198
GX9 ASD Installation and Operation Manual
Low Output Disable Start Level (Hz)
Program
Special
Low Output Disable Function
The
Low Output Disable Start Level
sets the output frequency threshold that,
if exceeded, will initiate the
LOD
function if properly configured.
Direct Access Number — F732
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Low Output Disable Start Time
Program
Special
Low Output Disable Function
The
Low Output Disable Start Time
sets the amount of time that the
LOD
Start Level
criteria must be met and maintained for the
LOD
function to be
initiated.
Direct Access Number — F733
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Setpoint Boost (Hz)
Program
Special
Low Output Disable Function
The
Low Output Disable
feature adds the user-input frequency value to the
commanded frequency.
Direct Access Number — F734
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Low Output Disable Boost Time
Program
Special
Low Output Disable Function
The
Low Output Disable
Boost Time
sets the on-time timer for the
LOD
Boost
function.
Once expired, the
LOD Boost
function ceases.
Direct Access Number — F735
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Low Output Disable Feedback Level (Hz)
Program
Special
Low Output Disable Function
The
Low Output Disable Feedback Level
sets a frequency level that, until the
output of the ASD drops below this setting, the
Restart Delay Timer
does not
start.
Direct Access Number — F736
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Low Output Disable Restart Delay Time
Program
Special
Low Output Disable Function
The
Low Output Disable Restart Delay Time
sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Direct Access Number — F737
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......