6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 807 -
4.9.2
Cancel logic for SBO mode
In the SBO control mode, the reception of a cancel command can be possible when the cancel
conditions are satisfied, the function can discard the select command; finally, the operation
returns to the initial stage (i.e., “wait for a command”).
(i)
Receiving “Cancel” from the remote-end
Figure 4.9-21 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Signal reception in
IEC61850
Cancel from remote-end
Do nothing
Cancel
decision
Success
Failed
Cancel logic
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P2 control by the PLC function
Wait for a command
Operate logic
Operate command
Operate logic
P1 control from the remote-end
P3 control by the PLC function
Select stage
Cancel from the local-end
Wait for a next command
Figure 4.9-21 Outline of ‘cancel’ command from remote-end
Input point required mapping
Figure 4.9-22 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the TPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the “Selection command P1 (Remote-P1-Control)” signal.
TPOS01 function (Function ID: 513001)
“TPOS01_ CC_SS”
(513001
_
8604011E95)
DEV01_CONTROL_REQ
Cancel command
Command
“Remote-cancel”
513001
_
7004016D08
510001 7001016D08
Input
Output
Cancel logic in TPOS01
Cancel condition
†
&
&
Successes to cancel
Operation Failed
“TPOS01_CC_FS”
(513001
_
8704011E96)
“Do nothing”
To
“Wait for a command”
Figure 4.9-22 ‘Cancel’ from the remote-end in TPOS01
†Note: The logic “cancel condition” is shown in Figure 4.9-25.
Output signal to BO
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......