6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 678 -
Δ
Δ
reducing
Δ
increasing
Δ
near
zero
Vr†
Vi‡
Vi
Vi
Vi
Figure 4.6-4 Permissible ranges for connections between asynchronous networks
†
Note: Vr is the voltage on a running line.
‡
Note: Vi is the voltage on an incoming line.
Table 4.6-3 Settings in SYNCHK_Ry1
Setting Name
Description
Default
Setting item or value
SyncRy1-Angle
Checking angle variance
30 degrees
0 to 75 degrees
SyncRy1-dV
Checking voltage variance
150V
0 to 150 V
SyncRy1-df
Checking frequency variance
1Hz
0.01 to 2 Hz
SyncRy1-TCB
Advance time for SYNCHK01
–
Seconds
SYNC01_TSYN
Sync check timer for loop system
10s
0.00 to 100.00 s
SyncRy1-dfEN
Diff. frequency for the checking SyncRy1 enable
Off
Off / On
(i)
Synchronism-relays (SyncRy1-dV, SyncRy1-df, SyncRy1-d
θ
)
Synchronism-relays, SyncRy1-dV, SyncRy1-df, and SyncRy1-dθ are provided; the setting
ranges for these relays are shown in Table 4.6-3.
Voltage-variance (
Δ
The voltage-variance between Vr and Vi (
|𝑉
𝑟
− 𝑉
𝑖
|
) is measured by the voltage-variance relay-
element having a setting [
SyncRy1-dV
]. If equation (4.6-3) is satisfied together with the
conditions stipulated in equations (4.6-2) and (4.6-3), the SyncRy1-dV relay determines that
the voltage-variance is inside the permissible range.
𝑉
r
≥ Setting [
OVR1
]
(4.6-1)
𝑉
i
≥ Setting [
OVI1
]
(4.6-2)
|𝑉
𝑟
− 𝑉
𝑖
| ≤ Setting [
SyncRy1-dV
]
(4.6-3)
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......