210
GX9 ASD Installation and Operation Manual
Transducer Maximum Reading
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the maximum level of the transducer range for
Virtual Linear
Pump
operation.
Note:
The unit of measure for this parameter is selected at the
. The default setting is PSI.
Direct Access Number — F916
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — -3276.7
Maximum — 3276.7
Virtual Linear Pump Minimum
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the minimum setpoint within the
Virtual Linear Pump
operating
domain.
Direct Access Number — F917
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum — 10.00
Maximum —
Setting
Virtual Linear Pump Maximum
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the maximum setpoint within the
Virtual Linear Pump
operating
domain.
Direct Access Number — F918
Parameter Type —
Numerical
Factory Default —
10.00
Changeable During Run —
Yes
Minimum —
Setting
Maximum — 200.00
Virtual Linear Pump Low Frequency Limit
Program
Virtual Linear Pump
Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the
Virtual Linear Pump
Low Frequency Limit
.
Direct Access Number — F919
Parameter Type —
Numerical
Factory Default —
15.00
Changeable During Run —
Yes
Minimum — 10.00
Maximum — 60.00
Units — Hz
Virtual Linear Pump Command Source
Program
Virtual Linear Pump
Settings
During
Direct
mode or the
Process Hold
mode operation, this parameter sets
the
Virtual Linear Pump
command source.
Settings:
0 — EOI
1 — *VI/II
2 — RR
3 — Communication Option
Note:
Selecting
VI/II
here will result in an error message if
Process
Hold
Direct Access Number — F920
Parameter Type —
Selection List
Factory Default —
EOI
Changeable During Run —
No
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......