Louver control:
Outline of specifications
1) Louver position setup
s
When the louver position is changed, the position moves
necessarily to downward discharge position once to return to
the set position.
s
The louver position can be set up in the following operation
range.
Remarks
In cooling/dry operation
In heating/fan operation
s
In group operation, the louver positions can be set up
collectively or individually.
In case of refrigerant recovery control, the louver position
becomes horizontal.
2) Swing setup
s
[SWING] is displayed and the following display is repeated.
In all operations
(Repeats)
s
In group operation, the louver positions can be set up
collectively or individually.
3) When the unit stopped or the warning was output, the louver is
automatically set to full closed position.
4) When PRE-HEAT
(Heating ready) is displayed
(Heating operation started or defrost operation is performed),
heating thermo is off, the louver is automatically set to horizontal
discharge position.