6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 809 -
at the monitoring point “TPOS01_CC_SS”, when the TPOS01 function determines that the
“Local-Cancel” signal is true.
(iii)
Cancel condition logic
Figure 4.9-25 shows the cancel condition logic. As the criteria “Unmatched condition detected”
is connected normally for the cancel condition logic, set
Fixedlogic
for the scheme switch
[
TPOS01-LGCNFFCT
].
TPOS01 function (Function ID: 513001)
User configurable condition (PLC connection point)
Fixedlogic
[
TPOS01-LGCNFFCT
]
To cancel logic in
TPOS01
Unmatched condition detected *1
TPOS01IN_TMP_40
513001 800401EE69
&
&
1
≥
Figure 4.9-25 Logic “Cancel condition” in TPOS01
1
Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”, like in Figure 4.9-20.
2
Note: With the exception of the above ‘cancel’ logic, there is an operate-condition logic
within the TPOS01 function; the operate-condition logic will always checks
conditions. That is, the user is required to set either the “Operate-condition” or the
“cancel-condition” logic.
If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point “User Configurable condition”:
Connect the user-customized logic, with the “TPOS01IN_TMP_40”, which is listed
in Table 4.9-12.
Set scheme switch [
TPOS01-LGCNFFCT
] to
PLC
.
(iv)
Signal name and number
Note: The user should note the following descriptions shown in the column “M/O” in
each table:
“O” indicates that the signal is provided for the optional use.
“M” indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure for the default
settings.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.9-12 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number
Signal Name
Description
M/O
513001 800401EE69
TPOS01IN_TMP_40
TPOS1 user configurable cancel condition
O
513001 800401EE69
TPOS02IN_TMP_40
TPOS2 user configurable cancel condition
O
513001 800401EE69
TPOS03IN_TMP_40
TPOS3 user configurable cancel condition
O
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......