6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 868 -
4.10.2
Mapping for IEC61850 communication
Sending a report to the client is possible after the mapping is performed for IEC 61850
communication using GR-TIEMS. The user should proceed as follows,
Step1:
Editing Logical Node
Step2:
Mapping output data
(i)
Editing Logical Node
The user must make a logical node (LN) for the GENBI function. Figure 4.10-4 exemplifies LN
making; LN “GGIO101” is selected for the GENBI function. After editing, the GENBI logical
node can be saved with the name “GGIO101”. Object “Ind1” is defined in the GENBI function.
Figure 4.10-4 Defining “Ind1” object in GGIO101 logic node
(ii)
Mapping output data
With the IEC 61850 communications standard a GOOSE message can be used to send a signal
to a client. The user will need to collect the signals corresponding to the GENBI function and
then map them for IEC 61850 communication using GR-TIEMS.
Table 4.10-5 shows the mapping signals that are required within the GENBI function for
IEC 61850 communications. Figure 4.10-5 shows how to map a signal.
Table 4.10-5 Mapping signals for Ind1 object in GENBI function
Object_reference
Attribute
Type
FC Signal Number
Signal Name
Ctrl/GGIO101$Ind1
stVal
BOOLEAN
ST
580001 0010001001
SLOT1 GBI01_STATE
Ctrl/GGIO101$Ind1
q
Quality
ST
580001 3110001005
SLOT1 GBI01_QUALITY
Ctrl/GGIO101$Ind1
t
Timestamp
ST
580001 9010001006
SLOT1 GBI01_TIMESTAM
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......