6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 921 -
Binary IO module (BI, BO, and BIO)
Binary IO modules are provided in the IED to signal a command for external devices. Binary
IO modules are also used to receive status information. Binary IO modules are connected to
external devices with signal wires using terminal blocks on the rear of the IED. There are
standard type and variable type in Binary IO modules as shown in Table 5.4-1.
Table 5.4-1 Number of input and output circuits
1
#
Module
name
3
Module
Type
4
Number of
input
circuits
Number of output circuits
2
Fast
operating
Semi-fast
operating
Hybrid
Auxiliary
(Normal)
Form C
1
BI1A
Standard
18
0
0
0
0
0
2
BI2A
Variable
12
0
0
0
0
0
3
BI3A
Standard
32
0
0
0
0
0
4
BO1A Standard
0
0
6
0
12
0
5
BO2A Standard
0
0
0
16
0
0
6
BIO1A Standard
7
0
6
0
3
1
7
BIO2A Standard
12
0
3
0
1
1
8
BIO3A Standard
8
6
0
0
1
1
1
Note: PWS module supplies a DC voltage for binary IO modules: 48Vdc or 220Vdc.
Hence, the BIOs output circuits operate with the supplied DC voltage. Dual
voltages output (i.e., 48Vdc and 220Vdc) is not possible in the binary IO
modules.
2
Note: For the structure and the number of binary IO modules, see section 5.4.5.
3
Note: For details of the output circuits, see Table 5.4-8.
4
Note: For the binary input circuits in the standard type, the user can choice either
a high voltage or a low voltage with regard to the input threshold. For the
ones of the variable type, the user itself can set a threshold value with regard
to input voltage using settings.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......