6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 794 -
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
††
Note: To identify the input/output signals of the other TPOS logics, see Table 4.9-6,
Table 4.9-7, and Table 4.9-10.
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue “Select success”
signal at the output-point “TPOS01_P2SL_BO_FLG”.
1
Note: The “TPOS01_P2SL_BO_FLG” signal is the same as the signal shown in Figure
4.9-5. If the “Local-P2-Control” signal is not true, the TPOS01 function returns to
the “Wait for a command” stage.
(vi)
Receiving “Select command P3-control” from the local-end
Figure 4.9-12 outlines the reception of the select command ‘P3-control’ from the local-end.
Keying
“Select
command
”
P3control from the local-end
Signal output
Select
decision
Success
Failed
Selection logic
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Select stage
Cancel logic
Wait for a command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
P1 control from the remote-end
Figure 4.9-12 Outline of select command ’P3-control’
Input signal generated at the local-end
Figure 4.9-13 shows the select logic when a “Select command (Local-P3-Control)” signal is
applied to the TPOS01 function. The signal is provided when the user press a “Local-P3-control”
key on the IED front panel; the user is not required to take account of mapping.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...