HX7+ ASD Installation and Operation Manual
Speed Loop Proportional Gain
Program
Feedback Parameters
PG Settings
This parameter sets the
Proportional Gain
(sensitivity) of the drive when
monitoring the
PG
signal to control speed. The larger the value entered here,
the more sensitive the drive is to changes in the received feedback and the
quicker it responds.
Direct Access Number — F376
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 3.2
Maximum — 1000
Speed Loop Integral Gain
Program
Feedback Parameters
PG Settings
This parameter sets the response time of the
Speed Loop Integral Gain
. The
smaller the value here, the more pronounced (quicker) the effect of the integral
function.
Direct Access Number — F377
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 200.0
Motor Counter Data
Program
Feedback Parameters
PG Settings
This parameter sets the pulses-per-revolution displayed at the Monitor screen
when using a shaft-mounted encoder for speed control. This setting is used for
display purposes only and does not affect the speed control of the system.
If zero is selected here then the setting at
(Electronic Gear Setting)
determines the pulses-per-revolution to be displayed at the Monitor screen.
Settings:
Selection 0
setting
Selection 1
— 256 pulses/revolution
Selection 2
— 512 pulses/revolution
Selection 3
— 1024 pulses/revolution
Selection 4
— 2048 pulses/revolution
Selection 5
— 4096 pulses/revolution
Direct Access Number — F378
Parameter Type —
Selection List
Factory Default —
Selection 0
Changeable During Run —
No
Minimum — Selection 0
Maximum — Selection 5
Speed Loop Parameter Ratio
Program
Feedback Parameters
PG Settings
Contact the
Toshiba Customer Support Center
for information on this
parameter.
Direct Access Number — F379
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
No
Minimum — 0.01
Maximum — 10.00
Use Speed Mode
Program
Pattern Run
Preset Speed Mode
This parameter
Enables/Disables
the
Use Speed
mode. When enabled, the
system uses all of the parameter settings of the
Preset Speed
being run.
Otherwise, only the frequency setting is used.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F380
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...