6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 719 -
4.8.1
Select logic for SBO/DIR modes
The user should set scheme switch [
DPOS01-CTREN
] to
On
prior to DPOS01 operation. Table
4.8-10 shows all of the scheme switches in the DPOS function.
(i)
Receiving “Select command On” from the remote-end
Figure 4.8-1 outlines the reception of the select command ‘On’ from the remote-end.
Signal reception
IEC61850
Select command On from the remote-end
Signal output
Select
decision
Success
Failed
Selection logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from the remote-end
Select command On from the local-end
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Figure 4.8-1 Outline of Select command ‘On’
Input point required mapping
Figure 4.8-2 shows the Select logic when a “Select command On (Remote-ON-Control)” signal
is applied to the DPOS01 function. The logic has the input-point “DEV01_CONTROL_REQ”
for the reception of the select command. That is, the input-point must be mapped for IEC61850
communication. The function will fail to operate if mapping is not performed correctly. We will
discuss how to map the input-points for IEC61850 communication in section 4.8.7.
Output signal to BO
The DPOS01 function can issue a “Select success” signal at the output point
“DPOS01_OSL_BO_FLG”, when the DPOS01 function determines that the “Remote-ON-
Control” signal is true. If the DPOS01 function determines that the “Remote-ON-Control”
signal is not true, the DPOS01 function returns to the “Wait for a command” stage.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......