background image

SMMS Floor Standing Type

Installation Manual

EN

SMMS Floor Standing Type

Installation Manual

– 12 –

8

Applicable Controls

REQUIREMENT

When the air conditioner is used for the first time, it will 
take some moments after the power has been turned on 
before the remote controller becomes available for 
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic 

addresses are set up by performing operations on the 
outdoor interface circuit board.)

 

While the automatic addresses are being set up, no 
remote controller operations can be performed. Setup 
takes up to 10 minutes (usually about 5 minutes).

• When the power is turned on after automatic address 

setup

 

It takes up to 10 minutes (usually about 3 minutes) for 
the outdoor unit to start operating after the power has 
been turned on.

Before the air conditioner was shipped from the factory, 
all units are set to [STANDARD] (factory default). If 
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote 
controller.
* The settings cannot be changed by using only a 

wireless remote controller, simple remote controller or 

group control remote controller by itself so install a 

wired remote controller separately as well.

„

Basic procedure for changing 
settings

Change the settings while the air conditioner is not 
working. 

(Stop the air conditioner before making 

settings.)

CAUTION

Set only the CODE No. shown in the following table: Do 
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to 
operate the air conditioner or other trouble with the 
product may result.
* The displays appearing during the setting process 

differ from the ones for previous remote controllers 

(AMT21E, AMT31E). (There are more CODE No.)

1

Push and hold 

 button and “TEMP.” 

 

button simultaneously for at least 4 
seconds. After a while, the display flashes 
as shown in the figure. Confirm that the 
CODE No. is [01].

If the CODE No. is not [01], push 

 button to clear 

the display content, and repeat the procedure from 
the beginning. (No operation of the 

 remote 

controller is accepted for a while after button is 
pushed.)

 

(While air conditioners are operated under the 
group control, “ALL” is displayed first. When 

 is pushed, the indoor unit number 

displayed following “ALL” is the header unit.)

1

6

1

3

2

5

4

(* Display content varies with the indoor unit 

model.)

2

Each time 

 button is pushed, indoor 

unit numbers in the control group change 
cyclically. Select the indoor unit to change 
settings for.

 

The fan of the selected unit runs and the 
louvers start swinging. The indoor unit for 
change settings can be confirmed.

3

Specify CODE No. [

] with  “TEMP.” 

 / 

 buttons.

4

Select SET DATA [

] with “TIME” 

 / 

 buttons.

5

Push 

 button. When the display changes 

from flashing to lit, the setup is completed.

• To change settings of another indoor unit, 

repeat from Procedure 

2

.

• To change other settings of the selected indoor 

unit, repeat from Procedure 

3

.

Use 

 button to clear the settings. To make 

settings after 

 button was pushed, repeat from 

Procedure 

2

.

6

When settings have been completed, push 

 button to determine the settings.

When 

 button is pushed, 

 flashes and 

then the display content disappears and the air 
conditioner enters the normal stop mode.

 

 (While 

 is flashing, no operation of the 

remote controller is accepted.)

„

Filter sign setting

According to the installation condition, the filter sign 
term (Notification of filter cleaning) can be changed.

 

Follow to the basic operation procedure

 

(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [01].

• For the [SET DATA] in Procedure 

4

, select the SET 

DATA of filter sign term from the following table.

„

To secure better effect of 
heating

When it is difficult to obtain satisfactory heating due to 
installation place of the indoor unit or structure of the 
room, the detection temperature of heating can be 
raised. Also use a circulator or other machinery to 
circulate heat air near the ceiling.

 

Follow to the basic operation procedure

 

(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

).

• For the CODE No. in Procedure 

3

, specify [06].

• For the set data in Procedure 

4

, select the SET 

DATA of shift value of detection temperature to be 
set up from the following table.

SET DATA

Filter sign term

0000

None

0001

150 H

(Factory default)

0002

2500 H

0003

5000 H

0004

10000 H

SET DATA

Detection temperature shift value

0000

No shift

(Factory default)

0001

+1 °C

0002

+2 °C

0003

+3 °C

0004

+4 °C

0005

+5 °C

0006

+6 °C

23-EN

24-EN

+00EH99880501_01EN.book  Page 12  Thursday, April 7, 2011  10:15 AM

Содержание MMC-AP0154H-TR

Страница 1: ...4H E MMF AP0484H E MMF AP0564H E Indoor Unit Model name Floor Standing Type MMF AP0154H E MMF AP0184H E MMF AP0244H E MMF AP0274H E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99880501_01EN book Page 1 Thursday April 7 2011 10 15 AM ...

Страница 2: ...ved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters ...

Страница 3: ...cap Repair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might ge...

Страница 4: ...acking carton You may injure yourself if the bands should break Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in inju...

Страница 5: ...act a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or...

Страница 6: ... the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations where an in house power generator is used for the power supply The power line freq...

Страница 7: ...or immediately for safety Installation of indoor unit Fixing to the wall surface Use the attached wall fixing bracket by inverting it at upper side of the unit Fix the indoor unit to the wall surface using the attached screw bolts anchor bolts or etc at two positions A many holes for fixing the indoor unit to wall surface and for fixing the indoor unit itself are provided on the bracket Sliding th...

Страница 8: ... room Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Vertical louver Turn the vertical louver while lifting up lightly and then insert it into the clearance of extrusion of the coupling rod Extrusion Coupling rod 8 m or less 5 Drain Piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained...

Страница 9: ...5 mm or more on AP015 to AP027 model If the clearance is less than 5 mm drip proof cover cannot be removed and the electrical control box cannot be took out Drain hose Drain pan Heat insulator Hart polyvinyl chloride pipe Adhesion for hart polyvinyl chloride pipe used To connect drain hose on right route it through the knock out for refrigerant piping on AP015 to AP027 model Power supply wire take...

Страница 10: ...12 7 16 6 15 9 19 7 Use two wrenches to connect the indoor unit pipe Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorr...

Страница 11: ...the power supply specifications follow to the following table If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separate...

Страница 12: ...gh voltage circuit How to remove the electrical control box cover AP015 to AP027 models Take off screws 1 and 2 at this side of the electrical control box and remove the drip proof cover Take off screws 3 and 4 at front side of the electrical control box and remove the electrical control box cover AP036 to AP056 models Take off screws 3 and 4 at front side of the electrical control box and remove ...

Страница 13: ...on is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected u...

Страница 14: ...s been performed using this method do NOT forget to release the shorting of CN72 after the test run is completed Operate the unit with the wired remote controller as usual For the procedure of the operation refer to the attached Owner s Manual to the outdoor unit A forced test run can be executed in the following procedure even if the operation stops by thermostat OFF In order to prevent a serial ...

Страница 15: ...nd outdoor units regularly will result in poor performance freezing water leakage and even compressor failure 4 1 3 Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any cl...

Страница 16: ...rs The log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button us...

Страница 17: ...roller E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at...

Страница 18: ... 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor error ...

Страница 19: ... side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address ...

Страница 20: ...mp 2 Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch a...

Страница 21: ...r Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF AP0154H E MMF AP0184H E MMF AP0244H E MMF AP0274H E MMF AP0364H E MMF AP0484H E MMF AP0564H E Commercial name Super Modular Multi System Air Conditio...

Страница 22: ...ulti air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The stand...

Страница 23: ...nd fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F...

Страница 24: ...EH99880599 00EH99880501_01EN book Page 23 Thursday April 7 2011 10 15 AM ...

Отзывы: