background image

EN

EN

FR

IT

DE

PT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

11

Air to water heat pump 

operating conditions

OTHERS

OTHERS

Gas Leak Test

Finishing

After the refrigerant pipe, Hydro / Outdoor connecting wires have been 
connected, cover them with 

fi

 nishing tape and clamp them to the wall with 

off-the-shelf support brackets or their equivalent.   
Keep the power wires and Hydro / outdoor connecting wires off the valve on 
the gas side or pipes that have no heat insulator.

Earthing

Connect the earth wire properly following applicable technical standards.
Connecting the earth wire is essential to preventing electric shock and to 
reducing noise and electrical charges on the outdoor unit surface due to the 
high-frequency wave generated by the frequency converter (inverter) in the 
outdoor unit. 
If you touch the charged outdoor unit without an earth wire, you may 
experience an electric shock.

Test run

Annual maintenance

•  Turn on the leakage breaker at least 12 hours before starting a test run to 

protect the compressor during startup.

•  Check the following before starting a test run: 

  That all pipes are connected securely without leaks.

•  That the valve is open.

If the compressor is operated with the valve closed, the outdoor unit will 
become overpressurized, which may damage the compressor or other 
components.
If there is a leak at a connection, air can be sucked in and the internal 
pressure further increases, which may cause a burst or injury.

•  Operate the air to water heat pump in the correct procedure as speci

fi

 ed 

in the Owner’s Manual.

Please refer to the Hydro unit installation manual for the detail of the test 
run.

•  For an air to water heat pump system that is operated on a regular basis, 

cleaning and maintenance of the Hydro / outdoor units are strongly 
recommended.
As a general rule, if an Hydro unit is operated for about 8 hours daily, the 
Hydro / outdoor units will need to be cleaned at least once every 
3 months.
This cleaning and maintenance should be carried out by a quali

fi

 ed 

service person.
Failure to clean the Hydro / outdoor units regularly will result in poor 
performance, icing, water leaking and even compressor failure. 

For proper performance, operate the air to water heat pump under the 
following temperature conditions: 

Cooling operation

10 °C to 43 °C

Heating operation

-20 °C to 25 °C

Hot water operation

-20 °C to 43 °C*

If air to water heat pump is used outside of the above conditions, safety 
protection may work. 
*  Heater operation in more than 35 °C 

Check places for
the hydro unit.

Check places for
the outdoor unit.

• Check the 

fl

 are nut connections for the gas leak with a gas leak detector or

soap water.

01_1120551201-1 EN.indd   11

01_1120551201-1 EN.indd   11

5/18/2560 BE 3:12 PM

5/18/2560 BE   3:12 PM

Содержание HWS-455H-E

Страница 1: ...Outdoor unit HWS 455H E AIR TO WATER HEAT PUMP INSTALLATION MANUAL ENGLISH ...

Страница 2: ...Refrigerant Piping Connection Evacuating ELECTRICAL WORKS Wiring Connection Power Supply and Connecting Cable Connection Power supply input Wiring Diagram OTHERS Gas Leak Test Earthing Finishing Test run Annual maintenance Air to water heat pump operating conditions CONTENTS EN 1 7 7 7 8 8 9 10 10 10 10 11 11 11 11 11 11 11 ...

Страница 3: ...se of this unit can result in a high possibility of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 2 or property damage 3 1 A severe injury refers to blindness injury burns hot or cold electrical shock bone fracture or poisoning that leaves aftereffects and...

Страница 4: ...e sizes of charging port connecting sections on the main unit are different from those for the conventional refrigerant and different size tools are also required For connecting pipes use new and clean piping materials with high pressure withstand capabilities designed for R410A only and ensure that water or dust does not enter Moreover do not use any existing piping as its pressure withstand may ...

Страница 5: ... RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR TO WATER HEAT PUMP FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AN...

Страница 6: ...he hydro outdoor units Midway connection stranded wire and single wire connections are not allowed Improper connection or fixing may cause a fire Wiring between the hydro unit and outdoor units must be well shaped so that the cover can be firmly placed Improper cover installation may cause increased heat fire or electrical shock at the terminal area Be sure to use only approved accessories or the ...

Страница 7: ...air absorbed and abnormal high pressure inside the refrigeration cycle and resulting burst or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock Do not use any refrigerant different from the one specified for complement or replacement Oth...

Страница 8: ...harged Improper drainage can result in water leakage causing water damage to furniture Tighten the flare nut with a torque wrench using the prescribed method Do not apply excess torque Otherwise the nut may crack after a long period of usage and it may cause the leakage of refrigerant Wear gloves heavy gloves such as cotton gloves for installation work Failure to do so may cause personal injury wh...

Страница 9: ...ION DIAGRAM OF OUTDOOR UNITS INSTALLATION DIAGRAM OF OUTDOOR UNITS Part code Parts name Q ty A Refrigerant piping Liquid side Ø6 35 mm Gas side Ø12 7 mm One each B Pipe insulating material polyethylene foam 6 mm thick 1 C Putty PVC tapes One each Optional Installation Parts 600 mm or more 100 mm or more 100 mm or more 600 mm or more 600 mm or more Remark Some pictures might be different from the a...

Страница 10: ... A place full of machine oil A saline place such as the coast A place full of sulfide gas A place where high frequency waves are likely to be generated as from audio equipment welders and medical equipment Strong wind Incused line Flare at hydro unit side Flare at outdoor unit side Flare nut Half union Externally threaded side Internally threaded side Use a wrench to secure Use a torque wrench to ...

Страница 11: ...d liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Using a vacuum pump Packed valve at liquid side Service port Valve core Setting pin Packed valve at gas side Vacuum pump Vacuum pump adapter for counter flow prevention For R410A only Charge hose For R410A only Handle Hi Keep full closed Manifold valve Pressure gauge Compound pressure g...

Страница 12: ... Block 0 1 0 1 0 1 0 1 30 30 40 40 L N 1 2 3 1 2 3 L N Connecting cable Earth line Earth line Connecting cable Connecting cable connect to terminal block 1 2 3 Power supply terminal block L N Power cord Power cord Terminal block CAUTION 1 The power supply must be same as the rated of air to water heat pump 2 Prepare the power source for exclusive use with air to water heat pump 3 Circuit breaker m...

Страница 13: ...d which may damage the compressor or other components If there is a leak at a connection air can be sucked in and the internal pressure further increases which may cause a burst or injury Operate the air to water heat pump in the correct procedure as specified in the Owner s Manual Please refer to the Hydro unit installation manual for the detail of the test run For an air to water heat pump syste...

Страница 14: ......

Отзывы: