background image

Engineering 

Data Book

E14-361 

Notice: Toshiba is committed to continuously improving its products to ensure the highest
quality and reliability standards, and to meet local regulations and market requirements. All
features and specifications are subject to change without prior notice.

Model name:

MCY-MHP0404HT-E
MCY-MHP0504HT-E
MCY-MHP0604HT-E

Outdoor units

Side blow VRF

Содержание MCY-MHP0404HT-E

Страница 1: ... its products to ensure the highest quality and reliability standards and to meet local regulations and market requirements All features and specifications are subject to change without prior notice Model name MCY MHP0404HT E MCY MHP0504HT E MCY MHP0604HT E Outdoor units Side blow VRF ...

Страница 2: ...frigerant piping 18 3 4 Allowable length height difference of refrigerant piping with PMV Kit 19 3 5 Selection of refrigerant piping with PMV Kit 20 3 6 Charging requirement with additional refrigerant 21 4 Wiring design 22 4 1 General 22 4 2 Electrical wiring design 22 4 3 Outdoor unit power supply 22 4 4 Indoor unit power supply 23 4 5 Design of control wiring 26 5 Outdoor unit 28 5 1 Specificat...

Страница 3: ...rvicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminium fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the service valves before the operation otherwise there might be the burst CAUTION Do not climb onto the fan guard Doing so may result in injury WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric...

Страница 4: ...frigerant gas leaks during installation work ventilate the room If the leaked refrigerant gas approaches to fire noxious gas may generate After installation work confirm that refrigerant gas does not leak If refrigerant gas leaks in the room and approaches to fire such as fan heater stove or kitchen range generation of noxious gas may be caused Never recover refrigerant in the outdoor unit Be sure...

Страница 5: ... R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F ...

Страница 6: ...air temperature 7 C DB 6 C WB Corresponding HP Inverter unit 4HP 5HP 6HP Model name MCY MHP0404HT E MCY MHP0504HT E MCY MHP0604HT E Cooling capacity kW 1 12 1 14 0 15 5 Heating capacity kW 1 12 5 16 0 18 0 No of connectable indoor units 6 6 6 MCY_ M H T J H P _E E Europe corresponding to European standard model J Anti corrosion heavy protection T Capacity variable unit H Heat pump Development seri...

Страница 7: ...type 0 80 2 2 2 5 MMU AP0092WH 009 type 1 00 2 8 3 2 MMU AP0122WH 012 type 1 25 3 6 4 0 MMU AP0152WH 015 type 1 70 4 5 5 0 MMU AP0182WH 018 type 2 00 5 6 6 3 MMU AP0242WH 024 type 2 50 7 1 8 0 MMU AP0272WH 027 type 3 00 8 0 9 0 MMU AP0302WH 030 type 3 20 9 0 10 0 MMU AP0362WH 036 type 4 00 11 2 12 5 MMU AP0482WH 048 type 5 00 14 0 16 0 MMU AP0562WH 056 type 6 00 16 0 18 0 1 way Air Discharge Casse...

Страница 8: ... type 2 50 7 1 8 0 Available High wall Type 4 series MMK AP0074MH E 007 type 0 80 2 2 2 5 Available MMK AP0094MH E 009 type 1 00 2 8 3 2 Available MMK AP0124MH E 012 type 1 25 3 6 4 0 Available Floor Standing Concealed Type MML AP0074BH E 007 type 0 80 2 2 2 5 MML AP0094BH E 009 type 1 00 2 8 3 2 MML AP0124BH E 012 type 1 25 3 6 4 0 MML AP0154BH E 015 type 1 70 4 5 5 0 MML AP0184BH E 018 type 2 00...

Страница 9: ...g joints and headers 1 2 4 PMV Kits Name Model name Appearance Remarks Y shapebranching joint RBM BY55E 4 branching header RBM HY1043E 8 branching header RBM HY1083E Name Model name Appearance Remarks PMV Kits RBM PMV0362E RBM PMV0902E ...

Страница 10: ...le timer 7 day timer function RBC AMS41E Lite Vision plus Remote Controller RBC AMS51E EN ES EN English Italian Polish Greece Russian Turkish ES English Spanish Portuguese French Dutch German Name Model Name Remarks Power peak cut control board TCB PCDM4E External master ON OFF control board TCB PCMO4E Output control board TCB PCIN4E Name Model Name Remarks Touch Screen Controller BMS TP0641ACE BM...

Страница 11: ...tiplying the value of step1 by corrected capacity A Calculate corrected capacity C of each indoor unit by multiplying the total corrected capacity of outdoor unit at by proportional division of each indoor unit standard capacity for total standard capacity of all indoor units Find correction values of below items for the standard capacity of outdoor unit selected at or Then determination of total ...

Страница 12: ...e is the same as 007 type 2 2 2 For outdoor unit maximum No of connectable indoor units and total capacity code of indoor units are decided Capacity rank type 005 1 007 008 009 010 012 014 015 017 018 020 024 027 030 036 048 056 Capacity code Equivalent to HP 0 8 0 8 0 9 1 0 1 1 1 25 1 5 1 7 1 85 2 0 2 25 2 5 3 0 3 2 4 0 5 0 6 0 Outdoor unit Capacity code of outdoor unit No of connectable indoor u...

Страница 13: ...tween indoor and outdoor units 4 Correction of outdoor unit diversity Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity 㪇㪅㪏㩷 㪇㪅㪐㩷 㪈㪅㪇㩷 㪈㪅㪈㩷 㪈㪅㪉㩷 㪈㪌 㪉㪇 Capacity correction value Indoor air wet bulb temp C 0 8 0 9 1 0 1 1 1 2 5 0 5 10 15 20 25 30 35 40 Capacity correction value Outdoor air dry bulb temp C Hei...

Страница 14: ...r units 4 Correction of outdoor unit diversity Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor units are not equal to the outdoor unit capacity 0 8 0 9 1 0 1 1 1 2 15 20 Capacity correction value Indoor air dry bulb temp C 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 20 15 10 5 0 5 10 15 Capacity correction value Outdoor air wet bulb temp C Height of outdoor unit H ...

Страница 15: ...as found on the outdoor heat exchanger Heating capacity Capacity after correction of outdoor unit x Correction value of capacity resulted from frost Capacity after correction of outdoor unit Heating capacity calculated in the above item 2 5 capacity correction in case of frost on the outdoor heat exchanger Capacity correction value Outdoor air wet bulb temp C ...

Страница 16: ...20 C however considerable performance decrease will be expected below 15 C Therefore please consider installation location surroundings and system design when expected to operate between 15 C and 20 C Outdoor air dry bulb temp C Indoor air wet bulb temp C Cooling Indoor air dry bulb temp C Outdoor air wet bulb temp C Heating ...

Страница 17: ...ly increase the flexibility of refrigerant piping design Line branching system Header branching system Header branching system Line branching system after header branching Header branching system after header branching Branching joint Indoor unit Remote controller Outdoor Branching header Remote controller Outdoor In case of PMV Kit Branching header Branching joint Remote controller PMV Kit Indoor...

Страница 18: ...m 1st branching Li 1 20 m L3 f Max real length of indoor unit connecting pipe 10 m a b c d e f Height Difference Height between indoor and outdoor units H1 Upper outdoor unit 15 m Lower outdoor unit 15 m Height between indoor units H2 10 m f a b c d A 1 L3 L1 L2 e Outdoor unit Height difference between indoor and outdoor units H1 Main pipe 1st branching section Branching pipe Branching header Indo...

Страница 19: ...hing section Y shaped branching joint 5 Branching section Branching header Selection of branching section Branching header 5 2 4 1 3 3 3 3 2 4 3 3 Outdoor unit Liquid pipe Gas pipe Main pipe 1st branching section Branching pipe Branching header Indoor unit Indoor unit Branching pipe Y shaped branching joint Outdoor unit capacity type Gas pipe Liquid pipe 0404 type 15 88 9 52 0504 type 15 88 9 52 0...

Страница 20: ...m g h i j k l Height Difference Height between indoor and outdoor units H1 Upper outdoor unit 15 m Lower outdoor unit 15 m Height between indoor unit and PMV Kit H2 10 m NOTE Do not connect two or more indoor units to one PMV Kit Arrange one indoor unit and one PMV Kit set to 1 by 1 K O D O O G O N PMV Kit PMV Kit t i n u r o o d n I t i n u r o o d n I e l f a b g h i j c d H2 H2 H2 A 1 L3 L1 L2 ...

Страница 21: ...f branching section Branching header 6 PMV Kit PMV Kit Selection of PMV Kit PMV kit can be connected less than 027 type FCU 5 2 4 1 3 6 3 3 2 4 3 6 6 6 3 6 3 6 Outdoor unit Liquid pipe Gas pipe Main pipe 1st branching section Branching pipe Branching header Indoor unit Indoor unit Branching pipe Y shaped branching joint PMV Kit Outdoor unit capacity type Gas pipe Liquid pipe 0404 type 15 9 9 5 050...

Страница 22: ...5 018 024 027 030 036 048 056 Capacity code Equivalent to HP 0 8 0 8 1 0 1 25 1 7 2 0 2 5 3 0 3 2 4 0 5 0 6 0 Indoor unit model name 4 way cassette MMU AP H 0 4 0 4 0 8 0 8 0 8 0 8 0 8 1 2 1 2 1 2 MMU AP MH 0 4 0 4 0 4 0 4 0 6 0 6 2 way cassette MMU AP WH 0 4 0 4 0 4 0 5 0 7 0 7 0 7 0 7 1 1 1 1 1 1 1 way cassette MMU AP YH SH 0 4 0 4 0 4 0 5 0 5 0 6 Duct MMD AP BH 0 3 0 3 0 3 0 5 0 5 0 8 0 8 0 8 1...

Страница 23: ...ming of the refrigerant pipe has finished For the wiring of power to indoor units and that between indoor and outdoor units follow the instructions in the installation manual of each indoor unit 4 2 Electrical wiring design Determine the wire size for the indoor unit according to the number of connected indoor units downstream 4 3 Outdoor unit power supply Electrical characteristics MCA Maximum Ci...

Страница 24: ...0 072 1 15 1 44 15 MMU AP0564HP E 230 1 50 198 264 0 072 1 15 1 44 15 Compact 4 way Cassette 600 x 600 Type MMU AP0054MH E 230 1 50 198 264 0 060 0 32 0 40 15 MMU AP0074MH E 230 1 50 198 264 0 060 0 32 0 40 15 MMU AP0094MH E 230 1 50 198 264 0 060 0 35 0 44 15 MMU AP0124MH E 230 1 50 198 264 0 060 0 36 0 45 15 MMU AP0154MH E 230 1 50 198 264 0 060 0 48 0 60 15 MMU AP0184MH E 230 1 50 198 264 0 060...

Страница 25: ...230 1 50 198 264 0 060 0 38 0 48 15 MMD AP0184SPH E 230 1 50 198 264 0 060 0 47 0 59 15 Ceiling Type MMC AP0154H E 230 1 50 198 264 0 030 0 33 0 41 15 MMC AP0184H E 230 1 50 198 264 0 030 0 37 0 46 15 MMC AP0244H E 230 1 50 198 264 0 040 0 48 0 60 15 MMC AP0274H E 230 1 50 198 264 0 040 0 48 0 60 15 MMC AP0364H E 230 1 50 198 264 0 080 0 90 1 13 15 MMC AP0484H E 230 1 50 198 264 0 080 0 96 1 20 15...

Страница 26: ...50 198 264 0 019 0 29 0 36 15 MML AP0124BH E 230 1 50 198 264 0 019 0 29 0 36 15 MML AP0154BH E 230 1 50 198 264 0 070 0 52 0 65 15 MML AP0184BH E 230 1 50 198 264 0 070 0 52 0 65 15 MML AP0244BH E 230 1 50 198 264 0 070 0 53 0 66 15 Floor Standing Type MMF AP0154H E 230 1 50 198 264 0 037 0 77 0 96 15 MMF AP0184H E 230 1 50 198 264 0 037 0 77 0 96 15 MMF AP0244H E 230 1 50 198 264 0 063 1 01 1 27...

Страница 27: ...he end of terminal Use 2 core non polarity wire for remote controller A B terminals Use 2 core non polarity wire for wiring of group control A B terminals U1 U2 U3 U4 U1 U2 U3 U4 U1 U2 A B 2 U B A U1 U2 U1 A 2 U B U1 A B B A B A B A Central controller Outdoor unit Control wiring between indoor and outdoor unit Shield wire Control wiring between indoor units Shield wire Indoor unit Indoor unit Indo...

Страница 28: ... Up to 1000 m 2 0 mm2 Up to 2000 m Wiring 2 core non polarity Type Shield wire Size Length 1 25 mm2 to 2 0 mm2 Up to 100 m L5 Wire 2 core Size 0 5 mm2 to 2 0 mm2 Length Up to 500 m L6 L7 Up to 400 m with of wireless remote controller in group control Up to 200 m total length of control wiring between indoor units L6 U3 U4 U1 U2 U1 U3 U2 U4 U1 U2 A B U3 U4 U1 U2 U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 ...

Страница 29: ...EER 4 20 4 00 3 56 Heating Running current A 13 3 12 8 12 2 18 0 17 3 16 5 21 3 20 4 19 5 Power consumption kW 2 73 3 81 4 50 Power factor 93 96 96 COP 4 58 4 20 4 00 Starting Current A Soft start Soft start Soft start Dimension Unit Height mm 1 235 1 235 1 235 Width mm 990 990 990 Depth mm 390 390 390 Packing Height mm 1 350 1 350 1 350 Width mm 1 102 1 102 1 102 Depth mm 552 552 552 Total Weight...

Страница 30: ...29 5 Outdoor unit 5 2 Dimensional drawing MCY MHP0404HT E MCY MHP0504HT E MCY MHP0604HT E ...

Страница 31: ... side 700 90 83 6 22 2 15 9 7 x 8 x 8 x 1 x 1 x 1 Liquid side 680 60 15 9 9 5 7 x 8 x 1 x 1 Model A B øC øD Accessory socket Qty RBM BY55E Gas side 160 80 15 9 15 9 x 1 x 2 x 2 Liquid side 130 70 9 5 9 5 x 2 Gas side Liquid side Gas side Liquid side Outer dia Outer dia Outer dia Outer dia 369O 1 dh A B C D 58 9 5 12 7 15 9 71 15 9 19 1 22 2 80 22 2 25 4 28 6 87 25 4 28 6 31 8 95 28 6 31 8 38 1 A B...

Страница 32: ...rmo Solenoid valve SV5 Strainer PMV Strainer Sensor TL Liquid side packed valve Gas side ball valve Compressor Strainer Sensor TD 4 Way valve Sensor TS Solenoid valve Solenoid valve Capillary tube Check joint Muffler High pressure sensor Check joint Low pressure sensor Accumulator High pressure SW ...

Страница 33: ...32 5 Outdoor unit 5 5 Wiring diagram MCY MHP0404HT E MCY MHP0504HT E MCY MHP0604HT E ...

Страница 34: ...ection of shield wire must be connected Connected to all connecting sections in each Indoor unit 3 Group control 4 Select the power supply wiring and fuse of outdoor indoor units according to each models specification Perform wiring of power supply complying with the rules and regulations of the local electric company 5 Fro the control wires connecting indoor units outdoor units and between indoor...

Страница 35: ...y Optional PCB Display relay Shield wire Shield wire SW07 bit 2 OFF 2 stage switching Input SW07 bit 1 Display relay L1 SW1 SW2 Bit 1 OFF Bit 1 ON OFF ON 100 normal operation 100 normal operation OFF ON OFF 0 forced stop Approx 60 upper limit regulated ON PJ17 TB1 ON OFF TB2 COM ON COM OFF CN513 SW07 Bit 2 ON L1 SW1 ON OFF 1 2 3 4 SW2 Outdoor unit interface PCB Connection cable attached in this op...

Страница 36: ...stricted while the signal of the night operation control is input It makes the noise reduction during the night time operation SW1 Night time signal switch Each terminal should be connected to dry contact The input signal is recognized during its rising falling phase After reaching the top bottom of the rising falling edge the signal must remain there for at least 100 ms Model name Appearance Func...

Страница 37: ...Cooling Heating Relative to maximum capacity Model 0404 47 50 approx 85 approx 95 Model 0504 47 50 approx 80 approx 80 Model 0604 50 50 approx 80 approx 70 7 1 J P TB1 SW1 SW2 COM HEAT COOL Outdoor unit interface PCB Connection cable attached in this optional PCB Locally procured Optional PCB Shield wire CN510 Input Signal Operation Selected operation mode Cooling SW1 Heating SW2 ON OFF Cooling op...

Страница 38: ...door unit Model name Appearance Function OUTPUT1 PJ20 OUTPUT2 OUTPUT3 TB1 L1 L2 1 2 5 6 4 3 C1 PS PS K1 K2 1 ON OFF 2 3 4 SW16 Outdoor unit interface PCB Optional PCB Locally procured Shield wire CN511 C1 Attached connection cable 1 4wires CN511 Connector on interface side green K1 K2 Relays L1 Error indication Lamp L2 Operation indication Lamp OUTPUT1 Error output OUTPUT2 Operation output PJ20 Co...

Страница 39: ...MS 10 MS OFF COM COM ON ON T82 T81 K100 PJ17 5 5 ICI 4 1 8 OPERATION TOSHIBA NCC 1212 Terminal Screw M3 6 55 5 45 5 60 50 PJ17 TOSHIBA NCC 1214 4 4ø hole 5 4 1 ICI 4 1 D2 HEAT COM COM COOL 10 TB1 8 C4 C2 C3 K1 1 2 OUTPUT1 OUTPUT2 OUTPUT3 3 4 5 6 K2 1 PJ20 5 K3 TB1 MCC 1613 02 3 D 2 D 1 D 63 73 69 79 4 4 mm dia mounting holes Terminal block M3 ...

Страница 40: ... 9 1 46 9 7 1 22 8 5 1 00 7 3 0 80 6 1 0 63 20 12 1 12 1 1 66 10 9 1 41 9 7 1 18 8 5 0 97 7 3 0 78 6 1 0 61 19 12 1 12 1 1 60 10 9 1 36 9 7 1 14 8 5 0 93 7 3 0 75 6 1 0 59 17 12 1 12 1 1 48 10 9 1 26 9 7 1 06 8 5 0 87 7 3 0 71 6 1 0 56 15 12 1 12 1 1 38 10 9 1 18 9 7 0 99 8 5 0 82 7 3 0 66 6 1 0 52 Heating Compressor Outdoor Fan Power consumption kW Outdoor Unit Outdoor Unit 100 Heating Capacity k...

Страница 41: ... 1 16 8 4 0 92 7 0 0 72 20 14 0 14 0 1 97 12 6 1 66 11 2 1 38 9 8 1 12 8 4 0 89 7 0 0 69 19 14 0 14 0 1 89 12 6 1 60 11 2 1 33 9 8 1 08 8 4 0 86 7 0 0 67 17 14 0 14 0 1 75 12 6 1 48 11 2 1 24 9 8 1 01 8 4 0 81 7 0 0 63 15 14 0 14 0 1 62 12 6 1 38 11 2 1 15 9 8 0 94 8 4 0 76 7 0 0 59 Heating Compressor Outdoor Fan Power consumption kW Outdoor Unit Outdoor Unit 100 Heating Capacity kW 100 90 80 70 6...

Страница 42: ...49 9 3 1 17 7 8 0 90 20 15 5 15 5 2 57 14 0 2 16 12 4 1 78 10 9 1 44 9 3 1 14 7 8 0 87 19 15 5 15 5 2 48 14 0 2 09 12 4 1 72 10 9 1 40 9 3 1 10 7 8 0 85 17 15 5 15 5 2 31 14 0 1 95 12 4 1 61 10 9 1 31 9 3 1 04 7 8 0 80 15 15 5 15 5 2 16 14 0 1 82 12 4 1 51 10 9 1 23 9 3 0 98 7 8 0 75 Heating Compressor Outdoor Fan Power consumption kW Outdoor Unit Outdoor Unit 100 Heating Capacity kW 100 90 80 70 ...

Страница 43: ...20 Audibility limits of continuous white noise Octave band sound pressure level dB A Octave band center frequency Hz MCY MHP0604HT E Sound pressure level dB A Cooling Heating 52 55 Octave band sound pressure level dB A Octave band center frequency Hz 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 Cooling Heating NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 Audibility limits of continuous whi...

Страница 44: ...0 500 1000 2000 4000 8000 NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 Audibility limits of continuous white noise Cooling Heating MCY MHP0604HT E Sound pressure level dB A Cooling Heating 48 50 Octave band sound pressure level dB A Octave band center frequency Hz 10 20 30 40 50 60 70 80 90 63 125 250 500 1000 2000 4000 8000 Cooling Heating NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 Audibility limits of continuou...

Страница 45: ...or unit capacity type Diameter of refrigerant pipe RBM PMV0362E 005 to 014 type ø6 4 RBM PMV0902E 015 to 018 type ø6 4 020 to 027 type ø9 5 Allowable length of refrigerant piping PMV Kit Indoor unit PMV Kit Refrigerant pipe 2 m to 10 m Indoor unit PMV Kit NO GOOD OK Indoor unit Note Do not connect two or more indoor units to one PMV Kit Arrange one indoor unit and one PMV Kit set to 1 by 1 Label M...

Страница 46: ...s used High Wall Type 3 series MMK AP 3H Mount the clamp filter Accessory to the connection wire 11 m out of the PMV kit main body Refer to the mounting method Remove the connector conversion cable mounted to the connection cable out of the PMV kit main body and then connect it The additional clamp filter is not used for the indoor unit but the connector conversion cable is used Indoor unit except...

Страница 47: ...0 RBM PMV0902E When attached joint is used RBM PMV0362E RBM PMV0902E 200 or more 55 55 50 or more Box cover Check port 450 x 450 500 or more 200 or more 200 or more 73 73 or more 50 50 or more Binding band L Binding band M Installation image Binding band M Binding band L Binding band M Refrigerant pipe Gas side Heat insulating pipe Heat insulating pipe Refrigerant pipe Liquid side Refrigerant pipe...

Страница 48: ...Side blow VRF 4 6HP Engineering Data Book May 2014 First Edition ...