e s s e r d d a t i n u r o o d n i d e t a c i l p u D s e s s e r d d a t i n u r o o d n i d e t a c i l p u D 8 0 E 8 0 E r e l l o r t n o c e t o m e R s r e l l o r t n o c e t o m e r r e t s a m d e t a c i l p u D 9 0 E t i n u r o o d n I C M t i n u r o o d n i n e e w t e b r o r r e n o i t a c i n u m m o C 0 1 E E12 E12 01 Indoor Outdoor units communication 02 Outdoo...

Страница 22: ...H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side U D P I r o r r e m e t s y s t i u c r i c t c e t e d t n e r r u C F I n o i t a r e p o o m r e h t e s a c 1 p m o C 4 0 H 4 0 H F I g n i r i w s i m r o s n e s 1 D T 5 0 H 5 0 H F I n o i t a r e p o e v i t c e t o r p e r u s s e r p w o L 6 0 H 6 0 H F I n o i t c e t o r p e v i t c e t e d n w o d l e v e l l i O 7 0 H 7 0 H H08 H08 01 ...

Страница 23: ...00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side T L A Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side F I U D P I r o r r e t a e h r e v o k n i s t a e H T L A a e h o N T L A s s e r d d a e g a r o t s t a e h d e t c e t e D 9 0 P 9 0 P t i n u ...

Страница 24: ...vice indication Outdoor unit 7 segment display Sensor block display of receiving unit h s a l F y d a e R r e m i T n o i t a r e p O e d o c y r a i l i x u A K N I L C C T e c i v e d l o r t n o c l a r t n e c K N I L C C T n i r o r r e g n i d n e S 5 0 C K N I L C C T e c i v e d l o r t n o c l a r t n e c K N I L C C T n i r o r r e g n i v i e c e R 6 0 C e c a f r e t n i l o r t n o c ...

Страница 25: ...dular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law Declaration of incorporation of partly completed machinery Must not be put into service until the final machinery into which...

Страница 26: ...or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No partitio...

Страница 27: ... F STATIC 5 0005 F STATIC 6 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F STATIC 1 0001 F STATIC 2 0002 F STATIC 3 0003 F STATIC 4 0004 F STATIC 5 0005 F STATIC 6 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign ...

Страница 28: ...THAILAND CO LTD 144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND 1117065599 1117065599 01 _EN indd 28 1117065599 01 _EN indd 28 01 07 15 3 42 PM 01 07 15 3 42 PM ...

Отзывы: