background image

17-EN 

18-EN 

– 9 –  

87

170

320

176

205

98

158

244

218

690

102

132

192

235

F

E

G

125

87

33

191

40

145

48

66

109

33 85

A

250 or more

250 or more

Approx. 8 m 

Left drain pipe connecting port 

Refrigerant pipe (Gas side ØD)

B (Hanging position) 

Refrigerant pipe (Liquid side ØC) 

Power supply wire take-in port 

(knockout hole Ø40)

Signal receiving unit mounting section

500 or more 

 

Installation space

Reserve suf

fi

 cient space required for installation or service work. 

 

Ceiling height 

 

External dimensions

 

In case of wireless type

If height of ceiling exceeds 3.5 m, hot air becomes dif

fi

 cult to reach the 

fl

 oor surface, and then the change of setup 

of high ceiling is necessary. 
For the change method of high ceiling, refer to the application control, “Installing indoor unit on high ceiling” in this 
Manual.

Height list of ceiling possible to be installed 

The lighting time of the 

fi

 lter sign (noti

fi

 cation of 

fi

 lter cleaning) on the remote controller can be changed according 

to installation conditions. 
When it is dif

fi

 cult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room, 

the detection temperature of heating can be raised. 
For change the setup time, refer to the application control, “Filter sign setting” and “To secure better effect of 
heating” in this Manual.

Decide the position which remote controller is operated and the installation place. 
And then refer to the Installation Manual of the wireless remote controller kit sold separately. 
(The signal of the wireless type remote controller can be received within approx. 8 m. This distance is a criterion 
and varies a little according to capacity of the battery) 
• To prevent malfunction, select a place where is not affected by a 

fl

 uorescent lamp or direct sunlight. 

• Two wireless-type indoor units can be set in a room.

4

 Installation 

Model MMC- 

Possible installed ceiling height

AP015 to AP027 

Up to 4.0 m

AP036 to AP056

Up to 4.3 m

Model MMC-

AP015 to AP027

AP036 to AP056

SET DATA

Standard (Factory default)

Up to 3.5 m

Up to 3.5 m

0000

High ceiling (1)

Up to 4.0 m

Up to 4.3 m

0003

(Unit: mm)

Drain pipe connecting port 

Remote controller wire take-in port

Remote controller wire take-in 
port (Knockout hole) 

(Hanging position) 

Upper pipe draw-out port (knockout hole) 

Power supply wire take-in port 

(knockout hole Ø40)

Left drain pipe draw-out port 

(knockout hole)

Model MMC- 

A

B

C

D

E

F

G

AP015, AP018 

950

906 Ø6.4 Ø12.7 

351

270

353

AP024, AP027 

1270 1223 

Ø9.5 Ø15.9 

AP036 to AP056 

1586 1540 

376

303

378

(Unit: mm)

 CAUTION

Strictly comply with the following rules to prevent damage of the indoor units and human injury. 

•  Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged) 
•  Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering 

cloth or other material to not damage the unit. 

•  Carry the package by two or more persons, and do not bundle it with plastic band at positions other than speci

fi

 ed. 

•  To install vibration isolation material to hanging bolts, con

fi

 rm that it does not increase the unit vibration.

Содержание MMC-AP0158HP Series

Страница 1: ...PE Installation Manual For commercial use Indoor Unit Model name Ceiling Type MMC AP0158HP Series MMC AP0188HP Series MMC AP0248HP Series MMC AP0278HP Series MMC AP0368HP Series MMC AP0488HP Series MMC AP0568HP Series English ...

Страница 2: ...9 10 Maintenance 20 11 Troubleshooting 21 12 Specifications 26 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the indoor unit For installation of the outdoor unit follow the Installation Manual attached to the outdoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly re...

Страница 3: ...ted to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air cond...

Страница 4: ...bility for the damage caused by not observing the description of this manual WARNING General Before starting to install the air conditioner read through the Installation Manual carefully and follow its instructions to install the air conditioner Only a qualified installer 1 or qualified service person 1 is allowed to do installation work Inappropriate installation may result in water leakage elect...

Страница 5: ...cuit breaker to OFF without fail and place a Work in progress sign near the circuit breaker before proceeding with the work Before working at heights put a sign in place so that no one will approach the work location before proceeding with the work Parts and other objects may fall from above possibly injuring a person below While carrying out the work wear a helmet for protection from falling obje...

Страница 6: ...Use forklift to carry in the air conditioner units and use winch or hoist at installation of them Refrigerant piping Install the refrigerant pipe securely during the installation work before operating the air conditioner If the compressor is operated with the valve open and without refrigerant pipe the compressor sucks air and the refrigeration cycles is over pressurized which may cause a injury T...

Страница 7: ...in the community and installation manual Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on ...

Страница 8: ...tallation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner If the fan grille is damaged do not approach the outdoor unit but set the circuit breaker to the OFF position and contact a qualified service person 1 to have the repairs done...

Страница 9: ... cranes ships or other moving conveyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the ...

Страница 10: ...mote controller kit sold separately The signal of the wireless type remote controller can be received within approx 8 m This distance is a criterion and varies a little according to capacity of the battery To prevent malfunction select a place where is not affected by a fluorescent lamp or direct sunlight Two wireless type indoor units can be set in a room 4 Installation Model MMC Possible install...

Страница 11: ...hanging bolt Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the External dimensions Installation of remote controller Sold separately For installation of the remote controller follow the Installation Manual attached with the remote controller Pull out the remote controller cord together with the refrigerant pipe or drain pipe Pass the...

Страница 12: ... cutter In case of taking pipe from upper side Taking pipe from upper side is applied only to the refrigerant pipe When taking out the drain pipe from the upper side use a drain up kit sold separately Open the upper pipe draw out port Knockout hole shown in the external dimensions Make the diagonally shaded hole when you do not use the Elbow Piping Kit Make only this knockout hole when you use the...

Страница 13: ...not provide any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe A hard PVC pipe cannot be connected to the drain pipe connecting port of the indoor unit Be absolutely sure to use the flexible hose provided for the connections with the drain pipe connecting port Adhesive agents cannot be used for th...

Страница 14: ... leak In case of taking pipe from the left side In case of taking pipe from the left side exchange the plug from left to right Push in the plug of which end is not sharp up to the end Drain up When a down gradient cannot be secured for the drain pipe drain up piping is possible The height of the drain pipe must be 600 mm or less from the underside of the indoor unit When Drain Pump Kit sold separa...

Страница 15: ...e to charge the refrigerant of specified amount REQUIREMENT Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix the compressor and refrigeration cy...

Страница 16: ... of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cable 3 core 2 5 mm in conformity with Design 60245 IEC 57 CAUTION If incorrect incomplete wiring is carried out it will cause an e...

Страница 17: ...wer supply wiring fuse rating for indoor units should be selected by the accumulated total current values of the indoor units Power supply wiring Below 50 m 2 5 mm2 Control wiring Central controller wiring 2 core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring To prevent noise trouble use 2 core shield wire The length of the co...

Страница 18: ...Remote controller Indoor unit Indoor unit Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Earth leakage breaker Outdoor Power supply 380 415 V 50 Hz 380 V 60 Hz 1 Push and hold button and TEMP button simultaneously for at least 4 seconds After a while the display flashes as shown in the figure Confirm that the CODE No is 01 I...

Страница 19: ...wiring procedure and wiring method of the individual line Identical refrigerant line system refer to Electrical connection in this Manual Wiring between indoor units in a group is performed in the following procedure Connect the indoor units by connecting the remote controller inter unit wires from the remote controller terminal blocks A B of the indoor unit connected with a remote controller to t...

Страница 20: ... available for trial runs To perform a test run set the unit to heating mode with the remote controller The unit might not operate in heating mode however depending on temperature conditions 1 Hold down the TEMPORARY button for over 10 seconds With a beep sound the unit is set to the forced cooling mode In approximately three minutes it is forced to start in cooling mode Determine that cool air co...

Страница 21: ... the part Check if there is any clogging or drain water is polluted Maintenance List Part Unit Check visual auditory Maintenance Heat exchanger Indoor outdoor Dust dirt clogging scratches Wash the heat exchanger when it is clogged Fan motor Indoor outdoor Sound Take appropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contamin...

Страница 22: ...er rors The log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of butt...

Страница 23: ...4 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicat...

Страница 24: ...I F F23 F23 ALT Ps sensor error I F F24 F24 ALT Pd sensor error I F F29 SIM Indoor unit other error Indoor unit F31 F31 SIM Indoor unit EEPROM error I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Current detect circuit system er...

Страница 25: ... unit L31 Extended I C error I F P01 ALT Indoor fan motor error Indoor unit P03 P03 ALT Discharge temp TD1 error I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation IPDU P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC volta...

Страница 26: ...6 Comp 2 Comp 3 07 Comp 1 Comp 2 Comp 3 08 Fan 09 Comp 1 Fan 0A Comp 2 Fan 0B Comp 1 Comp 2 Fan 0C Comp 3 Fan 0D Comp 1 Comp 3 Fan 0E Comp 2 Comp 3 Fan 0F Comp 1 Comp 2 Comp 3 Fan Error detected by TCC LINK central control device Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display Sensor block display of receiving unit...

Страница 27: ...the machinery described below Generic Denomination Air Conditioner Model type MMC AP0158HP Series MMC AP0188HP Series MMC AP0248HP Series MMC AP0278HP Series MMC AP0368HP Series MMC AP0488HP Series MMC AP0568HP Series Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies ...

Страница 28: ...frigerant kg Min volume of the indoor unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device Important 2 When there is an effective opening with the adjacent ro...

Страница 29: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1114654499 1 ...

Отзывы: